6
Using the LSWM1BFANSC fan tray
采用LSWM1BFANSC风扇模块
Using the LSWM1BFANSCB fan tray
采用LSWM1BFANSCB风扇模块
5
The switch provides front-rear air aisles. Select fan trays to provide airflow from the power module side
to the port side or from the port side to the power module side, based on the ventilation requirements
at the installation site.
交换机采用前后风道设计,通过安装不同的风扇模块,可提供“电源侧到端口侧”和“端口侧到电
源侧”两种气流方向,满足不同环境下的散热要求。
Airflow through the switch 交换机的风向设计
Mounting brackets installed near the power module side 挂耳安装在靠近电源侧 Installing and removing fan trays 风扇模块的安装与拆卸
The LSWM1BFANSC fan tray provides forward airflow from the power module side to the port
side. The fan tray handles are blue. The LSWM1BFANSCB fan tray provides reverse airflow
from the port side to the power module side. The fan tray handles are red.
LSWM1BFANSC为吹风风扇,风向为电源侧进风,端口侧出风,风扇把手为蓝色
LSWM1BFANSCB为抽风风扇,风向为端口侧进风,电源侧出风,风扇把手为红色。
Before installing a fan tray, make sure the airflow direction marked on the fan tray meets the
ventilation requirements at the installation site.
安装风扇模块前,请根据风扇模块的风向指示,确认气流方向和安装环境的通风要求一致。
When you install a fan tray, make sure the "TOP" mark is on top of the fan tray.
安装风扇模块时,请确保“TOP”丝印朝上。
The switch comes with the three fan tray slots empty. You can power on the switch only when
the switch has three fan trays of the same model installed.
交换机出厂时三个风扇插槽均为空,为保证设备的正常散热,用户必须安装三个相同型号的风扇
模块,否则禁止交换机上电运行。
If a fan tray fails, replace it immediately and keep the fan tray in position before the replacement.
如果一个风扇模块出现故障,请及时进行更换,且更换前需保持故障风扇模块在位。
If two fan trays fail, finish replacing at least one fan tray within 1 minute. Replace the fan trays
one after another. Do not remove them simultaneously.
如果两个风扇模块出现故障,请在1分钟之内至少完成一个风扇模块的更换。在更换风扇模块过
程中应按照拔出一个更换一个的方式进行,禁止将两个风扇模块同时拔出。
Connect the other end of the groundingcabletothegroundingpoint on the rack
接地线另一端连接到机柜接地点
2
1
2
Install a fan tray安装风扇 Remove a fan tray 拆卸风扇
1
2
1
Installing and removing power modules 电源模块的安装与拆卸
Install a filler panel in an empty power module slot to prevent dust from entering the chassis
and ensure good ventilation.
若电源模块插槽没有安装电源模块,请及时安装假面板,以保证设备的良好通风散热并防止灰尘进
入交换机。