OPERATION
To begin, press the “ON/MODE” button, pressing again toggles between FREE RUN
and HOLD mode which is indicated by a dot at the top of the display. Unit
remains on for approximately 25 minutes until auto shut off operates or until
turned off manually. To conserve battery life the backlight will be turned off
automatically after 5 min.
To turn on the backlight continue to hold the ON/MODE button while turning the
unit on until the backlight turns on (approximately 5 seconds).
FREE RUN displays continuous readings, updated at approximately 1 second
intervals.
HOLD MODE displays the highest reading sensed, until the mode switch is
pressed.
Low battery is indicated by a dot under BATT LOW.
Current readings may not be accurate if low battery indicator is steady.
To change the battery remove the four corner screws and lift off the back cover,
when re-installing cover, ensure that the lid gasket is seated properly in its groove.
The Load Spotter may be attached to a hot stick, or used with the handle supplied
on low voltage conductors.
To turn the unit off, press and hold the ON/MODE button until the unit turns off
(approximately 3 seconds).
SPECIFICATIONS
Conductor Size ½ to 1 ¼ inches with captive adapter in place
1 ¼ to 2 inches without adapter
Current Range 0 –2000 Amps
Accuracy ± 1 % of reading
Maximum Line Voltage Field tested to 345 kV
Temperature Range –4° F to +104° F (–20° C to +40° C)
Battery 6 AA alkaline cells
Weight 2.4 lbs (1.1 kg)
P30764 Rev. 8/18