
D6039 - SIL2 Line-Fault Transp. Switch/Prox. RepeaterG.M. International ISM0432-1 5
D6039 series must be installed, operated and maintained only by qualified personnel, in accordance to the relevant national/international installation standards.
Failure to properly installation or use of the equipment may risk to damage the unit or severe personal injury.
The unit cannot be repaired by the end user and must be returned to the manufacturer or his authorized representative. Any unauthorized modification must be avoided.
Warning
Operation
D6039 series can accept on input connections switches or proximity detectors (EN60947-5-6, NAMUR). The output port can assume two different impedance values (RL or RH) or it can
open completely. The module output repeats the input state according to the following correspondence: low input state -> RL, high input state -> RH. Alternatively, the output can be
configured to invert the input state. In both cases, the output opens and the fault LED turns on if any fault (open or short circuit) occurs at the corresponding input.
Presence of supply power and status of output (energized or de-energized), as well as integrity or fault condition of sensor and connecting line are displayed by signaling LEDs (green for
power, yellow for status and red for fault condition).
Note: use of voltage free electrical contacts with fault detection enabled (control equipment) requires, near the switch at the end of the line a R1=1 kΩ typical (470 Ω to 2 kΩ range)
resistor in series and a R2=10 kΩ typical (5 kΩ to 15 kΩ range) resistor in parallel to the contacts in order to allow the fault detection circuit to distinguish between a condition of contact
close/open and a line open/short circuit fault.
Installation
D6039 series is switch/proximity repeater housed in a plastic enclosure suitable for installation on EN/IEC60715 TH 35 DIN-Rail, with or without Power Bus or on customized Termination
Board. D6039 series can be mounted with any orientation over the entire ambient temperature range.
Electrical connections are accommodated by polarized plug-in removable screw terminal blocks which can be plugged in/out into a powered unit without suffering or causing any
damage. Connect only one individual conductor per each clamping point, use conductors up to 2.5 mm² (13 AWG) and a torque value of 0.5‑0.6 Nm. Use only cables that are suitable for
a temperature of at least 85°C.The wiring cables have to be proportionate in base to the current and the length of the cable.
On the section “Function Diagram” and enclosure side a block diagram identifies all connections.
The enclosure provides, according to EN60529, an IP20 minimum degree of protection (or similar to NEMA Standard 250 type 1). The equipment shall only be used in an area of at least
pollution degree 2, as defined in IEC 60664-1. The end user is responsible to ensure that the operating temperature of the module is not exceeded in the end use application.
Units must be protected against dirt, dust, extreme mechanical (e.g. vibration, impact and shock) and thermal stress, and casual contacts. If enclosure needs to be cleaned use only a
cloth lightly moistened by a mixture of detergent in water.
Any penetration of cleaning liquid must be avoided to prevent damage to the unit.
Any unauthorized modification must be avoided.
D6039 series must be connected to SELV or PELV supplies.
All circuits connected to D6039 series must comply with the overvoltage category II (or better) according to EN/IEC60664‑1.
Start-up
Before powering the unit check that all wires are properly connected, particularly supply conductors and their polarity, input and output wires, also check that Intrinsically Safe conductors
and cable trays are segregated (no direct contacts with other non I.S. conductors) and identified either by color coding, preferably blue, or by marking. Check conductors for exposed
wires that could touch each other causing dangerous unwanted shorts. Turn on power, the “power on” green led must be lit, status and fault led on each channel must be in accordance
with condition of the corresponding input line. If possible close and open input lines one at time checking the corresponding status and fault leds condition as well as output to be correct.