GMI D1010S Instruction Manual

D1010 - SIL 2 Repeater Power Supply Smart-Hart compatible ISM0007-16
D1010S - D1010D
SIL 2 Repeater Power Supply
Smart-Hart compatible
DIN-Rail Models D1010S, D1010D
INSTRUCTION & SAFETY MANUAL

2 D1010 - SIL 2 Repeater Power Supply Smart-Hart compatible G.M. International ISM0007-16
General Description: The single and dual channel DIN Rail Repeater Power Supply, D1010S and D1010D, provides a fully floating dc supply for energizing conventional 2 wires
4-20 mA transmitters, or separately powered 3, 4 wires 4-20, 0-20 mA transmitters located in Hazardous Area, and repeats the current in floating circuit to drive a Safe Area load.
The circuit allows bi-directional communication signals, for Hart-Smart transmitters.
Function: 1 or 2 channels I.S. analog input for 2 wires loop powered or separately powered Smart transmitters, provides 3 port isolation (input/output/supply) and current (source or sink)
or voltage output signal.
Signalling LED: Power supply indication (green).
Field Configurability: mA (source or sink) or V output signal.
Smart Communication Frequency Band: 0.5 to 40 KHz within 3 dB (Hart and higher frequency protocols).
EMC: Fully compliant with CE marking applicable requirements.
Functional Safety Management Certification:
G.M. International is certified by TUV to conform to IEC61508:2010 part 1 clauses 5-6 for safety related systems up to and included SIL3.
Technical Data
Characteristics
Supply: 24 Vdc nom (20 to 30 Vdc) reverse polarity protected, ripple within voltage limits 5 Vpp.
Current consumption @ 24 V: 115 mA for 2 channels D1010D, 60 mA for 1 channel D1010S with 20 mA output typical.
Power dissipation: 1.9 W for 2 channels D1010D, 1.0 W for 1 channel D1010S with 24 V supply voltage and 20 mA output typical.
Max. power consumption: at 30 V supply voltage and short circuit condition, 3.7 W for 2 channels D1010D, 2.0 W for 1 channel D1010S.
Isolation (Test Voltage): I.S. In/Out 1.5 KV; I.S. In/Supply 1.5 KV; I.S. In/I.S. In 500 V; Out/Supply 500 V; Out/Out 500 V.
Input: 0/4 to 20 mA (separately powered input, voltage drop 0.9 V) or 4 to 20 mA (2 wire Tx current limited at 25 mA).
Transmitter line voltage: 15.0 V at 20 mA with max. 20 mVrms ripple on 0.5 to 40 KHz frequency band.
Output: 0/4 to 20 mA, on max. 600 load in source mode; V min. 5 V at 0 load V max. 30 V in sink mode, current limited at 23 mA or 0/1 to 5 V on internal 250 shunt
(or 0/2 to 10 V on internal 500 shunt on request).
Response time: 50 ms (10 to 90 % step change).
Output ripple: 20 mVrms on 250 communication load on 0.5 to 40 KHz band.
Frequency response: 0.5 to 40 KHz bidirectional within 3 dB (Hart and higher frequency protocols).
Performance: Ref. Conditions 24 V supply, 250 load, 23 ± 1 °C ambient temperature.
Calibration accuracy: ± 0.1 % of full scale.
Linearity error: ± 0.05 % of full scale.
Supply voltage influence: ± 0.05 % of full scale for a min to max supply change.
Load influence: ± 0.05 % of full scale for a 0 to 100 % load resistance change.
Temperature influence: ± 0.01 % on zero and span for a 1 °C change.
Compatibility:
CE mark compliant, conforms to Directive: 2014/34/EU ATEX, 2014/30/EU EMC, 2014/35/EU LVD, 2011/65/EU RoHS.
Environmental conditions: Operating: temperature limits -20 to + 60 °C, relative humidity max 95%.
Storage: temperature limits – 45 to + 80 °C.
Safety Description:
ATEX: II (1)G [Ex ia Ga] IIC, II (1)D [Ex ia Da] IIIC, I (M1) [Ex ia Ma] I; II 3G Ex nA IIC T4 Gc
IECEx / INMETRO: [Ex ia Ga] IIC, [Ex ia Da] IIIC, [Ex ia Ma] I; Ex nA IIC T4 Gc
UL: NI / I / 2 / ABCD / T4, AIS / I, II, III / 1 / ABCDEFG, AEx nC [ia] IIC
C-UL: NI / I / 2 / ABCD / T4, AIS / I, II, III / 1 / ABCDEFG, Ex nC [ia] IIC
FM: NI / I / 2 / ABCD / T4, NI / I / 2 / IIC / T4, AIS / I, II, III / 1 / ABCDEFG, AEx [ia] IIC
FM-C: NI / I / 2 / ABCD / T4, NI / I / 2 / IIC / T4, AIS / I, II, III / 1 / ABCDEFG, Ex [ia] IIC
EAC-EX: 2Ex nA [ia Ga] IIC T4 Gc X, [Ex ia Da] IIIC X, [Ex ia Ma] I X
UKR TR n. 898: 2ExnAiaIICT4 X, ExiaI X
associated apparatus and non-sparking electrical equipment.
Uo/Voc = 26.3 V, Io/Isc = 91 mA, Po/Po = 597 mW at terminals 14-15, 10-11.
Uo/Voc = 1.1 V, Io/Isc = 38 mA, Po/Po = 11 mW at terminals 15-16, 11-12.
Ui/Vmax = 30 V, Ii/Imax = 104 mA, Ci = 1.05 nF, Li = 0 nH at terminals 15-16, 11-12.
Um = 250 Vrms, -20 °C Ta 60 °C.
Approvals:
DMT 01 ATEX E 042 X conforms to EN60079-0, EN60079-11, EN60079-26.
IECEx BVS 07.0027X conforms to IEC60079-0, IEC60079-11, IEC60079-26.
IMQ 09 ATEX 013 X conforms to EN60079-0, EN60079-15.
IECEx IMQ 13.0011X conforms to IEC60079-0, IEC60079-15.
INMETRO DNV 13.0108 X conforms to ABNT NBR IEC60079-0, ABNT NBR IEC60079-11, ABNT NBR IEC60079-15, ABNT NBR IEC60079-26, ABNT NBR IEC 61241-11.
UL & C-UL E222308 conforms to UL913, UL 60079-0, UL60079-11, UL60079-15, ANSI/ISA 12.12.01 for UL and
CSA-C22.2 No.157-92, CSA-E60079-0, CSA-E60079-11, CSA-C22.2 No. 213 and CSA-E60079-15 for C-UL.
FM & FM-C No. 3024643, 3029921C, conforms to Class 3600, 3610, 3611, 3810,
ANSI/ISA 12.12.02, ANSI/ISA 60079-0, ANSI/ISA 60079-11, C22.2 No.142,
C22.2 No.157, C22.2 No.213, E60079-0, E60079-11, E60079-15.
C-IT.MH04.B.00306 conforms to GOST R IEC 60079-0,GOST R IEC 60079-11, GOST R IEC 60079-15.
C16.0034 X conforms to 7113, 22782.5-78, I 60079-15.
TÜV Certificate No. C-IS-236198-03, SIL 2 conforms to IEC61508:2010 Ed.2.
TÜV Certificate No. C-IS-236198-09, SIL 3 Functional Safety Certificate conforms to IEC61508:2010 Ed.2, for Management of Functional Safety.
DNV No.A-13778 and KR No.MIL20769-EL001 Certificates for maritime applications.
Mounting:
T35 DIN Rail according to EN50022.
Weight: about 175 g D1010D, 125 g D1010S.
Connection: by polarized plug-in disconnect screw terminal blocks to accommodate terminations up to 2.5 mm2.
Location:
Safe Area/Non Hazardous Locations or Zone 2, Group IIC T4, Class I, Division 2, Groups A, B, C, D Temperature Code T4 and Class I, Zone 2, Group IIC, IIB, IIA T4 installation.
Protection class: IP 20.
Dimensions: Width 22.5 mm, Depth 99 mm, Height 114.5 mm.
FSM
SIL 3

3
D1010 - SIL 2 Repeater Power Supply Smart-Hart compatibleG.M. International ISM0007-16
Model: D1010
1 channel S
Power Bus enclosure
2 channels D
/B
Ordering information
Front Panel and Features
SIL 2 according to IEC 61508:2010 Ed. 2 for Tproof = 7 / 10 years (10% / >10 % of total SIF) with active input.
SIL 2 according to IEC 61508:2010 Ed. 2 for Tproof = 6 / 10 years (10% / >10 % of total SIF) with passive input.
PFDavg (1 year) 1.30 E-04, SFF 80.51 % with active input.
PFDavg (1 year) 1.47 E-04, SFF 80.81 % with passive input.
SIL 3 Systematic capability.
Input from Zone 0 (Zone 20), Division 1,
installation in Zone 2, Division 2.
4-20 or 0-20 mA Input, Output Signal.
Wide Band Smart Communication,
Hart compatible.
Input and Output short circuit proof.
High Accuracy.
Three port isolation, Input/Output/Supply.
EMC Compatibility to EN61000-6-2, EN61000-6-4, EN61326-1
In-field programmability by DIP Switch.
ATEX, IECEx, UL & C-UL, FM & FM-C, INMETRO, EAC-EX, UKR TR n. 898, TÜV Certifications.
TÜV Functional Safety Certification.
Type Approval Certificate DNV and KR for maritime applications.
High Reliability, SMD components.
High Density, two channels per unit.
Simplified installation using standard DIN Rail and plug-in terminal blocks.
250 Vrms (Um) max. voltage allowed to the instruments associated with the barrier.
Not used
Terminal block connections
HAZARDOUS AREA SAFE AREA
+ Input Ch 2 for 2 wire Transmitters
- Input Ch 2 for 2 wire Transmitters or
+ Input Ch 2 for External Powered Transmitters
- Input Ch 2 for External Powered Transmitters
Not used
+ Input Ch 1 for 2 wire Transmitters
- Input Ch 1 for 2 wire Transmitters or
+ Input Ch 1 for External Powered Transmitters
- Input Ch 1 for External Powered Transmitters
9
10
11
12
13
14
15
16
+ Output Ch 1 for Current Source mode or
+ Output Ch 1 for Voltage Source mode
1
- Output Ch 1 for Current Source mode or - Output Ch 1 for
Voltage Source mode or + Output Ch 1 for Current Sink mode
2
+ Power Supply 24 Vdc
3
- Power Supply 24 Vdc
4
+ Output Ch 2 for Current Source mode or
+ Output Ch 2 for Voltage Source mode
5
- Output Ch 2 for Current Source mode or - Output Ch 2 for
Voltage Source mode or + Output Ch 2 for Current Sink mode
6
- Output Ch 2 for Current Sink mode
7
- Output Ch 1 for Current Sink mode
8
Power Bus and DIN-Rail accessories:
DIN rail anchor MCHP065 DIN rail stopper MOR016
Terminal block male MOR017 Terminal block female MOR022

4 D1010 - SIL 2 Repeater Power Supply Smart-Hart compatible G.M. International ISM0007-16
Parameters Table
NOTE for USA and Canada:
IIC equal to Gas Groups A, B, C, D, E, F and G,
IIB equal to Gas Groups C, D, E, F and G,
IIA equal to Gas Groups D, E, F and G
Must
be
Hazardous Area/
Hazardous Locations
Device Parameters
D1010 Associated
Apparatus Parameters
Must
be
Hazardous Area/
Hazardous Locations
Device + Cable Parameters
Uo / Voc = 26.3 V
Ui / Vmax
In the system safety analysis, always check the Hazardous Area/Hazardous Locations devices to conform with the related system documentation, if the device is Intrinsically Safe check
its suitability for the Hazardous Area/Hazardous Locations and gas group encountered and that its maximum allowable voltage, current, power (Ui/Vmax, Ii/Imax, Pi/Pi) are not exceeded
by the safety parameters (Uo/Voc, Io/Isc, Po/Po) of the D1010 series Associated Apparatus connected to it. Also consider the maximum operating temperature of the field device, check
that added connecting cable and field device capacitance and inductance do not exceed the limits (Co/Ca, Lo/La, Lo/Ro) given in the Associated Apparatus parameters for the effective
gas group. See parameters on enclosure side and the ones indicated in the table below:
D1010 Terminals
Ch1
Ch2
14 - 15
10 - 11
Uo / Voc = 1.1 V
Ch1
Ch2
15 - 16
11 - 12
Io / Isc = 91 mA
Ch1
Ch2
14 - 15
10 - 11
Io / Isc = 38 mA
Ch1
Ch2
15 - 16
11 - 12
Po / Po = 597 mW
Ch1
Ch2
14 - 15
10 - 11
Po / Po = 11 mW
Ch1
Ch2
15 - 16
11 - 12
Ii/ Imax
Pi / Pi
D1010 Terminals
Ch1
Ch2
14 - 15
10 - 11
D1010 Associated
Apparatus Parameters
Ci / Ci device + C cable
IIC (A, B)
Co / Ca = 95 nF
Co / Ca = 738 nF
Co / Ca = 2.508 µF
IIB (C)
IIA (D)
Co / Ca = 3.95 µF
Co / Ca = 738 nF
I
IIIC
Ch1
Ch2
14 - 15
10 - 11
IIC (A, B)
Co / Ca = 100 µF
Co / Ca = 1000 µF
Co / Ca = 1000 µF
IIB (C)
IIA (D)
Co / Ca = 1000 µF
Co / Ca = 1000 µF
I
IIIC
Ch1
Ch2
14 - 15
10 - 11
Li / Li device + L cable
IIC (A, B)
Lo / La = 4.3 mH
Lo / La = 17.2 mH
Lo / La = 34.5 mH
IIB (C)
IIA (D)
Lo / La = 56.6 mH
Lo / La = 17.2 mH
I
IIIC
Ch1
Ch2
14 - 15
10 - 11
IIC (A, B)
Lo / La = 11.3 mH
Lo / La = 45.3 mH
Lo / La = 90.7 mH
IIB (C)
IIA (D)
Lo / La = 148.8 mH
Lo / La = 45.3 mH
I
IIIC
Ch1
Ch2
14 - 15
10 - 11 Li / Ri device and
L cable / R cable
IIC (A, B)
Lo / Ro = 59.6 µH/
Lo / Ro = 238.4 µH/
Lo / Ro = 476.8 µH/
IIB (C)
IIA (D)
Lo / Ro = 782.2 µH/
Lo / Ro = 238.4 µH/
I
IIIC
Ch1
Ch2
14 - 15
10 - 11
IIC (A, B)
Lo / Ro = 3490 µH/
Lo / Ro = 13963 µH/
Lo / Ro = 27927 µH/
IIB (C)
IIA (D)
Lo / Ro = 45820 µH/
Lo / Ro = 13963 µH/
I
IIIC

5
D1010 - SIL 2 Repeater Power Supply Smart-Hart compatibleG.M. International ISM0007-16
When used with separate powered intrinsically safe devices, check that maximum allowable voltage, current (Ui/Vmax, Ii/Imax) of the D1010 Associated Apparatus are not exceeded by
the safety parameters (Uo/Voc, Io/Isc) of the Intrinsically Safe device, indicated in the table below:
For installations in which both the Ci and Li of the Intrinsically Safe apparatus exceed 1 % of the Co and Lo parameters of the Associated Apparatus (excluding the cable),
then 50 % of Co and Lo parameters are applicable and shall not be exceeded (50 % of the Co and Lo become the limits which must include the cable such that
Ci device + C cable 50 % of Co and Li device + L cable 50 % of Lo).
If the cable parameters are unknown, the following value may be used: Capacitance 60pF per foot (180pF per meter), Inductance 0.20µH per foot (0.60µH per meter).
The Intrinsic Safety Entity Concept allows the interconnection of Intrinsically Safe devices approved with entity parameters not specifically examined in combination as a system
when the above conditions are respected.
For Division 1 and Zone 0 installations, the configuration of Intrinsically Safe Equipment must be FM approved under Entity Concept (or third party approved);
for Division 2 installations, the configuration of Intrinsically Safe Equipment must be FM approved under non-incendive field wiring or Entity Concept (or third party approved).
Must
be
Hazardous Area/
Hazardous Locations
Device Parameters
D1010 Associated
Apparatus Parameters
Ui / Vmax = 30V Uo / Voc
D1010 Terminals
Ch1
Ch2
15 - 16
11 - 12
li / Imax = 104 mA
Ch1
Ch2
15 - 16
11 - 12
Io / Isc
Ci = 1.05 nF, Li= 0 nH
Ch1
Ch2
15 - 16
11 - 12

6 D1010 - SIL 2 Repeater Power Supply Smart-Hart compatible G.M. International ISM0007-16
Function Diagram
HAZARDOUS AREA ZONE 0 (ZONE 20) GROUP IIC,
HAZARDOUS LOCATIONS CLASS I, DIVISION 1, GROUPS A, B, C, D,
CLASS II, DIVISION 1, GROUPS E, F, G, CLASS III, DIVISION 1,
CLASS I, ZONE 0, GROUP IIC
SAFE AREA, ZONE 2 GROUP IIC T4,
NON HAZARDOUS LOCATIONS, CLASS I, DIVISION 2,
GROUPS A, B, C, D T-Code T4, CLASS I, ZONE 2, GROUP IIC T4
MODEL D1010D
==
=
=
=
14
15
16
3 +
4 -
1
2
8
RLmA
+
-mA +
V
HHT
Supply 24 Vdc
Source I Source V
Sink I
Out 1
+
-
HHT
2 Wire Tx
+
-+
-
I
?
+
-
External
Powered Tx
In 1
==
=
=
=
10
11
12
5
6
7
RLmA
+
-mA +
V
Source I Source V
Sink I
Out 2
+
-
2 Wire Tx
+
-+
-
+
-
External
Powered Tx
In 2
RL
RL
HHTHHT
I
?
MODEL D1010S
==
=
=
=
14
15
16
3 +
4 -
1
2
8
RLmA
+
-mA +
V
HHT
Supply 24 Vdc
Source I Source V
Sink I
Out 1
+
-
HHT
2 Wire Tx
+
-+
-
I
?
+
-
External
Powered Tx
In 1
RL

7
D1010 - SIL 2 Repeater Power Supply Smart-Hart compatibleG.M. International ISM0007-16
Function Diagram
HAZARDOUS AREA ZONE 0 (ZONE 20) GROUP IIC,
HAZARDOUS LOCATIONS CLASS I, DIVISION 1, GROUPS A, B, C, D,
CLASS II, DIVISION 1, GROUPS E, F, G, CLASS III, DIVISION 1,
CLASS I, ZONE 0, GROUP IIC
SAFE AREA, ZONE 2 GROUP IIC T4,
NON HAZARDOUS LOCATIONS, CLASS I, DIVISION 2,
GROUPS A, B, C, D T-Code T4, CLASS I, ZONE 2, GROUP IIC T4
Terminals 14-11
Uo/Voc = 27.4 V
Io/Isc = 91 mA
Po/Po = 624 mW
Connections for Duplication of 2 wires Transmitter Input
Safety Description
Restriction on specifications for 2 wires Transmitter Input:
Bidirectional communication for Smart Transmitter is provided only on channel 1
The minimum supply voltage available for Transmitter (Vtx) is 14.1 V at 20 mA input
The safety parameters must be changed in: Uo/Voc = 27.4 V, Io/Isc = 91 mA, Po/Po = 624 mW
MODEL D1010D Duplicator
==
=
=
=
14
15
16
3 +
4 -
1
2
8
RLmA
+
-mA +
V
HHT
Supply 24 Vdc
Source I Source V
Sink I
Out 1-A
+
-
HHT
2 Wire Tx
+
-+
-
I
?
In 1
==
=
=
=
10
11
12
5
6
7
RLmA
+
-mA +
V
Source I Source V
Sink I
Out 1-B
+
-+
-
RL
RL
IIC
IIB
IIA
0.085
0.675
2.258
4.3
17.2
34.5
54.7
218.9
437.9
Group
Cenelec
Lo/Ro
(µH/)
Lo/La
(mH)
Co/Ca
(µF)
(with 15-12 shorted)

8 D1010 - SIL 2 Repeater Power Supply Smart-Hart compatible G.M. International ISM0007-16
Function Diagram
HAZARDOUS AREA ZONE 0 (ZONE 20) GROUP IIC,
HAZARDOUS LOCATIONS CLASS I, DIVISION 1, GROUPS A, B, C, D,
CLASS II, DIVISION 1, GROUPS E, F, G, CLASS III, DIVISION 1,
CLASS I, ZONE 0, GROUP IIC
SAFE AREA, ZONE 2 GROUP IIC T4,
NON HAZARDOUS LOCATIONS, CLASS I, DIVISION 2,
GROUPS A, B, C, D T-Code T4, CLASS I, ZONE 2, GROUP IIC T4
Terminals 15-12
Uo/Voc = 2.2 V
Io/Isc = 38 mA
Po/Po = 21 mW
Connections for Duplication of Active Input Signals
Safety Description
Restriction on specifications for externally powered Transmitter:
The voltage drop must be changed in 1.8 V maximum
The safety parameters must be changed in: Uo/Voc = 2.2 V, Io/Isc = 38 mA, Po/Po = 21 mW
MODEL D1010D Duplicator
==
=
=
=
14
15
16
3 +
4 -
1
2
8
RLmA
+
-mA +
V
Supply 24 Vdc
Source I Source V
Sink I
Out 1-A
+
-+
-
+
-
External
Powered Tx
In 1
==
=
=
=
10
11
12
5
6
7
RLmA
+
-mA +
V
Source I Source V
Sink I
Out 1-B
+
-+
-
RL
RL
IIC
IIB
IIA
100
1000
1000
11.3
45.3
90.7
849
3396
6793
Group
Cenelec
Lo/Ro
(µH/)
Lo/La
(mH)
Co/Ca
(µF)
(with 16-11 shorted)

9
D1010 - SIL 2 Repeater Power Supply Smart-Hart compatibleG.M. International ISM0007-16
Functional Safety Manual and Application
Application for D1010S, with active input (external powered Tx)
Failure category Failure rates (FIT)
dd = Total Dangerous Detected failures 121.58
du = Total Dangerous Undetected failures 29.43
sd = Total Safe Detected failures 0.00
su = Total Safe Undetected failures 0.00
λtot safe = Total Failure Rate (Safety Function) = λdd + λdu + λsd + λsu 151.01
MTBF (safety function, single channel) = (1 / λtot safe) + MTTR (8 hours) 755 years
no effect = “No effect” failures 192.59
not part = “Not Part” failures 65.00
λtot device = Total Failure Rate (Device) = λtot safe + λno effect + λnot part 408.60
MTBF (device, single channel) = (1 / λtot device) + MTTR (8 hours) 279 years
λsd λsu λdd λdu SFF
0.00 FIT 0.00 FIT 121.58 FIT 29.43 FIT 80.51%
DCD
80.51%
DCS
0%
T[Proof] = 1 year
PFDavg = 1.30 E-04 - Valid for SIL 2
T[Proof] = 7 years
PFDavg = 9.11 E-04 - Valid for SIL 2
PFDavg vs T[Proof] table (assuming Proof Test coverage of 99%), with determination of SIL supposing module contributes >10% of total SIF dangerous failures:
PFDavg vs T[Proof] table (assuming Proof Test coverage of 99%), with determination of SIL supposing module contributes 10% of total SIF dangerous failures:
Failure rates table according to IEC 61508:2010 Ed.2 :
Failure rate table:
Safety Function and Failure behavior:
D1010S is considered to be operating in Low Demand mode, as a Type A module, having Hardware Fault Tolerance (HFT) = 0.
The failure behaviour of the D1010S (when the output current range is 4 to 20 mA) is described by the following definitions:
Fail-Safe State: it is defined as the output going to Fail Low or Fail High, considering that the Safety logic solver can convert the Low or High failures (dangerous detected failures)
to the Fail-Safe state.
□Fail Safe: failure mode that causes the module / (sub)system to go to the defined fail-safe state without a demand from the process.
□Fail Dangerous: failure mode that does not respond to a demand from the process (i.e. being unable to go to the defined Fail-Safe state) or deviates the output current by more
than 5% (0.8 mA) of full span.
□Fail High: failure mode that causes the output signal to go above the maximum output current (> 20 mA). Assuming that the application program in the Safety logic solver is
configured to detect High failures and does not automatically trip on these failures, this failure mode has been classified as a dangerous detected (DD) failure.
□Fail Low: failure mode that causes the output signal to go below the minimum output current (< 4 mA). Assuming that the application program in the Safety logic solver is
configured to detect Low failures and does not automatically trip on these failures, this failure mode has been classified as a dangerous detected (DD) failure.
□Fail “No Effect”: failure mode of a component that plays a part in implementing the Safety Function but that is neither a safe failure nor a dangerous failure.
When calculating the SFF, this failure mode is not taken into account.
□Fail “Not part”: failure mode of a component which is not part of the safety function but part of the circuit diagram and is listed for completeness.
When calculating the SFF this failure mode is not taken into account.
Failure rate date: taken from Siemens Standard SN29500.
Description:
For this application, enable 4 - 20 mA output current (source or sink) mode, setting the internal dip-switches in the following mode (see page 15 for more information):
The module is powered by connecting 24 Vdc power supply to Pins 3 (+ positive) and 4 (- negative).
The green LED is lit in presence of the supply line.
The active input signal from external powered Tx is applied to Pins 15-16.
The output current is applied to Pins 1-2 (for source current mode) or Pins 2-8 (for sink current mode).
T[Proof] = 10 years
PFDavg = 1.30 E-03 - Valid for SIL 2
Dip-switch position (D1010S) 1 2 3 4
Output Source/Sink current mode OFF OFF - -
Systematic capability SIL 3.
In 1 D1010S
Source I
1
2
Out 1
Supply
24 Vdc
3 + 4 -
15
16
External
Powered Tx
8
+
-
mA RL
+
-
mA
RL
Sink I
+
-
14

10 D1010 - SIL 2 Repeater Power Supply Smart-Hart compatible G.M. International ISM0007-16
Functional Safety Manual and Application
Application for D1010S, with passive input (2 wires Tx)
Failure category Failure rates (FIT)
dd = Total Dangerous Detected failures 139.73
du = Total Dangerous Undetected failures 33.18
sd = Total Safe Detected failures 0.00
su = Total Safe Undetected failures 0.00
λtot safe = Total Failure Rate (Safety Function) = λdd + λdu + λsd + λsu 172.91
MTBF (safety function, single channel) = (1 / λtot safe) + MTTR (8 hours) 660 years
no effect = “No effect” failures 219.69
not part = “Not Part” failures 16.00
λtot device = Total Failure Rate (Device) = λtot safe + λno effect + λnot part 408.60
MTBF (device, single channel) = (1 / λtot device) + MTTR (8 hours) 279 years
λsd λsu λdd λdu SFF
0.00 FIT 0.00 FIT 139.73 FIT 33.18 FIT 80.81%
DCS
0%
DCD
80.81%
T[Proof] = 1 year
PFDavg = 1.47 E-04 - Valid for SIL 2
T[Proof] = 6 years
PFDavg = 8.80 E-04 - Valid for SIL 2
PFDavg vs T[Proof] table (assuming Proof Test coverage of 99%), with determination of SIL supposing module contributes >10% of total SIF dangerous failures:
PFDavg vs T[Proof] table (assuming Proof Test coverage of 99%), with determination of SIL supposing module contributes 10% of total SIF dangerous failures:
Failure rates table according to IEC 61508:2010 Ed.2 :
Failure rate table:
Safety Function and Failure behavior:
D1010S is considered to be operating in Low Demand mode, as a Type A module, having Hardware Fault Tolerance (HFT) = 0.
The failure behaviour of the D1010S (when the output current range is 4 to 20 mA) is described by the following definitions:
Fail-Safe State: it is defined as the output going to Fail Low or Fail High, considering that the Safety logic solver can convert the Low or High failures (dangerous detected failures)
to the Fail-Safe state.
Fail Safe: failure mode that causes the module / (sub)system to go to the defined fail-safe state without a demand from the process.
Fail Dangerous: failure mode that does not respond to a demand from the process (i.e. being unable to go to the defined Fail-Safe state) or deviates the output current by more
than 5% (0.8 mA) of full span.
Fail High: failure mode that causes the output signal to go above the maximum output current (> 20 mA). Assuming that the application program in the Safety logic solver is
configured to detect High failures and does not automatically trip on these failures, this failure mode has been classified as a dangerous detected (DD) failure.
Fail Low: failure mode that causes the output signal to go below the minimum output current (< 4 mA). Assuming that the application program in the Safety logic solver is
configured to detect Low failures and does not automatically trip on these failures, this failure mode has been classified as a dangerous detected (DD) failure.
Fail “No Effect”: failure mode of a component that plays a part in implementing the Safety Function but that is neither a safe failure nor a dangerous failure.
When calculating the SFF, this failure mode is not taken into account.
Fail “Not part”: failure mode of a component which is not part of the safety function but part of the circuit diagram and is listed for completeness.
When calculating the SFF this failure mode is not taken into account.
Failure rate date: taken from Siemens Standard SN29500.
Description:
For this application, enable 4 - 20 mA output current (source or sink) mode, setting the internal dip-switches in the following mode (see page 15 for more information):
The module is powered by connecting 24 Vdc power supply to Pins 3 (+ positive) and 4 (- negative).
The green LED is lit in presence of the supply line.
The passive input signal from 2 wires Tx is applied to Pins 14-15.
The output current is applied to Pins 1-2 (for source current mode) or Pins 2-8 (for sink current mode).
T[Proof] = 10 years
PFDavg = 1.47 E-03 - Valid for SIL 2
Systematic capability SIL 3.
D1010S
Source I
1
2 Out 1
Supply
24 Vdc
3 + 4 -
15
16
2 wire
Tx
8
+
-
mA RL
+
-
mA
RL
Sink I
+
-
14
?
I
In 1
Dip-switch position (D1010S) 1 2 3 4
Output Source/Sink current mode OFF OFF - -

11
D1010 - SIL 2 Repeater Power Supply Smart-Hart compatibleG.M. International ISM0007-16
Functional Safety Manual and Application
Application for D1010D, with active input (external powered Tx)
Failure category Failure rates (FIT)
dd = Total Dangerous Detected failures 125.60
du = Total Dangerous Undetected failures 29.46
sd = Total Safe Detected failures 0.00
su = Total Safe Undetected failures 0.00
λtot safe = Total Failure Rate (Safety Function) = λdd + λdu + λsd + λsu 155.06
MTBF (safety function, one channel) = (1 / λtot safe) + MTTR (8 hours) 736 years
no effect = “No effect” failures 196.04
not part = “Not Part” failures 399.90
λtot device = Total Failure Rate (Device) = λtot safe + λno effect + λnot part 751.00
MTBF (device, one channel) = (1 / λtot device) + MTTR (8 hours) 152 years
λsd λsu λdd λdu SFF
0.00 FIT 0.00 FIT 125.60 FIT 29.46 FIT 81.00%
DCS
0%
DCD
81.00%
T[Proof] = 1 year
PFDavg = 1.30 E-04 - Valid for SIL 2
T[Proof] = 7 years
PFDavg = 9.12 E-04 - Valid for SIL 2
PFDavg vs T[Proof] table (assuming Proof Test coverage of 99%), with determination of SIL supposing module contributes >10% of total SIF dangerous failures:
PFDavg vs T[Proof] table (assuming Proof Test coverage of 99%), with determination of SIL supposing module contributes 10% of total SIF dangerous failures:
Failure rates table according to IEC 61508:2010 Ed.2 :
Failure rate table:
Safety Function and Failure behavior:
D1010D is considered to be operating in Low Demand mode, as a Type A module, having Hardware Fault Tolerance (HFT) = 0.
The failure behaviour of the D1010D (when the output current range is 4 to 20 mA) is described by the following definitions:
Fail-Safe State: it is defined as the output going to Fail Low or Fail High, considering that the Safety logic solver can convert the Low or High failures (dangerous detected
failures) to the Fail-Safe state.
Fail Safe: failure mode that causes the module / (sub)system to go to the defined fail-safe state without a demand from the process.
Fail Dangerous: failure mode that does not respond to a demand from the process (i.e. being unable to go to the defined Fail-Safe state) or deviates the output current by more
than 5% (0.8 mA) of full span.
Fail High: failure mode that causes the output signal to go above the maximum output current (> 20 mA). Assuming that the application program in the Safety logic solver is
configured to detect High failures and does not automatically trip on these failures, this failure mode has been classified as a dangerous detected (DD) failure.
Fail Low: failure mode that causes the output signal to go below the minimum output current (< 4 mA). Assuming that the application program in the Safety logic solver is
configured to detect Low failures and does not automatically trip on these failures, this failure mode has been classified as a dangerous detected (DD) failure.
Fail “No Effect”: failure mode of a component that plays a part in implementing the Safety Function but that is neither a safe failure nor a dangerous failure.
When calculating the SFF, this failure mode is not taken into account.
Fail “Not part”: failure mode of a component which is not part of the safety function but part of the circuit diagram and is listed for completeness.
When calculating the SFF this failure mode is not taken into account.
This analysis is also valid for D1010D as Duplicator of Active Input Signal.
Failure rate date: taken from Siemens Standard SN29500.
Description:
For this application, enable 4 - 20 mA output current (source or sink) mode for each channel of D1010D, setting the internal dip-switches in the following mode
(see page 15 for more information):
The module is powered by connecting 24 Vdc power supply to Pins 3 (+ positive) and 4 (- negative).
The green LED is lit in presence of the supply line.
The active input signal from external powered Tx is applied to Pins 15-16 (for Ch. 1) or to Pins 11-12 (for Ch. 2).
The output current is applied to Pins 1-2 (for source current mode) or Pins 2-8 (for sink current mode) for Ch. 1 or to Pins 5-6 (for source current mode) or Pins 6-7 (for sink
current mode) for Ch. 2.
T[Proof] = 10 years
PFDavg = 1.30 E-03 - Valid for SIL 2
Dip-switch position (D1010D) 1 2 3 4
Output Source/Sink current mode OFF OFF OFF OFF
Systematic capability SIL 3.
D1010D
1
2
Supply
24 Vdc
3 + 4 -
15
16 8
Source I
Out 1
+
-
mA RL
+
-
mA
RL
Sink I
External
Powered Tx
In 1
+
-
14
5
6
11
12 7
Source I
Out 2
+
-
mA RL
+
-
mA
RL
Sink I
External
Powered Tx
In 2
+
-
10
Channel 1
Channel 2

12 D1010 - SIL 2 Repeater Power Supply Smart-Hart compatible G.M. International ISM0007-16
Functional Safety Manual and Application
Application for D1010D, with passive input (2 wires Tx)
Failure category Failure rates (FIT)
dd = Total Dangerous Detected failures 143.75
du = Total Dangerous Undetected failures 33.21
sd = Total Safe Detected failures 0.00
su = Total Safe Undetected failures 0.00
λtot safe = Total Failure Rate (Safety Function) = λdd + λdu + λsd + λsu 176.96
MTBF (safety function, single channel) = (1 / λtot safe) + MTTR (8 hours) 645 years
no effect = “No effect” failures 223.14
not part = “Not Part” failures 350.90
λtot device = Total Failure Rate (Device) = λtot safe + λno effect + λnot part 751.00
MTBF (device, single channel) = (1 / λtot device) + MTTR (8 hours) 152 years
λsd λsu λdd λdu SFF
0.00 FIT 0.00 FIT 143.75 FIT 33.21 FIT 81.23%
DCS
0%
DCD
81.23%
T[Proof] = 1 year
PFDavg = 1.47 E-04 - Valid for SIL 2
T[Proof] = 6 years
PFDavg = 8.81 E-04 - Valid for SIL 2
PFDavg vs T[Proof] table (assuming Proof Test coverage of 99%), with determination of SIL supposing module contributes >10% of total SIF dangerous failures:
PFDavg vs T[Proof] table (assuming Proof Test coverage of 99%), with determination of SIL supposing module contributes 10% of total SIF dangerous failures:
Failure rates table according to IEC 61508:2010 Ed.2 :
Failure rate table:
Safety Function and Failure behavior:
D1010D is considered to be operating in Low Demand mode, as a Type A module, having Hardware Fault Tolerance (HFT) = 0.
The failure behaviour of the D1010D (when the output current range is 4 to 20 mA) is described by the following definitions:
Fail-Safe State: it is defined as the output going to Fail Low or Fail High, considering that the Safety logic solver can convert the Low or High failures (dangerous detected
failures) to the Fail-Safe state.
Fail Safe: failure mode that causes the module / (sub)system to go to the defined fail-safe state without a demand from the process.
Fail Dangerous: failure mode that does not respond to a demand from the process (i.e. being unable to go to the defined Fail-Safe state) or deviates the output current by more
than 5% (0.8 mA) of full span.
Fail High: failure mode that causes the output signal to go above the maximum output current (> 20 mA). Assuming that the application program in the Safety logic solver is
configured to detect High failures and does not automatically trip on these failures, this failure mode has been classified as a dangerous detected (DD) failure.
Fail Low: failure mode that causes the output signal to go below the minimum output current (< 4 mA). Assuming that the application program in the Safety logic solver is
configured to detect Low failures and does not automatically trip on these failures, this failure mode has been classified as a dangerous detected (DD) failure.
Fail “No Effect”: failure mode of a component that plays a part in implementing the Safety Function but that is neither a safe failure nor a dangerous failure. When calculating the
SFF, this failure mode is not taken into account.
Fail “Not part”: failure mode of a component which is not part of the safety function but part of the circuit diagram and is listed for completeness.
When calculating the SFF this failure mode is not taken into account
Failure rate date: taken from Siemens Standard SN29500.
Description:
For this application, enable 4 - 20 mA output current (source or sink) mode for each channel of D1010D, setting the internal dip-switches in the following mode
(see page 15 for more information):
The module is powered by connecting 24 Vdc power supply to Pins 3 (+ positive) and 4 (- negative).
The green LED is lit in presence of the supply line.
The passive input signal from 2 wires Tx is applied to Pins 14-15 (for Ch. 1) or to Pins 10-11 (for Ch. 2).
The output current is applied to Pins 1-2 (for source current mode) or Pins 2-8 (for sink current mode) for Ch. 1 or to Pins 5-6 (for source current mode) or Pins 6-7 (for sink current
mode) for Ch. 2.
T[Proof] = 10 years
PFDavg = 1.47 E-03 - Valid for SIL 2
Systematic capability SIL 3.
2 wire
Tx
?
I
Dip-switch position (D1010D) 1 2 3 4
Output Source/Sink current mode OFF OFF OFF OFF
D1010D
1
2
Supply
24 Vdc
3 + 4 -
15
16 8
Source I
Out 1
+
-
mA RL
+
-
mA
RL
Sink I
In 1
+
-
14
5
6
11
12 7
Source I
Out 2
+
-
mA RL
+
-
mA
RL
Sink I
In 2
+
-
10
Channel 1
Channel 2
2 wire
Tx
?
I

13
D1010 - SIL 2 Repeater Power Supply Smart-Hart compatibleG.M. International ISM0007-16
The proof test must be performed to reveal dangerous faults which cannot be otherwise detected. This means that it is necessary to specify how dangerous undetected faults, which
have been noted during the FMEDA analysis, can be revealed during the proof test.
The Proof Test 1 consists of the following steps:
Testing procedure at T-proof
Steps Action
1Bypass the Safety-related PLC or take any other appropriate action to avoid a false trip.
2Send a HART command to the repeater to go to the High (> 20 mA) alarm current output and verify that the analog current reaches that value.
This test is for voltage compliance problems, such as a low loop power supply voltage or an increased wiring resistance, and for other possible failures.
3Send a HART command to the repeater to go to the Low (< 4 mA) alarm current output and verify that the analog current reaches that value.
This tests is for possible quiescent current related failures.
4Restore the loop to full operation.
5Remove the bypass from the Safety-related PLC or restore normal operation.
This test will reveal approximately 99 % of possible Dangerous Undetected failures in the repeater.
Steps Action
1 Bypass the Safety-related PLC or take any other appropriate action to avoid a false trip.
2 Perform steps 2 and 3 of the Proof Test 1.
3 Perform a two-point calibration (i.e. down and full scale) of the connected transmitter and verify that the current output value remains within the specified values.
This requires that the transmitter has already been tested without the repeater and does not contain any dangerous undetected failures.
4 Restore the loop to full operation.
5 Remove the bypass from the safety-related PLC or restore normal operation.
This test will reveal approximately 50% of possible Dangerous Undetected failures in the repeater.
The Proof Test 2 consists of the following steps:
D1010 series are isolated Intrinsically Safe Associated Apparatus installed into standard EN50022 T35 DIN Rail located in Safe Area/ Non Hazardous Locations or Zone 2, Group IIC,
Temperature Classification T4, Class I, Division 2, Groups A, B, C, D, Temperature Code T4 and Class I, Zone 2, Group IIC, IIB, IIA Temperature Code T4 Hazardous Area/Hazardous
Locations (according to EN/IEC60079-15, FM Class No. 3611, CSA-C22.2 No. 213-M1987, CSA-E60079-15) within the specified operating temperature limits Tamb -20 to +60 °C,
and connected to equipment with a maximum limit for AC power supply Um of 250 Vrms.
Non-incendive field wiring is not recognized by the Canadian Electrical Code, installation is permitted in the US only.
For installation of the unit in a Class I, Division 2 or Class I, Zone 2 location, the wiring between the control equipment and the D1010 associated apparatus shall be accomplished
via conduit connections or another acceptable Division 2, Zone 2 wiring method according to the NEC and the CEC.
Not to be connected to control equipment that uses or generates more than 250 Vrms or Vdc with respect to earth ground.
D1010 series must be installed, operated and maintained only by qualified personnel, in accordance to the relevant national/international installation standards
(e.g. IEC/EN60079-14 Electrical apparatus for explosive gas atmospheres - Part 14: Electrical installations in hazardous areas (other than mines), BS 5345 Pt4, VDE 165,
ANSI/ISA RP12.06.01 Installation of Intrinsically Safe System for Hazardous (Classified) Locations, National Electrical Code NEC ANSI/NFPA 70 Section 504 and 505,
Canadian Electrical Code CEC) following the established installation rules, particular care shall be given to segregation and clear identification of I.S. conductors from non I.S. ones.
De-energize power source (turn off power supply voltage) before plug or unplug the terminal blocks when installed in Hazardous Area/Hazardous Locations or
unless area is known to be nonhazardous.
Warning: substitution of components may impair Intrinsic Safety and suitability for Division 2, Zone 2.
Explosion Hazard: to prevent ignition of flammable or combustible atmospheres, disconnect power before servicing or unless area is known to be nonhazardous.
Failure to properly installation or use of the equipment may risk to damage the unit or severe personal injury.
The unit cannot be repaired by the end user and must be returned to the manufacturer or his authorized representative. Any unauthorized modification must be avoided.
D1010 Associated Apparatus
FM Approved
under Entity Concept
and non-incendive field wiring
Unclassified Locations or
Hazardous (Classified) Locations
Class I, Division 2, Groups A, B, C, D, T-Code T4
Class I, Zone 2, Group IIC, IIB, IIA, T-Code T4
FM Approved under Entity Concept,
or third party approval
Hazardous (Classified) Locations
Class I, Division 1, Groups A, B, C, D
Class II, Division 1, Groups E, F, G
Class III, Division 1
Class I, Zone 0, Group IIC, IIB, IIA
Intrinsically
Safe Equipment
Must not use or generate
more than 250 Vrms or Vdc
Control
Equipment
Unclassified Locations
Unclassified Locations or
Hazardous (Classified) Locations
Class I, Division 2, Groups A, B, C, D, T-Code T4
Class I, Zone 2, Group IIC, IIB, IIA, T-Code T4
Hazardous (Classified) Locations
Class I, Division 2, Groups A, B, C, D
Class II, Division 2, Groups E, F, G
Class III, Division 2
Class I, Zone 2, Group IIC, IIB, IIA
FM Approved under non-incendive field
wiring (permitted only for US installations),
or third party approval
Non-incendive
Equipment
Unclassified Locations
14
15
1
2
+
-/+
+
-/+
-
+
Power Supply
3
4
Must not use or generate
more than 250 Vrms or Vdc
16
--
8
-/+
-
+
-/+
-
+
Control
Equipment
6
7
5
Intrinsically
Safe Equipment
-/+
-
+
11
12
10
Non-incendive
Equipment
-/+
-
+
12
10
11
15
16
14
7
4
3
5
6
2
8
1
Control
Equipment
-
-
+
Power Supply
+
-/+
-/+
-
+
Control
Equipment
D1010 Associated Apparatus
FM Approved
under Entity Concept
and non-incendive field wiring
Warning

14 D1010 - SIL 2 Repeater Power Supply Smart-Hart compatible G.M. International ISM0007-16
Start-up
Before powering the unit check that all wires are properly connected, particularly supply conductors and their polarity, input and output wires, also check that Intrinsically Safe conductors
and cable trays are segregated (no direct contacts with other non I.S. conductors) and identified either by color coding, preferably blue, or by marking. Check conductors for exposed
wires that could touch each other causing dangerous unwanted shorts. Turn on power, the “power on” green led must be lit, for 2 wire transmitter connection the supply voltage on each
channel must be 15 V, output signal should be corresponding to the input from the transmitter. If possible change the transmitter output and check the corresponding Safe Area output.
Operation
D1010 provides fully floating DC supply for energizing 2 wire 4-20 mA transmitters, or separately powered 3, 4 wire, 0/4-20 mA transmitters located in Hazardous Area, and repeats and
converts the current to a 0/4-20 mA or 0/1-5 V floating output signal to drive a Safe Area load.
The circuit allows bi-directional communication signal for smart transmitters, a “POWER ON” green led lits when input power is present.
Installation
D1010 series are repeater power supply smart/hart compatible housed in a plastic enclosure suitable for installation on T35 DIN Rail according to EN50022.
D1010 unit can be mounted with any orientation over the entire ambient temperature range, see section “Installation in Cabinet” and "Installation of Electronic Equipments in Cabinet"
Instruction Manual D1000 series for detailed instructions.
Electrical connection of conductors up to 2.5 mm² are accommodated by polarized plug-in removable screw terminal blocks which can be plugged in/out into a powered unit
without suffering or causing any damage (for Zone 2 or Division 2 installations check the area to be nonhazardous before servicing).
The wiring cables have to be proportionate in base to the current and the length of the cable.
On the section “Function Diagram” and enclosure side a block diagram identifies all connections and configuration DIP switches.
Identify the number of channels of the specific card (e.g. D1010S is a single channel model and D1010D is a dual channel model), the function and location of each connection terminal
using the wiring diagram on the corresponding section, as an example:
Connect 24 Vdc power supply positive at terminal “3” and negative at terminal “4”.
For Model D1010S connect positive output of channel 1 (mA source mode) at terminal “1” and negative output at “2”.
For Model D1010D in addition to channel 1 connections above, connect positive output of channel 2 at terminal “5” and negative output at “6”.
For Model D1010S, in case of a 2 wire Transmitter, connect the wires at terminal “14” for positive and “15” for negative.
For separately powered Transmitters connect input signal at terminal “15” for positive and “16” for negative.
For Model D1010D in addition to channel 1 connections above, connect terminal “10” for positive and “11” for negative on channel 2.
Connect input signal from separately powered Transmitters at terminals “11” for positive and “12” for negative channel 2.
Intrinsically Safe conductors must be identified and segregated from non I.S. and wired in accordance to the relevant national/international installation standards
(e.g. EN/IEC60079-14 Electrical apparatus for explosive gas atmospheres - Part 14: Electrical installations in hazardous areas (other than mines), BS 5345 Pt4, VDE 165,
ANSI/ISA RP12.06.01 Installation of Intrinsically Safe System for Hazardous (Classified) Locations, National Electrical Code NEC ANSI/NFPA 70 Section 504 and 505,
Canadian Electrical Code CEC), make sure that conductors are well isolated from each other and do not produce any unintentional connection.
The enclosure provides, according to EN60529, an IP20 minimum degree of mechanical protection (or similar to NEMA Standard 250 type 1) for indoor installation, outdoor installation
requires an additional enclosure with higher degree of protection (i.e. IP54 to IP65 or NEMA type 12-13) consistent with the effective operating environment of the specific installation.
Units must be protected against dirt, dust, extreme mechanical (e.g. vibration, impact and shock) and thermal stress, and casual contacts.
If enclosure needs to be cleaned use only a cloth lightly moistened by a mixture of detergent in water.
Electrostatic Hazard: to avoid electrostatic hazard, the enclosure of D1010 must be cleaned only with a damp or antistatic cloth.
Any penetration of cleaning liquid must be avoided to prevent damage to the unit. Any unauthorized card modification must be avoided.
According to EN61010, D1010 series must be connected to SELV or SELV-E supplies.

15
D1010 - SIL 2 Repeater Power Supply Smart-Hart compatibleG.M. International ISM0007-16
An output configuration DIP Switch is located on component side of pcb, by closing switch “ON” (1-2 for channel 1, 3-4 for channel 2) output signal is configured for 0/1-5 Volts
(250 W internal shunt), opening the switch produces the conventional 0/4-20 mA.
Configuration
Side A Panel View
Span Trimmer CH1
Span Trimmer CH2
Screwdriver
for Trimmers
Calibration Trimmer Ch1
Calibration Trimmer Ch2
Dip switch configuration
Turn the trimmer clockwise to
Increase Output value or turn
the trimmer counterclockwise
if you want to decrease
1234
ON
Switch positions
OFF position
Ch1 current output
0/4-20 mA
OFF position
Ch2 current output
0/4-20 mA
12 34
ON
Side B Panel View
For SIL applications.
ON position
Ch1 voltage output
0/1-5 V
ON position
Ch2 voltage output
0/1-5 V
12 34
Current Output is
factory settings

16 D1010 - SIL 2 Repeater Power Supply Smart-Hart compatible G.M. International ISM0007-16
Set multimeter (DMM) for the reading in DC supply, 10 V range.
Set calibrator (CAL) at 20.000 mA and power supply (PS) at 20.0 V; verify that output voltage (20 mA current on the 250 shunt resistance) read by multimeter (DMM) is
5.000 V ± 10 mV.
Check that dip switch in the unit is in position “ON” (see “Configuration” section). Connect the unit as shown below:
(2) For voltage output please follow step 2
MODEL D1010D
==
=
=
=
14
15
16
3 +
4 -
1
2
8
==
=
=
=
10
11
12
5
6
7
PS
Supply
=
_
V1
In 2
V1CAL
In 1
Out 2
Out 1
+
DMM
+
DMM V
V
mA
mA CAL
Calibration instruction and Troubleshooting
In case a calibration check or readjustment is necessary the following equipment is required:
Adjustable Power Supply Range 0-35 V Resolution 0.1 V,
Accuracy 1% Output Capability 200 mA
Current Meter range 20 mA, Resolution 1 µA Accuracy 0.01%
or Voltage Meter Range 10 V, Resolution 1 mV Accuracy 0.01%
Voltage Meter range 30 V, Resolution 1 mV Accuracy 0.05 %
Current Calibrator range 20 mA, Resolution 1 µA Accuracy 0.01 %
Agilent
E3611A
Agilent
34410A
Fluke
175
Yokogawa
7651
Equipment Required Instrument
Set power supply (PS) at 24.0 V at terminals 3 (+) and 4 (-), the calibrator (CAL) in the function “mA” 20 mA range at terminals 14 (-) and 15 (+), the multimeter (V1) for the reading in
DC supply 30 V range at terminals 14 (+) and 15 (-), the multimeter (DMM) for the reading in DC supply 20 mA range at terminals 1 (+) and 2 (-).
Execute the next test to verify D1010S unit channel or execute it twice to verified both D1010D unit channels.
Verify that green led on the front panel is ON.
Check that dip switch in the unit is in position “OFF” (see “Configuration” section). Connect the unit as shown below:
If the power ON Led is off, check supply voltage, polarity and wiring.
Set calibrator (CAL) at 4.000 mA and verify that the output current, read by multimeter (DMM), is correspondent with a maximum deviation presented in the section “Technical Data”.
Set calibrator (CAL) at 20.000 mA and verify that the output current, read by multimeter (DMM), is correspondent with a maximum deviation presented in the section “Technical Data”.
Set calibrator (CAL) at 20.000 mA and power supply (PS) at 20.0 V; verify that multimeter (V1) reads input voltage as presented in the section “Technical Data”.
If the maximum deviation is exceeded, repeat the board calibration and proceed in the following way:
Set the calibrator (CAL) at 20.000 mA and regulate the current, read by multimeter (DMM), by turning the span trimmer of the unit (see “Configuration” section) until reading
20.000 mA ± 5 µA value.
To execute a linearity test: set the calibrator (CAL) at 4.000, 8.000, 12.000, 16.000, 20.000 mA and verify current output is correspondent with a maximum deviation presented in
the section “Technical Data”.
(1) For current output please follow step 1
PS
DMM
V1
CAL
Identification
MODEL D1010D
==
=
=
=
14
15
16
3 +
4 -
1
2
8
==
=
=
=
10
11
12
5
6
7
Out 2
PS
Supply
=
_
Out 1
+
DMM
+
V1CAL
In 2
V1CAL
In 1
DMM
mA
mA
mA
mA
This manual suits for next models
1
Table of contents
Other GMI Repeater manuals
Popular Repeater manuals by other brands

Kenwood
Kenwood TKR-751E instruction manual

Cellphone-Mate
Cellphone-Mate SureCall CM800 user manual

Doro
Doro rp2001x user manual

Repeater Technologies
Repeater Technologies RC1920C Reference manual

SmartTrunk Systems
SmartTrunk Systems ST-9116 Programming Software Manual

ICP DAS USA
ICP DAS USA CAN Repeater I-7531 user manual