
8
2. Parallel alignment - horizontally
1. Turn motor and pump shaft 90°.
2. Set the dial gauge pointer to zero, turn motor and pump shaft
180° and check that the index lines are still in line.
3. Read dial gauge. If dial gauge shows a deflection exceeding
±0.2 mm, move the motor sideways until the reading of the
dial gauge is within the allowable tolerance of ±0.2 mm.
4. Remove dial gauge (2).
3. Angular alignment - horizontally
1. Mount dial gauge (1) in position 90° (3 o’clock), see fig. 11.
2. Make index lines on the two coupling halves, see fig. 11.
3. Set the dial gauge pointer to zero, turn motor and pump shaft
simultaneously until dial gauge is in position 270° (9 o’clock)
and check that the index lines are still in line.
4. Read dial gauge (1). If the dial gauge shows a deflection
exceeding ±0.2 mm, move the motor sideways until the
deflection is halved.
5. Set the dial gauge pointer to zero, turn motor and pump shaft
simultaneously until dial gauge is in position 90° (3 o’clock)
and read dial gauge (1) again.
6. Now the reading should be within the allowable tolerance of
±0.2 mm. If not - repeat the procedure.
4. Angular alignment - vertically
1. Turn motor and pump shaft until dial gauge (1) in position 0°
(12 o’clock).
2. Set the dial gauge pointer to zero, turn motor and pump shaft
simultaneously until dial gauge is in position 180° (6 o’clock)
and check that the index lines are still in line.
3. Read dial gauge (1). If dial gauge shows a deflection
exceeding ±0.2 mm, add or remove shims under the motor
until the deflection is halved.
4. Set the dial gauge pointer to zero, turn motor and pump shaft
until dial gauge is in position 0° (12 o’clock) and read dial
gauge (1) again.
5. Now the reading should be within the allowable tolerance of
±0.2 mm. If not - repeat the procedure.
6. Remove dial gauge (1).
Note: Coupling tolerances may differ from coupling make to
coupling make. For the standard mounted pin and bush coupling
the allowable tolerance is ±0.2 mm. For other coupling types,
please see the coupling data supplied with the pump.
Finish the alignment procedure by refitting and tightening the
coupling pins.
7. Piping
7.1 System types
The Grundfos HS horizontal split case pumps can be installed in
two types of system:
1. Closed systems or open systems where the liquid level is
above the pump inlet, meaning that a certain suction head will
be available.
2. Open systems where the liquid level is below the pump inlet,
meaning that the pump will be operating with a suction lift.
7.2 General information
When installing the piping, observe these precautions:
• Always run the piping to the pump.
• Do not move pump to the piping. This could make final
alignment impossible.
• Make sure that both suction and discharge piping are
independently supported near the pump so that no strain is
transmitted to the pump when the flange bolts are tightened.
Use pipe hangers or other supports with necessary spacing to
provide support.
• When expansion joints are used in the piping system, fit the
joints at a minimum distance of 1-1.5 flange diameters away
from the pump, both on the suction and the discharge sides.
This prevents turbulence in the joints, thus ensuring optimum
suction conditions and minimum pressure drop on the
discharge side.
• Install piping as straight as possible and avoid unnecessary
bends. Where necessary, use 45° or long sweep 90° fittings to
reduce friction loss, see fig. 19.
• Make sure that all piping joints are tight.
• Where flanged joints are used, ensure that inside diameters
match properly.
• Remove burrs and sharp edges when making up joints.
• Make sure that the piping does not cause stress or strain in
the pump.
• Provide for expansion of pipe material when hot liquids are to
be pumped.
TM03 2941 4905TM03 2942 4905TM03 2940 4905
Do not operate unit without ensuring that all guards
are in place.