HANYOUNG NUX HY-1000 User manual

3 4
MK0101KE121127
Danger
Warning
Caution
Analog Temperature Controller
HY-1000/2000/3000/AF1
Thank you for purchasing HANYOUNG product.
Please check whether the product is the exactly same as you ordered.
Before using the product, please read this instruction manual carefully.
Please keep this manual where you can view at any time
INSTRUCTION MANUAL
1381-3,Juan-Dong,Nam-GuIncheon,Korea.
TEL:(82-32)876-4697FAX:(82-32)876-4696http://www.hynux.net
HANYOUNGNUX CO.,LTD
HEADOFFICE
Safetyinformation
Beforeusingtheproduct,pleasereadthesafetyinformationthoroughlyanduseitproperly.Alerts
declaredinthemanualareclassifiedtoDanger,WarningandCautionbytheircriticality
Thereisadangerofoccurringelectricshockintheinput/outputterminalssopleaseneverlet
yourbodyorconductivesubstanceistouched.
•
Ifthereisaconcernaboutaseriousaccidentcausedbyamalfunctionorabnormalityofthis
product,pleaseinstallanexternalprotectioncircuitanddeviseaschemeforpreventinganaccident.
•Thisproductdoesnotcontainanelectricswitchorfuse,sotheuserneedstoinstalla
separateelectricswitchorfuseexternally.(Fuserating:250V0.5A)
•Topreventdefectionormalfunctionofthisproduct,applyaproperpowervoltagein
accordancewiththerating.
•
Topreventelectricshockormalfunctionofproduct,donotsupplythepoweruntilthewiringiscompleted.
•Sincethisproductisnotdesignedwithexplosion-protectivestructure,donotuseitanyplace
withflammableorexplosivegas.
•Donotdecompose,modify,reviseorrepairthisproduct.Thismaybeacauseofmalfunction,
electricshockorfire.
•
ReassemblethisproductwhilethepowerisOFF.Otherwise,itmaybeacauseofmalfunctionorelectricshock.
•Ifyouusetheproductwithmethodsotherthanspecifiedbythemanufacturer,theremaybe
bodilyinjuriesorpropertydamages.
•Thereisapossibilityofoccurringelectricshocksopleaseusethisproductafterinstallingit
ontoapanelwhileitisoperating.
•Thecontentsofthismanualmaybechangedwithoutpriornotification.
•Beforeusingtheproductyoupurchased,makesurethatitisexactlywhatyouordered.
•Makesurethatthereisnodamageorabnormalityoftheproductduringthedelivery.
•Usethisproductwithintherangeoftheoperatingambienttemperature,0~50℃(Whenitis
closelyinstalledMax40℃)andambienthumidity,35~85%R.H(Nocondensation).
•Donotusethisproductatanyplacewithoccurringcorrosive
(especiallynoxiousgasorammonia)orflammablegas.
•Donotusethisproductatanyplacewithdirectvibrationorimpact.
•Donotusethisproductatanyplacewithliquid,oil,medicalsubstances,dust,saltoriron
contents.(UseatPollutionlevel1or2)
•
Donotpolishthisproductwithsubstancessuchasalcoholorbenzene.(Useneutraldetergent.)
•Donotusethisproductatanyplacewithalargeinductivedifficultyoroccurringstatic
electricityormagneticnoise.
•
Donotusethisproductatanyplacewithpossiblethermalaccumulationduetodirectsunlightorheatradiation.
•Installthisproductatplaceunder2,000minaltitude.
•
Whentheproductgetswet,theinspectionisessentialbecausethereisdangerofanelectricleakageorfire.
•Incaseofinputtingthermocouple,useacompensatingcable.
(Ifusinganormalwire,thereisapossibilityofoccurringtemperatureerror.)
•
ForR.T.Dinput,useacablewhichisaleadwirehassmallresistanceandresistancesofthreewires
shallbethesame.(Ifthethreewireshavedifferentresistancesthentherewillbeatemperatureerror.)
•Toavoidaneffectofinductivenoisetoinputsignalcables,usetheproductafterseparating
theinputsignalcablesfrompower,outputandloadcables.
•Separateaninputsignalcablefromanoutputsignalcable.Ifseparatingisnotpossible,
pleaseusetheinputsignalcableaftershieldingit.
•Usenon-earthsensorwiththermocouple.(Incaseofusingearthsensor,thereisapossibility
ofoccurringmalfunctioncausedbyashortcircuit.)
•
Ifthereisexcessivenoisefromthepowersupply,usinginsulatingtransformerandnoisefilteris
recommended.Thenoisefiltermustbeattachedtoapanelwhichisalreadyconnectedtoaground
andthewirebetweenthefilteroutputsideandpowersupplyterminalmustbeshortaspossible.
•Iftwistingthepowercablescloselytogetherthenitiseffectiveagainstnoise.
•
Ifthealarmfunctionsarenotproperlysetthenitwillnotbeoutputwhentheproductis
malfunctioning.Therefore,makesureitsmovementsareproperlyworkingbeforetheoperation.
•TurnthepowerOFFwhenreplacingasensor.
•Useanauxiliaryrelayincaseofhighfrequentoperationsuchasproportionaloperationoretc.
itslifespanwillbeshorterifconnectingaloadwithoutpermissibleratingofoutputrelay.Inthis
case,usingSSRoutputtypeisrecommended.
·UsingElectromagneticSwitch:ProportionalCycle:setitabove20sec.
·UsingSSR:ProportionalCycle:setitabove1sec.
·LifeSpanofContactPointOutput:
MechanicalLifeSpan:above10milliontimes(withnoload)
ElectricalLifeSpan:100thousandtimes(250Va.c3A:withtheratedload)
•Donotconnectanythingtotheunusedterminals.
•Aftercheckingthepolarityofterminal,connectwiresatthecorrectposition.
•
Whenthisproductisconnectedontoapanel,useacircuitbreakerorswitchapprovedwithIEC60947-1orIEC60947-3.
DANGER
DANGERindicatesanimminentlyhazardoussituationwhich,ifnotavoided,willresultindeathorseriousinjury
WARNING
WARNINGindicatesapotentiallyhazardoussituationwhich,ifnotavoided,couldresultindeathorseriousinjury
CAUTION
CAUTIONindicatesapotentiallyhazardoussituationwhich,ifnotavoided,mayresultinminorormoderateinjury
Suffixcode
•Installacircuitbreakerorswitchatnearplaceforconvenientuse.
•Writedownonalabelthatifthecircuitbreakerorswitchisoperatingthenthepowerwillbe
disconnectedsincethecircuitbreakerorswitchisinstalled.
•Forthecontinuousandsafeuseofthisproduct,theperiodicalmaintenanceisrecommended.
•Somepartsofthisproducthavelimitedlifespan,andothersarechangedbytheirusage.
•Thewarrantyperiodforthisproductincludingpartsisoneyearifthisproductisproperlyused.
•Whenthepowerison,thepreparationperiodofcontactoutputisrequired.Incaseofusing
signalsofexternalinterlockcircuitoretc.,useitwithadelayrelay.
•Incaseofreplacingthisunitwithaspareunit,makesureitscompatibilitybecauseitsoperation
canbedifferentbydifferentparametersettingseventhoughthemodelnameisthesame.
•Beforeusingatemperaturecontroller,therecouldbeatemperaturedifferencebetweenPVof
thetemperaturecontrollerandtheactualtemperaturesopleaseoperatethetemperature
controlleraftercompensatingthetemperaturedifferenceappropriately.
Model Code Description
HY-
AF-  HY-1000,HY-2000,HY-3000,AF1
Adjusting
Action
F2-PositionControl(ON/OFF)
PProportionalAction
Input
KK(CA)
JJ(IC)
RR(PR13%)
DPt100Ω(KSStandards)
PPt100Ω(DINStandards)
V✽1-5Vd.c
C✽4-20㎃d.c
ControlOutput
MRelayContact
CCurrent(4-20㎃d.c)
S✽SSRdriving(VoltagePulse12Vd.c)
AlarmOutputorOperation
NNone
OHighLimitOperationAlarmOutput
PLowLimitOperationAlarmOutput
WHigh/LowLimitOperationAlarmOutput
ControlAction RReverseActionControl(forHeatingControl)
DDirectActionControl(forCoolingControl)
RangeCode StandardRangeCodeNumberSelection
Non-displayproductdoesnothavethefeature.
StandardRange
DimensionandPanelcutout
Model
CodeNo.
HY-1000 HY-2000,3000 AF1
Input Temp.Range Input Temp.Range Input Temp.Range
1Pt -50~50 Pt -99~99
2Pt -50~50
3Pt 0~100
4Pt,K,J 0~100 Pt 0~99
5Pt,K 0~200 Pt,K,J 0~200 Pt,K 0~199
6Pt,K 0~300 Pt,K,J 0~300 Pt,K 0~299
7Pt,K 0~400 Pt,K,J 0~400 Pt,K 0~399
8 K 0~600 K0~600
9 K 0~800 K0~800
10 K0~1200
11 K0~1200
12 R0~1600
▒HY-2000/3000
[Unit:mm]
INDONESIA
FACTORY
JL.CEMPAKABLOKF16NO.02DELTASILICONIIINDUSTRIALPARK
LIPPOCIKARANGCICAU,CIKARANGPUSATBEKASI17550INDONESIA
TEL:62-21-8911-8120~4FAX:62-21-8911-8126
PT. HANYOUNG ELECTRONIC INDONESIA
هرﮐ ﮓﻧﺎﯾﻧﺎھ تﻻوﺻﺣﻣ یرﺎﺻﺣﻧا هدﻧﯾﺎﻣﻧ ناوﯾﺳ تﮐرﺷ
021-33989001
www.sivancarno.com
021-33989002
3 4
▒HY-2000,3000 ▒HY-1000
Connectiondiagram
Model
Contents HY-1000,2000 HY-3000 AF1
Powersupplyvoltage
110Va.c/220Va.c60㎐
PermissibleVoltage
FluctuationRange
RatedVoltage±10%
ConsumptionPower
Approx.3VAmax
Input
Thermocouple,
Resistive
Thermocouple,Resistive,
DCCurrent,DCVoltage
Thermocouple,
Resistive
AdjustingSensitivity
±0.2%(fixed)ofMax.Range
ControlMethod
TimeProportionalControl,ON/OFFControl
SettingMethod
AnalogSetting
DigitalBCDSwitchSetting
DisplayMethod
Non-Display DeviationDisplay
ControlOutput
RelayOutput:
Capacity250Va.c3A
RelayOutput:capacity
250Va.c3A
SSROutput:12Vd.c
LoadResistance:
Above800Ω
SettingAccuracy
Within±2.0%ofMax.Range
SameasDisplayAccuracy
WithoutRelativeError
DisplayAccuracy
HY-1000:±1.0%
(fixed)ofMax.Range
HY-2000:±2.0%
(fixed)ofMax.Range
±2.5%(fixed)ofMax.
Range
±1.0%(fixed)ofMax.
Range
ProportionalBand
3%ofMax.Range(fixed)
ProportionalCycle
RelayOutput:Approx.20sec,SSROutput:Approx.2sec
ExternalInput
Resistance
Thermocouple:Below100Ω,Resistive:Below10ΩPer1Wire
(TheResistanceofEachWireShouldbetheSame.)
ResetRange
None
Above1.5%ofMax.Range
AlarmSettingRange
-
※
Within50℃ofHigh/
LowLimittotheOperating
PointofMainSettingValue
AlarmOutput
AdjustingSensitivity
-※1.5℃ofMax.Range
(fixed)
Hysteresis Thermocouple:1.2℃(Below600℃),2.4℃(Above600℃)
Resistive:0.6℃(Below200℃),1.2℃(Above200℃)
DielectricStrength
2000Va.c60㎐for1Minute
RelayLife
Expectancy
Mechanical:Above10MillionsTimes,
Electrical:Above100ThousandsTimes(250Va.c,3AResistiveLoad)
OperatingAmbient
Temperature/Humidity
0~50℃,35~85%R.H(WithoutCondensation)
Weight
HY-1000:358g(IncludingBrackets),
HY-2000,3000:558g(IncludingBrackets)
Approx.356g
(IncludingBrackets)
▒AF1
Specification
Terminology&FunctionExplanation
▒AF1(Built-inAlarmOutput) ▒AF1
▒ProportionalControl
ProportionalControlisthatanoutputcapacityregardingasettingvalue(SV)isproportionally
operatedbyadeviation.Thewidthwhichtheoutputisvariedwithin0~100%iscalled
ProportionalBand(PB).Therefore,forReverseAction,ifPT=Present(Process)Temperature,
PB=ProportionalBand
PT<PB→Outputcapacity100%
PT>PB→Outputcapacity0%
PT=PB→Outputcapacity50%
·PT:Present(Process)Temperature
·PC:ProportionalCycle
·SV:SettingValue(Temperatrue)
·PB:ProportionalBand
▒2-positionControl,ON-OFFControl
ThisisacontrolmethodthatifPTishigherthanSVthenoutputwillbeOFForifPTisless
thanSV,thentheoutputwillbeON.Also,itiscalled2-positioncontrolsinceitoutputseither
0%or100%.Thestatuswhichthetemperatureisunstableandthereishigh/lowwave
aroundSViscalledhunting.ThewidthbetweenthepointwhereitsoutputisOFFbecause
PTishigherthanSVandthepointwhereitsoutputisONsincePTislessthanSViscalled
adjustingsensitivity,hysteresis.Ifthewidth,hysteresis,isnarrow,thenhigh/lowwave
becomessmallerbutthecycleofON-OFFgetssmallersothatitmayseverelydamageto
electromagneticswitch,electrovalveoretc..Especially,forcontrollingburnerwhichisusing
freezerorelectrovalve,2-postioncontrolisgenerallyused.
·PT:Present(Process)Temperature
▒ResetVolume(RST)
ForProportionalControl,whenthecontrollingtemperature(PT)andSV*arethesame,it
generates50%ofoutputsothatthereisconstanterror(normaldeviation)byheatcapacity
oretc.ofacontrollingtarget.
Toeliminatethismatter,changetheoutputcapacitybyResetvolume.
DisplayValue<SettingValue:Turnthevolumeinclockwise.
DisplayValue>SettingValue:Turnthevolumeincounterclockwise.
▒AlarmVolume(ALM)
ForAlarmOperation,±0~50℃ofthesettingvalue(SV)canbesetandhighlimit,lowlimitor
high/lowlimitoperationcanbeselected.
Ex)forcaseofsettingAlarm(ALM)as50℃
HighLimitOperation:itwilloperatewhenitis50℃higherthanSV*.
LowLimitOperation:itwilloperatewhenitis50℃lowerthanSV*.
High/LowLimitOperation:itwilloperatewhenitis50℃higheror50℃lowerthanSV*.
·PT*:Present(Process)Temperature
·PC*:ProportionalCycle
·SV*:SettingValue(Temperatrue)
·PB*:ProportionalBand
Itisdependingonitsspecificationcodewhenyouareordering.
ProportionalControl/ON-OFFControlSelection
UsageoftheFrontVolume
▒HY-1000
هرﮐ ﮓﻧﺎﯾﻧﺎھ تﻻوﺻﺣﻣ یرﺎﺻﺣﻧا هدﻧﯾﺎﻣﻧ ناوﯾﺳ تﮐرﺷ
021-33989001
www.sivancarno.com
021-33989002

This manual suits for next models

3

Other HANYOUNG NUX Controllers manuals

HANYOUNG NUX NP100 User manual

HANYOUNG NUX

HANYOUNG NUX NP100 User manual

HANYOUNG NUX NP100 User manual

HANYOUNG NUX

HANYOUNG NUX NP100 User manual

HANYOUNG NUX ND4 User manual

HANYOUNG NUX

HANYOUNG NUX ND4 User manual

HANYOUNG NUX TPR-3N User manual

HANYOUNG NUX

HANYOUNG NUX TPR-3N User manual

HANYOUNG NUX TPR-3SL User manual

HANYOUNG NUX

HANYOUNG NUX TPR-3SL User manual

HANYOUNG NUX TPR-3SL-EP User manual

HANYOUNG NUX

HANYOUNG NUX TPR-3SL-EP User manual

HANYOUNG NUX TPR-2SL User manual

HANYOUNG NUX

HANYOUNG NUX TPR-2SL User manual

HANYOUNG NUX TPR-3SL-EP User manual

HANYOUNG NUX

HANYOUNG NUX TPR-3SL-EP User manual

HANYOUNG NUX TH510 Series User manual

HANYOUNG NUX

HANYOUNG NUX TH510 Series User manual

HANYOUNG NUX TPR-2 User manual

HANYOUNG NUX

HANYOUNG NUX TPR-2 User manual

HANYOUNG NUX ED6 User manual

HANYOUNG NUX

HANYOUNG NUX ED6 User manual

HANYOUNG NUX MT100 User manual

HANYOUNG NUX

HANYOUNG NUX MT100 User manual

HANYOUNG NUX TPR-3SL User manual

HANYOUNG NUX

HANYOUNG NUX TPR-3SL User manual

HANYOUNG NUX HY Series User manual

HANYOUNG NUX

HANYOUNG NUX HY Series User manual

HANYOUNG NUX TS500 User manual

HANYOUNG NUX

HANYOUNG NUX TS500 User manual

HANYOUNG NUX TPR-2N User manual

HANYOUNG NUX

HANYOUNG NUX TPR-2N User manual

HANYOUNG NUX TPR-3N User manual

HANYOUNG NUX

HANYOUNG NUX TPR-3N User manual

HANYOUNG NUX HY Series User manual

HANYOUNG NUX

HANYOUNG NUX HY Series User manual

HANYOUNG NUX HY Series User manual

HANYOUNG NUX

HANYOUNG NUX HY Series User manual

HANYOUNG NUX BR6 User manual

HANYOUNG NUX

HANYOUNG NUX BR6 User manual

HANYOUNG NUX MC9 Series User manual

HANYOUNG NUX

HANYOUNG NUX MC9 Series User manual

HANYOUNG NUX TPR-3M User manual

HANYOUNG NUX

HANYOUNG NUX TPR-3M User manual

HANYOUNG NUX FS-3A User manual

HANYOUNG NUX

HANYOUNG NUX FS-3A User manual

Popular Controllers manuals by other brands

Solaira SMaRT 16-DV Installation & user manual

Solaira

Solaira SMaRT 16-DV Installation & user manual

HydroHoist UltraLift Series owner's manual

HydroHoist

HydroHoist UltraLift Series owner's manual

Siemens 3VL971 Series operating instructions

Siemens

Siemens 3VL971 Series operating instructions

Balmar BRS-2T-24 operating instructions

Balmar

Balmar BRS-2T-24 operating instructions

IBC SFC manual

IBC

IBC SFC manual

MR TAPCON 230 VC operating instructions

MR

MR TAPCON 230 VC operating instructions

Marlec HRDi Installation & operation

Marlec

Marlec HRDi Installation & operation

Phoenix Contact ILC 2050 BI User manua

Phoenix Contact

Phoenix Contact ILC 2050 BI User manua

Banner Sure Cross Performance P15E Node Series manual

Banner

Banner Sure Cross Performance P15E Node Series manual

Kicker ZXMRLC quick start guide

Kicker

Kicker ZXMRLC quick start guide

stellar labs MK-16 RGBWT user manual

stellar labs

stellar labs MK-16 RGBWT user manual

Phonic STUDIO WIZARD user manual

Phonic

Phonic STUDIO WIZARD user manual

KMB NOVAR 2100 Short manual

KMB

KMB NOVAR 2100 Short manual

AirCycler FRV user guide

AirCycler

AirCycler FRV user guide

Cattron DYNAGEN TOUGH Series TE410 user manual

Cattron

Cattron DYNAGEN TOUGH Series TE410 user manual

Watlow DIN-A-MITE SCR Power Controller Specifications

Watlow

Watlow DIN-A-MITE SCR Power Controller Specifications

Allen-Bradley Logix5000 Series Application book

Allen-Bradley

Allen-Bradley Logix5000 Series Application book

Rain i-dial instructions

Rain

Rain i-dial instructions