Specifi cation
The Advance 2-Door Blade (Part No: SAT-ADV-BL-2D)
is a plug-in unit that can be purchased with either the
Advance Single-Blade Controller (Part No: SAT-ADV-C-
SNG-2D) or the Advance Multi-Blade Controller (Part
No: SAT-ADV-C-MLT-2D).
Each 2-Door Blade enables the connection of two
readers and two doors in Sateon access control
systems.
Clearly labelled connectors simplify the task.
Overview Sateon Advance 2-Door Blade
Lock Switching Capacity 12V/24V, 4A max (Solid State output, current limited)
Card Reader interface Wiegand, Clock/Data, RS485
Card Reader Supply, power limited 12V 500 mA, 5V 200 mA total (both ports)
Tamper, Door Sensor, Exit Switch, Aux, Inputs 5V pullup (2k2), max 12V in
Break Glass Input 24V max
Sounder, Valid, Invalid Output 500 max sink to GND (solid state), 12V max in
Aux Out Isolated 30V, 300mA max, internally fused
External Lock Input Supply 24V max, 8A max. Must be externally fused
Operating Temperature 0 to +49°C (32 to 120°F)
Humidity 5-85±5% at 30±2°C (86±4°F)
Weight 140 g
Dimensions 197 x 60 x 28 mm
Sateon Advance 2-Door Blade
Installation Guide
Page 1
Electromagnetic Compatibility
This product complies with the following standards,
following the provisions of EMC Directive 2014/30/EU:
EN 55022:2010 Class B
EN50130-4:2011 inc A1:2014
IEC 62599-2:2010
WEEE
Please refer to www.grosvenortechnology.com/
legal-info/ for disposal instructions under EU
Directive 2012/19/EU.
Current & Voltage
Measure
Overload Protection
Sounder 12V
Reader 12V
Reader 5V12V => 5V
Current & Voltage
Measure
Overload Protection
Current & Voltage
Measure
Overload Protection
12V Lock 1
(4 Amp max)
12V Lock 2
(4 Amp max)
Up to 8 Amp
12V IN
(from Controller)
12V/24V
External Lock
Supply
Input Power
The Advance 2-Door Blade draws 12V power from the
controller. The 2-Door Blade power draw is summed
as follows:
2-Door Blade Quiescent Current = 83 mA max @12V
(1.0W)
External Reader Current (200mA max @ 5V and/or
500mA max @ 12V)
External Door Lock Current (= 4A max per Lock @
12V)
Status LED
The main Blade LED Indicator is used to indicate
activity and state (see also the status LED on the
controller).
If the LED is continuously red, the 2-Door Blade is not
communicating with the controller.
Blade State is reported by fl ashing a code on the LED
every 15 seconds as follows:
5 blue fl ashes Board is not being monitored.
Probably no download to
controller from Sateon
5 red fl ashes Wrong device type confi gured, e.g.
a door is defi ned on an I/O Blade
3 red fl ashes Out of range device confi gured,
e.g. Input 3 defi ned when it only
supports 2
5 green fl ashes No devices confi gured for board
5 yellow fl ashes Reports electrical issues, such
as current tripped, over voltage,
under voltage, over current, under
current
Blade LED indicators
Blade Activity is reported as follows:
Yellow fl icker (lasts
about 30 seconds)
Firmware download in
progress
Green blink (every 5
seconds)
Board running OK
Blue blink Read
Yellow blink Input state change
Red blink Output state change
Other LED Indicators
There are three diagnostic red LEDs on a 2-Door
Blade. Note that these LEDs cannot be seen when the
controller and Blade are in the enclosure.
LED2 – Lock 1 Power. This will be on if Door 1 on the
Blade has not been defi ned or if the Lock 1 power
current limit has been tripped
LED3 – Lock 2 Power. This will be on if Door 2 on the
Blade has not been defi ned or if the Lock 2 power
current limit has been tripped
LED4 – Reader Power (includes other connections,
such as sounders). This will be on if the Blade has
not been defi ned or the current limit has been
tripped
External Lock Supply
For systems with 24V door locks, or locks requiring
more power than the controller can provide, the
2-Door Blade supports an external lock power supply.
This operates automatically if available, where the
Blade will fi nd the external lock power supply for the
locks, otherwise, it uses internal power. This cannot be
changed without powering off .
External lock power is separate from the controller
power. It will need an independent back-up if required:
it is not supported by the controller battery.
Power Options
Page 2
GND
In +
+12 V
+5 V
GND
RS485 A
RS485 B
Clock/D1
Data/D0
Valid
Beeper
Tamper
+12 V
Sounder
GND
REX
GND
Sensor
Lock +
GND
BGU
+12 V
+5 V
GND
RS485 A
RS485 B
Clock/D1
Data/D0
Valid
Beeper
Tamper
+12 V
Sounder
GND
REX
GND
Sensor
Lock +
GND
BGU
sateon
2 DOOR BLADE
Aux In +
Out ±
Return ±
Aux In +
GND
Out ±
Return ±
GND
0V
+12-24V
IN
ININ
Door/
Reader
1
Door/
Reader
2
I/O 1
I/O 2
External
power
+12 V
+5 V
GND
RS485 A
RS485 B
Clock/D1
Data/D0
Valid
Beeper
Tamper
+12 V
+5 V
GND
RS485 A
RS485 B
Clock/D1
Data/D0
Valid
Beeper
Tamper
HID Reader connections
Sateon Reader connections
Wiegand keypads can be
supported using the same
wiring.
+
_
Exit switch
Door sensor
+12 V
Sounder
GND
REX
GND
Sensor
Contact Only (no fault detection)
+
_
Door sensor
Exit switch
1K
1K
+12 V
Sounder
GND
REX
GND
Sensor
Contact Only (short/open circuit)
+
_
Door sensor
A1
Exit switch
1K
1K 2K2
Door sensor
A2
+12 V
Sounder
GND
REX
GND
Sensor
Contact Only (short/open circuit fault detect)
Resistors should be fi tted
as close as possible to the
door sensor.
Reader Connections
Door Connections
Reader and Door Connections
Resistors should be fi tted
as close as possible to the
door sensor.
Page 3
Page 4
Lock Connections Auxiliary Input connections
+
_
Fit mechanical
override for
emergency release
Lock
Lock +
GND
BGU
A Fail Secure lock requires power to release
the lock. The door would remain locked in the
case of a power failure.
Fail Secure Lock
+
_Lock
Normal
Broken
Broken
Normal
Break Glass
2- Pole Changeover
Fail Safe Lock with Break Glass
A Fail Safe lock requires power to lock the
door. The door would be unlocked in the case
of a power failure.
If an external power source is detected on
power up/reset, it is used to power the locks,
otherwise internal power supply is used. Do
not connect an external power supply while the
controller is running.
+
External Lock
Power Supply
12-24 V dc
GND
In +
0V
+12-24V
IN
ININ
External Power Supply
Input switch
Aux In +
Out ±
Return ±
GND
Contact Only (no fault detection)
Supervised (short/open circuit detect)
Supervised (short/open circuit fault detect) with
additional tamper state.
Auxiliary Output connections
ISO
Max Voltage 30V
Max Current 300mA
Fuse 0.3A
4
3
Aux Out
The Aux input is pulled to 5V by the Blade using the
equivalent circuit shown below:
GND GND
TVS 14k4
2k2
+5V
Lock and I/O Connections
Email: [email protected]
Telephone: +44 (0)1279 838000
Web: www.grosvenortechnology.com
For more information about Sateon, visit the website or contact Technical Support:
Input switch
Aux In +
Out ±
Return ±
GND
1K
1K
Input switch
Aux In +
Out ±
Return ±
GND
1K
1K
2K2
Tamper switch

Other Grosvenor IP Access Controllers manuals

Grosvenor Janus C4 Series User manual

Grosvenor

Grosvenor Janus C4 Series User manual

Grosvenor Sateon Advance I/O Blade User manual

Grosvenor

Grosvenor Sateon Advance I/O Blade User manual

Grosvenor Janus C4 485 User manual

Grosvenor

Grosvenor Janus C4 485 User manual

Popular IP Access Controllers manuals by other brands

H3C WAC360 Series installation guide

H3C

H3C WAC360 Series installation guide

SECO-LARM Enforcer SK-1011-SQ owner's manual

SECO-LARM

SECO-LARM Enforcer SK-1011-SQ owner's manual

SilverCloud CA101 user manual

SilverCloud

SilverCloud CA101 user manual

Niko 004-44600 quick start guide

Niko

Niko 004-44600 quick start guide

HIK VISION DS-K1T605 Series user manual

HIK VISION

HIK VISION DS-K1T605 Series user manual

XPR Access XPROX manual

XPR Access

XPR Access XPROX manual

Advanced Card Systems ACR350 user manual

Advanced Card Systems

Advanced Card Systems ACR350 user manual

Smarti SMNG480 user manual

Smarti

Smarti SMNG480 user manual

HIK VISION DS-K1TA70MI-T user manual

HIK VISION

HIK VISION DS-K1TA70MI-T user manual

Paradox DGP-ACM12 installation instructions

Paradox

Paradox DGP-ACM12 installation instructions

UNIONCOMMUNITY FMD10-BLE user guide

UNIONCOMMUNITY

UNIONCOMMUNITY FMD10-BLE user guide

Anviz VP30 owner's manual

Anviz

Anviz VP30 owner's manual

Rosslare AC-015 manual

Rosslare

Rosslare AC-015 manual

SDC EntryCheck 920 installation instructions

SDC

SDC EntryCheck 920 installation instructions

ICP DAS USA ACS-11P-MF quick start

ICP DAS USA

ICP DAS USA ACS-11P-MF quick start

Bosch ARD?FPBEW2?H2 Quick installation guide

Bosch

Bosch ARD?FPBEW2?H2 Quick installation guide

IRIS ID IrisAccess iCAM7000 Series Hardware guide

IRIS ID

IRIS ID IrisAccess iCAM7000 Series Hardware guide

Richelieu SAFE-O-TRONIC access 6330084330 manual

Richelieu

Richelieu SAFE-O-TRONIC access 6330084330 manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.