HDL HDL-MWM70-RF.12 Instruction Manual

Professional Home and Building Automation Do you need help? Contact with us
[email protected]om.cn
www.hdlautomation.com 1/ 7
Parameters
Electrical Parameters:
Rated voltage AC220V 50Hz
Voltage range AC220V±20% 50HZ
Slave interface 6P internet port
Rated power 70W
Rated torque 1.0Nm
Rated speed 112rpm
Rail belt speed 16cm/s
Communication Wireless
Wireless transmit power +10dbm
Wireless receive sensitivity -90dbm
Indoor communication distance 30m(barrier free)
RSSI receive signal intensity >-80dbm
Factory frequency
Band, PSK (Suggestion: your
setting should not be same as
the factory setting)
Environmental Conditions:
Working temperature -5℃~45℃
Working relative humidity <95%
Storage temperature -20℃~+60℃
Storage relative humidity <93%
Approved:
CE
RoHS
Product Information:
Dimensions 284×70×50(mm)
Weight 1352g
Housing material ABS, aluminum
Installation Wall hanging
Protection IP41
Insulation E
Overview
Wireless curtain motor
HDL-MWM70-RF.12
HDL-MWM70-RF.12 is the wireless curtain motor, which is
configured by HDL-MCIP-RF.10. It can control the curtain
to open, close, stop and percentage control. And it has over
load protection and over heat protection.
Installation Steps
■Install the rail
■Install the curtain motor
■Connect with MCIP-RF.10
■Curtain setting
■The distance testing of curtain.
■Drag mode: No action, Long drag, short drag.
■Percentage control.
■Communication: wireless.
■Supports online upgrading.
■Supports easy programming.
■Built-in new generation clutch, precise planetary. And
noise level is 40dB.
■Dry contact switch, it can control the curtain to open,
close, stop.
■Suitable for all small to medium-scale curtain applications,
linear and arched, one-and two-side opening.
Functions
■Horizontal pull is 8Kg, maximum load is 50Kg.
■It should configure by HDL-MCIP-RF.10.
Important Notes
Wireless central frequency:
(China) WPAN 780MHz to 786MHz
(Europe) SRD 864MHz to 870MHz
(North America) 904MHz to 928 MHz
Default band 780MHz
Default PSK HDL-SecurityKey0

Professional Home and Building Automation Do you need help? Contact with us
[email protected]om.cn
www.hdlautomation.com 2/ 7
Dimensions and wiring
AC220V power line, 1 meter.
(Brown for L, Blue for N, Y/G for PE)
Motor terminal
Motor terminal: Pull the latch to unlock direc-
tion, and then insert the motor terminal into the
C-Driver Unit. Then, put the latch into the
locked hole.
Wireless curtain motor
HDL-MWM70-RF.12
RJ11 6P network port, connect to the master and slave. It
supplies the working voltage for slave.
Dry contact switch, control the curtain to open, close, stop(COM+FROW is
open, COM+REV is close, COM+STP is stop)
Latch
284
70
50
6P interface
Latch
Lock
Unlock
ANT
Programming button
LED indicator
LED indicator
Function LED status Enter into the status Exit the status
Working properly LED flashes, 1 time/2s -- --
Modify the address of motor LED flashes Long press the button for 3s Long press the button for 3s
/ no operation for 2minutes
Testing for installation LED flashes, 1 time/2s Long press the button for 5s Long press the button for 5s
/ no operation for 20minutes
Easy programming LED flashes, 2 times/2s Long press the button for 10s Long press the button for 10s
/ no operation for 20minutes
Wireless setting LED flashes
Press the button 3 times and
the pressing interval times
should not exceed 2S
Press the button 1 time/ no
operation for 4 minutes
Note: The above operations are carried out in normal work.
■Do not make wrong connection on Bus interface, it will damage the Bus interface of this module.
■Never let liquids get into the module, it will damage this device.
■Ensure good ventilation
■Avoid contact with liquids and aggressive gases
■When you install the motor to the drive unit, please check and make sure that the latch is pushed into locked hole, otherwise the
motor will fall down to cause personal injury and product damage
■When the motor is installed, please do not pull the curtain with too mush force, and do not put any additional weight on the rail, do
not climb the curtain and do not hang anything on the curtain.
Safety Precautions

Professional Home and Building Automation Do you need help? Contact with us
[email protected]om.cn
www.hdlautomation.com 3/ 7
Step 2 Wireless setting
■Press the programming button 3 times, green LED will flash quickly and the wireless curtain motor enters gateway setup mode.
■Open HDL-BUS Pro Setup Tool, search wireless gateway, choose Node configuration.
■Click the ”enter gateway setup mode”.
■And then, search, gateway and curtain will connect, check the curtain, modify the subnet ID and device ID, finally save address-
modify settings of selection-all node exit setup.
Note: The subnet ID of wireless curtain should be same as the gateway.
Wireless curtain motor
HDL-MWM70-RF.12
Step 1 Install rail and motor
Installation effect picture
■The curtain hook mounting position:
Hook unit —> Fixed hole—> Roller runner—> Master carrier and its handle.
■Master, Slave:
The host is connected to AC220V, and it provides the power supply to the slave by the 6-core RJ11. The standard length of
RJ11 wire is 1 meter.
■Ceiling bracket’s mounting distance:
From both ends to the middle, it recommends to install a ceiling bracket and the distance is 600mm per (cannot exceed
600mm). In the middle rail, the ceiling bracket distance can be slightly long, the recommended distance is 800mm. (Because
the load in the ends is big, the mounting distance of ceiling bracket should to be short, and the load in the middle rail is small,
the distance of ceiling bracket can be slightly long)
Rail
Drive Unit Ceiling Bracket
Master Slave
Latch
Master Carrier
Drive Unit
Fixed Hole
Hook Unit
Roller Runner
Ceiling Bracket
RJ11 Cable RJ11 Cable
1
2
3
4

Professional Home and Building Automation Do you need help? Contact with us
[email protected]om.cn
www.hdlautomation.com 4/ 7
Step 4 Motor running
Step 3 Curtain basic information
Wireless curtain motor
HDL-MWM70-RF.12
Remark: indicate some information.
Modify subnet ID: can read and modify the subnet ID and device ID of curtain,
and the subnet ID of curtain should be same as the gateway.
Motor running mode: Forward or back-
ward.
According to the windows, choose the
motor running.
Auto off when power on: If choose,
when the motor power off and then
power on again, the motor will close
automatically.

Professional Home and Building Automation Do you need help? Contact with us
[email protected]om.cn
www.hdlautomation.com 5/ 7
Step 5 Testing for installation
Step 6 Drag mode
Drag mode: long drag, short drag, no action.
Long drag: Draw the curtain, the curtain will fully open or close automatically, the default distance is 20cm.
Short drag: Draw the curtain, the distance will be more than the safe distance and less than the short drag distance, the curtain will open or
close automatically,the default safe distance is 5cm,in order to avoid misoperation or curtain flap, you can set the safe distance. The
default distance is 20cm.
No action: Free mode, end-user can manually drag the curtain to any position freely.
Note: Long drag and short drag are depend on your habit. When pulley is moving, the length should not less than 5cm, and no more than
the half of total length.
Wireless curtain motor
HDL-MWM70-RF.12
Method one:
(1)Keep pressing the button for 5S, the LED will flash 1 time/2S, the curtain enters into the testing mode.
(2)The motor will measure moveable distance for the rail automatically (Open-close), when the motor stops,
finish.
(3)Short press the button, change the curtain status, if you press the button 1 time, the curtain will open, stop
or close.
(4)If it works properly, keep pressing the button for 5S, it will exit the testing mode.
Method two:
Click“Start”, the motor will measure moveable distance for the rail automatically, when it stops, will
exit.
No action
Long drag
Short drag

Professional Home and Building Automation Do you need help? Contact with us
[email protected]om.cn
www.hdlautomation.com 6/ 7
Step 7 Test
Wireless curtain motor
HDL-MWM70-RF.12
Curtain switch: set the curtain status. (stop, open, close or percentage)
After testing, when the curtain opens or closes, casement is maybe extruded or the
opening position is wrong (the curtain has stopped even if it is not fully opening.) Now,
you should adjust the opening and closing position again by “Adjust ON/OFF”.
Operation: Take the opening position as an example. At first, you should make sure the
opening position, control the curtain to close to the opening position. And then, select
“Open” (shown as above). If displays “ command error”, means the opening position has
confirmed. The closing position setting is same as the opening. General condition, the
closing position needn’t set.

Professional Home and Building Automation Do you need help? Contact with us
[email protected]om.cn
www.hdlautomation.com 7/ 7
Step 8 DLP panel setting
The wireless curtain motor can work with DLP panel, there are two ways for control:
Setting 1: The button setting is shown as follows.(HDL-BUS Pro Tool Setup)
Operation: (Parameter 1 is “1(switch no.)”, parameter 2 is “on”, “off”, “stop” or “percentage”
Long press the button, open or close the curtain, if loosen the button, it will stop running . If fully open or close, it will stop running auto-
matically.
Short press the button, it will be based on the percent to control the curtain
Setting 2: The button setting is shown as follows.(HDL-BUS Pro Tool Setup)
Operation: short press the button, control the curtain open, close or stop.
Step 9 Easy Programming
Wireless curtain motor
HDL-NWN70-RF.12
Keep pressing the button for 10S,the LED will flash 2 times/2s. The device will enter into easy programming mode.
Now, the panel will display “programming” , then keep pressing the shift buttons (button 9 and 10) of DLP switch
at the same time, the panel will display “external programming”.
In this mode, you can control the motor by PROG button. Keep pressing any panel button, it will cover the original
target. Short press the button, it will add the motor control.
Long press the button of motor for 10s, it can exit this status. If it is no action, it will exit automatically after 20min
without operation.
Packing List
■HDL-MWM70-RF.12 *1
■Datasheet *1
Table of contents
Other HDL Controllers manuals
Popular Controllers manuals by other brands

Avaya
Avaya WLAN 8100 Series Regulatory information

RMG
RMG 330 Operation and Maintenance, Spare Parts

RADEMACHER
RADEMACHER HomePilot Translation of the commissioning instruction manual

IAI
IAI RA3R First step guide

Mitsubishi Electric
Mitsubishi Electric Central Controller G-50A Operation manual

IBM
IBM 3745 Series Connection and Integration Guide