19
5. CU 300 with constant pressure
control - two-pump operation
5.1 Description
Using constant pressure control in connection with
two-pump operation enables automatic adjustment
of the pump performance according to the consump-
tion in systems where a high flow is required. The
system maintains a constant pressure within the
maximum pump performance in spite of a varying
water consumption.
Note: During two-pump operation, the two pumps
must have the same nominal flow, e.g. two SQE 2.
Fig. 19 shows an example of a two-pump installation
with constant pressure control.
Fig. 19
5.2 Function
The pressure is registered by means of the pressure
sensor and transmitted to the CU 300 (master). The
CU 300 adjusts the pump speed to ensure that the
pressure is kept constant. To ensure that the pump
connected to the CU 300 (master) is started when
water is consumed, a flow switch must be included in
the system.
Set the CU 300 (master) to the desired pressure
(setpoint) in the R100 display 12.1.1 Setpoint.
•Consumption up to 0.18 m³/h.
The flow switch contact is open.
The pump connected to the CU 300 (master)
starts when the pressure is equal to the setpoint
less 0.5 bar. The pump will fill the tank and stop
when the pressure is equal to the setpoint plus
0.5 bar. Consequently, the pump runs on/off oper-
ation.
•Consumption above 0.18 m³/h.
The flow switch contact is closed.
The pump connected to the CU 300 (master)
starts when the flow switch contact closes and the
speed control ensures that the pressure is kept
constant.
If the flow is lower than 0.18 m³/h and the flow
switch contact is opened, the tank is filled to a
pressure equal to the setpoint plus 0.5 bar. When
this pressure is reached, the pump stops. Stop-
ping is a combination of the flow switch contact
opening and the pressure being equal to the set-
point plus 0.5 bar.
If the consumption exceeds the quantity the pump
connected to the CU 300 (master) is able to de-
liver, the pressure in the diaphragm tank will fall.
The pump connected to the CU 300 (slave) will be
started in the two following situations:
1. If the pressure in the diaphragm tank falls to 1
bar below the setpoint or
2. if the pump connected to the CU 300 (master)
has been operating at maximum performance for
more than 5 seconds and the water requirement
has increased.
The pump connected to the CU 300 (slave) will be
stopped in the three following situations:
1. If the system pressure is 1 bar higher than the
setpoint or
2. if the pump connected to the CU 300 (master)
has been operating at minimum performance for
more than 5 seconds and the water requirement
has fallen or
3. if the flow switch indicates “no flow" and the sys-
tem pressure is 0.5 bar higher than the setpoint.
If the flow is larger than the quantity the pumps are
able to deliver at the desired pressure, the pressure
follows the pump curve as illustrated in fig. 20.
Fig. 20
A = Required pressure
TM01 2654 4601
Pos. Description
1A, 1B 1A = CU 300 (master)
1B = CU 300 (slave)
2Diaphragm tank, minimum 24 litres
Absorbs pressure variations.
3Flow switch
The pump starts at once when water is
consumed at the taps.
4Pressure sensor
The required pressure is set using the
R100.
1A 1B
2
3
4
TM01 2833 2598
A
Pressure
±1.0 bar
±0.2 bar