Bolts/Nuts
• ANSI:
Carbon Steel oval neck track head
bolts are heat-treated and conform
to the physical properties of ASTM
A183 Grade 2 and SAE J429 Grade
5 with a minimum tensile strength of
110,000 psi.
Carbon Steel heavy hex nuts con-
form to the physical properties of
ASTM A183 Grade 2 and SAE J995
Grade 5. Bolts and nuts are zinc-
electroplated conforming to ASTM
B633.
Stainless Steel bolts and nuts are
available upon request.
• Metric:
Carbon Steel oval neck track head
bolts (Gold color coded) are heat-
treated and conform to the physical
properties of ASTM F568M with a
minimum tensile strength of 760
MPa.
Carbon Steel heavy hex nuts con-
form to the physical properties of
ASTM A563M Class 9. Bolts and
nuts are zinc-electroplated conform-
ing to ASTM B633.
Gaskets
• Pre-lubricated Grade “A” EPDM,
Violet color code,
-30°F to 150°F (-34°C to 66°C)
For dry and freezer systems, lubrica-
tion is required. Refer to Installation
Manual IH-1000FP for details.
• Tri-Seal Grade “E” EPDM,
Green color code,
-30°F to 230°F (-34°C to 110°C)
For proper gasket selection, refer to
Technical Data Sheet TFP1895.
Care and
Maintenance
The GRINNELL G-FIRE Figure 577
Grooved Rigid Coupling must be main-
tained in accordance with this section.
Before closing a re protection system
main control valve for maintenance
work on the re protection system
that it controls, obtain permission to
shut down the affected re protection
system from the proper authorities
and notify all personnel who may be
affected by this decision.
After placing a re protection system
in service, notify the proper authorities
and advise those responsible for moni-
toring proprietary and/or central station
alarms.
The owner is responsible for the inspec-
tion, testing, and maintenance of their
re protection system and devices in
compliance with this document, as well
as with the applicable standards of the
NATIONAL FIRE PROTECTION ASSO-
CIATION, such as NFPA 25, in addition
to the standards of any authority having
jurisdiction. Contact the installing con-
tractor or product manufacturer with
any questions. Any impairments must
be immediately corrected.
Automatic sprinkler systems are rec-
ommended to be inspected, tested,
and maintained by a qualied Inspec-
tion Service in accordance with local
requirements and/or national codes.
Limited
Warranty
For warranty terms and conditions, visit
www.tyco-re.com.
Ordering
Procedure
GRINNELL Products are available glob-
ally through a network of distribution
centers. For the nearest distributor, visit
www.tyco-re.com. When placing an
order, indicate the full product name.
Specify: G-FIRE Figure 577 Grooved
Rigid Coupling, quantity, pipe size
(Nominal ANSI or O.D.), nish (Orange,
Red, or Galvanized), and type of gasket:
• Pre-lubricated Grade “A” EPDM
• Tri-Seal Grade “E” EPDM