
19
•Switch4, starting delay and automatic test run
(only in the case of battery back-up):
When the DIP switch setting is changed, the controller must be
switched off for at least 1 minute!
•Switches5, 6and 7, stop delay:
When the DIP switch setting is changed, the controller must be
switched off for at least 1 minute!
•Switch8:
When the DIP switch setting is changed, the controller must be
switched off for at least 1 minute!
•Switch9, automatic alarm resetting:
When the DIP switch setting is changed, the controller must be
switched off for at least 1 minute!
•Switch10, automatic restarting:
When the DIP switch setting is changed, the controller must be
switched off for at least 1 minute!
9.4 Battery back-up functions
The backup battery is available as an accessory.
If a back-up battery for the CU 214 module is installed, the follow-
ing functions will be carried out if the normal electricity supply to
the LCD 110 fails (see also the illustrations below):
• The common alarm is active, the red indicator light is on –
cannot be reset!
•If the external alarm device for common alarm is supplied from
an external power source, this device will be active – cannot
be reset by means of the reset button!
• The built-in buzzer is activated – can be reset by means of the
reset button!
•If the liquid level rises above the level for high-level alarm, the
top orange indicator light will be flashing and the second
orange indicator light from the top will be permanently on.
•If the starting delay function and automatic test run were
selected (switch 4 of the DIP switch), the start-up will be
delayed after the electricity supply has been switched on when
the liquid level is sufficiently high, see 9.3.2 DIP switch setting.
The table below shows the situations which may occur if the nor-
mal electricity supply to the LCD 110 fails and a back-up battery
is connected:
= the indicator light is off.
= the indicator light is on.
= the indicator light is flashing.
At this setting, the start-up is delayed within the range
from 0 to 255 sec. (random) after the electricity supply has
been switched on, when the liquid level is sufficiently high.
Automatic test run every 24 hours.
After the electricity has been switched on, the pump will
start immediately when the liquid level is sufficiently high.
No automatic test run.
The stop delay is the time from the stop signal is given until the
pumps are stopped.
It must be ensured that the pumps are not running dry.
0 sec. 60 sec.
15 sec. 90 sec.
30 sec. 120 sec.
45 sec. 180 sec.
Switch 8 has no function in connection with the applica-
tion, but this setting must be maintained!
This setting ensures automatic resetting of alarm signals
to external alarm devices and the built-in buzzer. How-
ever, an alarm signal will only be reset if the cause of the
fault no longer exists.
At this setting, the alarm signal must be reset manually by
means of the reset button (the reset button is described in
9.5 Reset button and ON-OFF-AUTO selector switch).
This setting enables automatic restarting after the motor
thermal switch has cut out the pump. Restarting will not be
carried out until the motor has cooled to normal tempera-
ture.
At this setting, the pumps must be restarted manually after
the motor thermal switch has cut out the pump. To restart
the pump, push the ON-OFF-AUTO selector switch into
position OFF for a short period (the ON-OFF-AUTO selector
switch is described in 9.5 Reset button and
ON-OFF-AUTO selector switch).
Mains supply failure:
• The common alarm is active. The red
indicator light is on.
• The green indicator light (electricity
supply switched on) is off.
Mains supply failure and high-level alarm:
• The common alarm is active. The red
indicator light is on.
• The top orange indicator light is flash-
ing.
• The second orange indicator light from
the top is on.
• The green indicator light (electricity
supply switched on) is off.
1
2
2
1