TFP1856
Page 4 of 8
Installation
GRINNELL G-FIRE Figure 579 Grooved
Rigid Coupling must be installed in
accordance with this section.
General Instructions
Always read and understand the
instructions. Never remove any piping
component without verifying that the
system is depressurized and drained.
The Figure 579 Grooved Rigid Cou-
pling with additional lubrication is rec-
ommended for applications below
40°F (4°C).
The installation is based on pipe
grooved in accordance with Standard
Cut Groove or Roll Groove Specifica-
tions. Refer to Technical Data Sheet
TFP1898 for additional information.
Step 1. Inspect exterior groove and
ends of the pipe to verify all burrs,
loose debris, dirt, chips, paint and any
other foreign material such as grease
are removed. Pipe end sealing sur-
faces must be free from sharp edges,
projections, indentations, and/or other
defects.
Grade “A” gaskets are supplied with a
pre-lubricant and do not require addi-
tional lubrication for applications above
40°F (4°C).
NOTE: Additional lubrication must be used
in dry pipe and freezer applications. A
silicone based lubricant is recommended.
To prevent deterioration of the gasket
material a petroleum lubricant should
not be used on Grade “A” “EPDM”.
CAUTION
Removal of the nut from the bolt may
result in the coupling segments sepa-
rating at the hinges and the coupling
disengaging from the pipe. Use caution
to avoid equipment damage and/or
personal injury.
Step 2. Do not remove the nut from the
bolt. Open the coupling by extending
the coupling segments out to the extent
allowed by the bolt and nut.
Step 3. Push the gasket/coupling onto
one end of the pipe until the center-
stop of the gasket is in contact with the
end of the pipe (See Figure 2).
NOTE: The gasket center-stop should not
ride up onto the gasket sealing surface
(See Figure 2).
CAUTION
Do not leave coupling unattended on
a single pipe end as it may disengage
from the pipe. Failure to do so may
result in equipment damage and/or
personal injury.
Step 4. Slide the other pipe end into
the gasket/coupling ensuring that it
makes contact with the center stop of
the gasket (See Figure 2). Both pipes
should be aligned vertically and hori-
zontally. Verify that the housing is over
the gasket and that the housing keys
are aligned with the pipe grooves.
Step 5. Tighten nut to the recom-
mended bolt torque, see Figure 5. Visu-
ally inspect the coupling to ensure that
the housing keys are engaged into the
pipe grooves.
NOTICE
The 1 1/4 in. to 8 in. (DN32 to DN200)
couplings have an intended gap of up
to 1/16 in. (1,60 mm) at the bolt pad to
allow for positive rigid gripping onto the
pipe.
Bolt-torque information is supplied
as a guideline in Figure 5 and may be
used when setting the torque on power
impact wrenches. Refer to the manu-
facturer’s instructions for settings.
Bolt lengths require the use of deep
or extra-deep-well sockets. Sockets
inner depth information is supplied for
reference only, see Figure 5. For spe-
cific socket recommendations, contact
Technical Services.
Step 3.
Step 1.
Step 2.
Step 5.
Step 4.
FIGURE 2
FIGURE 579 CENTER-STOP
GASKET POSITION