HDL M/R4.16.1 User manual

HDL KNX / EIB SwitchActuators
_____________________________________________________________________________________
Guangzhou Hedong Electronic Co.,Ltd (HDL) www.hdlchina.com 1/58

HDL KNX / EIB SwitchActuators
_____________________________________________________________________________________
Guangzhou Hedong Electronic Co.,Ltd (HDL) www.hdlchina.com 2/58
HDL KNX / EIB-BUS
(Intelligent Installation Systems)
Product Manual
Contents
1 General………………………………………………………..4
1.1 Product Function………………………….…………..………5
2 Hardware………………………………….………6
2.1 Technical data……………………………………….………..6
2.2 Dimension drawings…………………..……..………….……9
2.3 Wiring diagram………..………………….…………..…..…...9
2.4 Maintenance and Cautions…………………………………11
3 Software..…………………………………………………12
3.1 Database functions overview…………………….………12
3.2 Object/Association/Group address define……..………13
3.3 Function parameter “General”……………………………14
3.4 Function parameter Channel “N”…………………………15
3.5 Channel mode “Switch Actuator”……………..……………16
3.5.1 Channel function…………………………………………19
3.5.2 Channel function parameter……………………………19
3.5.3 Channel function “time”……………………………………21
3.5.3.1 Channel function “time-Flashing”………………………22
3.5.3.2 Channel function “time-Staircase lighting”…………….23
3.5.3.3 Channel function “time-ON/OFF delay”………….…….25
3.5.4 Channel function “scene”……………………..…..……… 27
3.5.5 Channel function “threshold”…………..…………….…….27
3.5.5.1 Channel function “1byte threshold”………………….…….29
3.5.5.2 Channel function “2byte threshold”……………..….…….31
3.5.6 Channel function “curtain”…………………………………33
3.5.7 Channel function “logic”……………………………………35
3.5.8 Channel “Heating Actuator”………………………..………38
4 Communication objects description………..……..……42

HDL KNX / EIB SwitchActuators
_____________________________________________________________________________________
Guangzhou Hedong Electronic Co.,Ltd (HDL) www.hdlchina.com 3/58
4.1 Objects“General” and “Ouput N”…………………….42
4.2 All objects with channel “N”…………………….……….42
4.2.1 Objects“Respone”…………………………………….……….43
4.2.2 Objects “R/W statistics for time”……………..….……….43
4.2.3 Objects “Alarm for ON time out” ……………...……..44
4.2.4 Objects “R/W statistics counter”…………..……...……..44
4.2.5 Objects “Alarm for ON counter out”………………..…….44
4.2.6 Objects “Flashing”…………………..…….…………….…..44
4.2.7 Objects “Staircase light” ………………………..…………….45
4.2.8 Objects“Change staircase lighting time”…………………….45
4.2.9 Objects “Alarm staircase lighting”………………….………45
4.2.10 Objects “Scene”………………………..…….………………46
4.2.11 Objects “Threshold”………………..……….…….…………46
4.2.12 Objects “Blinds”……………………………….………………47
4.2.13 Objects “Logic”………………………….…….………………48
4.2.14 Objects “Heating”……………………….….….………………48
4.2.15 Objects “Forced position”…………………..…….…….……49
5 Application……………………………………….………….50
5.1 Program functions diagram…………….………………….…50
5.2 Scene…………………………………………………………..51
5.3 Threshold………………………………………….…………..51
5.4 Blinds…………………………..………………………………52
5.5 Logical function ……………………………………………….53
5.6 PWM control ………………………………………………….54

HDL KNX / EIB SwitchActuators
_____________________________________________________________________________________
Guangzhou Hedong Electronic Co.,Ltd (HDL) www.hdlchina.com 4/58
1-General
HDL KNX / EIB series switch actuator output modules are
developed by HDL. Using KNX/EIB BUS communicate with other KNX
devices. Database need to be downloaded to the switch actuator by
using ETS2 V1.3/ETS 3.0/ETS4, The document descript how to use
the products . Our products use standard according to EMC, electrical
safety, environmental conditions.
The switch actuators are used to control switched loads, such as:
* Lighting
* Motor
* Blinds
* Heating
* Other Equipments
The rights and the copyright to this manual are exclusively the property
of HDL.

HDL KNX / EIB SwitchActuators
_____________________________________________________________________________________
Guangzhou Hedong Electronic Co.,Ltd (HDL) www.hdlchina.com 5/58
1.1-Product Function
The switch Actuators can switch for 4, 8 and 12 channels
independent AC/DC loads. The outputs for MAX 16 A be
switched ON or OFF on every output channel and can manually
switch too. The M/R4.16.1 no need require an additional power
supply. The M/R8.16.1,M/R12.16.1 require an additional 24VDC
power supply if need frequently operation all of channel same
time, but normal operation is good also if there is no additional
power supply. The following functions can be set individually for
each output channel:
1-Channel s tate response.
2-Channel state after bus voltage failure and recovery
3-Time function
* Flashing
* Staircase light
* Delay
*4-Scene
* scene number:1-64
* 5-Threshold
* Two threshold value
6-Curetain
* top/left<->bottom/right
7-Logic
* AND/OR/XOR/GATE
8-Heat control
* PWM
The type of the switch Actuator Description as following:
M/Rx.y.z
* x=channel number
* y=Current 16A/channel
* z=Application Version

HDL KNX / EIB SwitchActuators
_____________________________________________________________________________________
Guangzhou Hedong Electronic Co.,Ltd (HDL) www.hdlchina.com 6/58
2- Hardware
The technical properties of HDL KNX/EIB
Switch Actuators as the following sections.
2.1 Technical data
Powersupply
*Operating voltage(supply by the bus) 21...30 V DC,
* Current consumption EIB / KNX(operate) < 15 mA
* Current consumption EIB / KNX(standby) < 5 mA
* Power consumption EIB / KNX(operate) < 450 mW
* Power consumption EIB / KNX(standby) < 150 mW
Output nominal values
*TypeofDeviceM/R 4.16.1 8.16.1 12.16.1
*Numberofcontacts 4 8 12
*Inratedcurrent 16A 16A 16A
* Power loss per device at max. load 2.7 W 5.4W 8 W
* Un rated voltage 250/440V AC (50/60 Hz)
Output switching currents
* AC operation (cos = 0.8) 12A / 230 V
* Fluorescent lighting load 16 A / 250 V (150 μF)
* Minimum switching capability 0.1mA/1V
DC current switching capability (ohmic load) 16 A / 12 V DC
Output life expectancy
* Mechanical Life > 1000000
* Electrical Life (240 V/cos = 0.8) > 100000
Output switching delay without additional DC power
* Max. delay time of relay per position changes (charge time of the capacity)
4.16.1 8.16.1 12.16.1
400ms 400ms 400ms
Note: it has voltage(capacity of relay driver) detect function in device ,it stop active and
keep the state of relays in the memory of device when the voltage is going to down
to stop level so this function can prevent the relay is not active success ,the relays
can active again in according to the state of relays in memory when the voltage
(capacity of relay driver) is going to up to active level , this function is very useful for
without additional DC power application in system , and the delay time is approx
0.4s on switch state change when the charge of the capacity is not enough.
Output switching delay with additional DC power
* Max. delay time of relay per position changes (charge time of the capacity)
8.16.1 12.16.1
100ms 100ms

HDL KNX / EIB SwitchActuators
_____________________________________________________________________________________
Guangzhou Hedong Electronic Co.,Ltd (HDL) www.hdlchina.com 7/58
Note: in some of application need ON/OFF the relay frequently and not allow too much
delay time, in that case it can be connected a additional 24-30VDC power supply,
the Max. current is requested 24mA when the relay is active ,the standby current is
requested 4mA , the delay time is approx 100ms on switch state change when the
charge of the capacity is not enough
Connections
* EIB / KNX Bus Connection Terminal
0.8 mm Ø, single core
* Load circuits Screw terminal with Slotted head
0.2...4 mm² multi- core
0.4...6 mm² single-core
*cableshoe 12mm
* Tightening torque Max. 0.8 Nm
Operating and display
* Red LED and EIB / KNX push button all in one
For assignment of the physical address
* Contact position indication Relay lever
Temperature range
*Operation –5°C~+45°C
* Storage – 25 °C ~ + 55 °C
*Transport –25°C~+70°C
Environment conditions
*humidity max.95%Non-condensing
Appearance design
* Modular DIN-Rail Modular installation
* Type–M/R 4.16.1 8.16.1 12.16.1
*Dimensions(HxWxD) 90xWx64
* Width W (unit mm) 72 144 216
* Mounting width (1P=18 mm) 4P 8P 12P
* Mounting depth (unit mm) 64 64 64
Weight (unitkg) 0.26 0.49 0.72
Installation Use 35 mm mounting rail
Mounting position Electricswitchbox
Material and Colour Plastic, grey
Standard and Safety Certificated
* LVD Standard EN60669-2-1 , EN60669-1
*EMC Standard EN50090-2-2
CE mark
* In accordance with the EMC guideline and low voltage guideline
Pollutant ComplywithRoHS
Note: All of loads, at 230 V AC

HDL KNX / EIB SwitchActuators
_____________________________________________________________________________________
Guangzhou Hedong Electronic Co.,Ltd (HDL) www.hdlchina.com 8/58
Motors 4HP
Lamps
* Incandescent lamp load 3500W
Low-volt halogen lamps
* Inductive transformer 1800 W
* Electronic transformer 2000 W
* Halogen lamp 230 V 3500 W
Mercury-vapour lamp
* Uncompensated luminaire 2800 W
* Parallel compensated 2800 W
Fluorescent lamp T5 / T8
* Uncompensated luminaire 3500 W
* Parallel compensated 2000 W
* DUO lamp 2000 W
Dulux lamp
* Uncompensated luminaire 1500 W
* Parallel compensated 1500 W
Switching performance (contact)
* Max. peak inrush-current Ip (120 μs) 600 A
* Max. peak inrush-current Ip (240 μs) 480 A
* Max. peak inrush-current Ip (480 μs) 300 A
* Max. peak inrush-current Ip (1000 μs) 170 A
Application table
Type M/R4.16.1 M/R8.16.1 M/R12.16.1
Max. number of communication objects 90 170 250
Max. number of group addresses 254 254 254
Max. number of associations 254 254 254
Note: The programming requires the EIB Software Tools ETS2 V1.3 or ETS3.0 or ETS4.
If use ETS2 V1.3, then import "*.vd2". If use ETS3.0, then Import "*.vd3”.If use ETS4,the
import “.knxprod”

HDL KNX / EIB SwitchActuators
_____________________________________________________________________________________
Guangzhou Hedong Electronic Co.,Ltd (HDL) www.hdlchina.com 9/58
2.2 Dimension drawings
M/R4.16.1 M/R8.16.1 M/R12.16.1
X 72mm 144mm 216mm
2.3 Wiring diagram
66mm
45mm
35mm
49mm
Xmm
90mm

HDL KNX / EIB SwitchActuators
_____________________________________________________________________________________
Guangzhou Hedong Electronic Co.,Ltd (HDL) www.hdlchina.com 10/58
1 Label area
2 Programming button&Programming LED
3KNX/EIB Bus Connector
4Terminal for Load Connection
5 Contact position indication and manual operation

HDL KNX / EIB SwitchActuators
_____________________________________________________________________________________
Guangzhou Hedong Electronic Co.,Ltd (HDL) www.hdlchina.com 11/58
6Additional power DC24V (Max.24mA in operate , Min. 4mA in
standby) optional
Note: a) Dimensions of the space to be provided for each switch
b) Dimensions and position of the means for supporting and fixing the
switch within this space
c) Minimum clearance between the various parts of the switch and
the surrounding parts where fitted
d) Minimum dimensions of ventilating opening , if needed, and their
correct arrangement.
e) The protective devices (e.g. fuses, automatic protective devices,
etc.) to be connected to the load to avoid overloading
2.4 Maintenance and Cautions
*Please read this user manual carefully before any operation.
*Don’t close to the interfering devices.
*The site should be ventilated with good cooling environment.
*Pay attention to damp proof, quakeproof and dustproof.
*Avoid rain, other liquids or caustic gas.
*Please contact professional maintenance staff or HDL service center
for repair or fix.
*Remove the dust regularly and do not wipe the unit with the volatile
liquids like alcohol, gasoline, etc.
*If damaged by damp or liquid, turn off it immediately.
*Regularly check the circuitry and other related circuit or cables and
replace the disqualified circuitry on time.
*For security, each circuit to connect an MCB or fuse
*Installation location should be well-ventilated, pay attention to
moisture, shock, dust proof.

HDL KNX / EIB SwitchActuators
_____________________________________________________________________________________
Guangzhou Hedong Electronic Co.,Ltd (HDL) www.hdlchina.com 12/58
3-Software
HDL KNX/EIB Switch Actuators database use ETS3.0 to do the
design. The device types are M/R4.16.1, M/R8.16.1 and
M/R12.16.1,and the databases name are “Switch 4fold 16A”,”Switch
8fold 16A”,”Switch 12fold 16A”. All Interface and the functions Apply
parameters please overview the following description of the
paragraph.
Each channel ouput of the Switch Actuators are independent and the
same. So, Understand only one channel ouput is enough. The
following paragraph will description of the first channel output in
detail.
3.1 Database functions Overview
The following table provide an overview of the functions and
some parameters with the switch actuators:
Switch
function
M/R4.16.1 M/R8.16.1 M/R12.16.1
General --- --- ---
Cycle telegram
(heartbeat)
Y Y Y
Switch delay
after recover
Y Y Y
Switch
Actuator --- --- ---
Save statistic for
ON switching
‘time’
Y Y Y
Save statistic for
ON switching
‘counter’
Y Y Y
Voltage fail
state
Y Y Y
Voltage
Recovery state
Y Y Y
Time --- --- ---
Flashing Y Y Y
Staircase lighting Y Y Y
ON/OFF delay Y Y Y
Scene --- --- ---
SceneNO.1-64 Y Y Y
Threshold --- --- ---

HDL KNX / EIB SwitchActuators
_____________________________________________________________________________________
Guangzhou Hedong Electronic Co.,Ltd (HDL) www.hdlchina.com 13/58
Threshold lower Y Y Y
Threshold middle Y Y Y
Threshold upper Y Y Y
Curtain --- --- ---
Blinds
UP/DOWN
Y Y Y
Blinds
Adjustment
Y Y Y
Logic --- --- ---
AND Y Y Y
OR Y Y Y
XOR Y Y Y
GATE Y Y Y
Heating
Actuator --- --- ---
Voltage fail state Y Y Y
Recovery Y Y Y
Switch state
Response
Y Y Y
1bit/1byte
PWM control
Y Y Y
Forced position Y Y Y
Table1: Database application overview.
Note: For each function and mode, can only be used alone,
but "ON/OFF delay" function can be used with “switch
actuator” mode and scene function .
3.2 Object/Association/Group address define
In following table, The objects is assigned to the some
function of the channel output pages, If active some
functions and the object will be valid. One or more group
addresses can be assigned to a object. The association will
connect group addresses to the object.
Name type Max. number of
communication
objects
Max. number
of associations Max .number
of group
addresses
Switch 4fold 16A M/R4.16.1 90 254 254
Switch 8fold 16A M/R8.16.1 170 254 254
Switch 12fold 16A M/R12.16.1 250 254 254
Table2: Overview the max. number of the objects, max.

HDL KNX / EIB SwitchActuators
_____________________________________________________________________________________
Guangzhou Hedong Electronic Co.,Ltd (HDL) www.hdlchina.com 14/58
number of associations and max. number of the
group addresses
Note: ETS2V1.3-> Import “VD2”
ETS3.0-> Import “VD3” to “VD5”.
ETS4-> Import “.KNXPROD”.
3.3 Function parameter “General”
Fig1: “General” parameter windows
In the parameter of the general windows can set two parameters
“Switching delay after recovery ” and “Cycle send general telegram”.
---Switching delay after recovery(2..200s)
Can operate relay for a delay time 2..200s after the power on. The
default value is 2 seconds. The Min. value is 2 seconds, and the max.
value is 200 seconds.
Options: 2…200s
When the power on and timer start, and when the time out, The switch
can be allow operating . This function is selected by user
---Cycle send general telegram(1..65535s,0-invalid)
The range of the parameter is 0 to 65535s. Zero of parameter
disable the function , other of parameter enable this function

HDL KNX / EIB SwitchActuators
_____________________________________________________________________________________
Guangzhou Hedong Electronic Co.,Ltd (HDL) www.hdlchina.com 15/58
Options: 0…65535s
The parameter set to nonzero, Device will send a telegram data
cyclically when time out. Send the value alternately between 0 and 1.
3.4 Function parameter Channel “N”
Fig2: “Channel N” parameter(N=A,B,C...) windows
In the parameter windows of the “Channel N”, can setup some
common functions. Through functional selection and download the
database to the device, and device will work in accordance with the
selected function.
---Channel “N(N=A,B,C…)” work mode:
The function of the output “N” work mode can be selected with three
parameter.
Options: Switch Actuator
Heating Actuator
Inactivated
If select “Inactivated”, The channel “N” function will be invalid,
otherwise work in the other two modes.

HDL KNX / EIB SwitchActuators
_____________________________________________________________________________________
Guangzhou Hedong Electronic Co.,Ltd (HDL) www.hdlchina.com 16/58
3.5 Channel mode “Switch Actuator”
Fig3: Switch Actuator windows
More functions setup in this mode, the following section will
description detailed of the Switch Actuator mode.
---Normally connected type
This parameter is the choice of the type of access load
Options: Normally Closed:
Normally Opened
Normally Closed: Access of the load type normally OFF state is
closed.
Normally Opened: Access of the load type normally OFF state is
opened.
---Response of switch state ON/OFF
This parameter is the choice of the switching state feedback
Options: No response
Always response

HDL KNX / EIB SwitchActuators
_____________________________________________________________________________________
Guangzhou Hedong Electronic Co.,Ltd (HDL) www.hdlchina.com 17/58
Only after change
No response: no response switch state.
Always response: always response switching state when receive the
channel telegram data.
Only after change: only response switching state when channel state
changed.
---Save statistic for ON switching ‘time(hour-2bytes)’
Statistics per channel ON time , useful for management and
monitoring
.
Options: Disable
Enable
Disable:Disable Statistics ON time
Enable: Enable Statistics ON time
>>:->Alarm for time out
Options: No
Yes
No: Not alarm
Yes: Alarm
>>:--Alarm when time out(1..65535h)
This parameter set the ON time alarm overflow time.
Options:1..65535h
>>:--Alarm telegram interval when time out(1..255s)
This parameter is set to ON time overflow alarm interval.
Options: 1..255s
>>:--Alarm telegram number(1..255,0-unlimited)
This parameter set the ON time overflow alarm of the number.
Options:0-unlimited
1..255
---Save statistic for ON switching ‘counter(4bytes)’
Statistical channel switch ON counter.
Options: Disable
Enable
Disable: Disable Statistics ON counter
Enable:Enable Statistics ON counter
>>:->Alarm for counter out

HDL KNX / EIB SwitchActuators
_____________________________________________________________________________________
Guangzhou Hedong Electronic Co.,Ltd (HDL) www.hdlchina.com 18/58
Options: No
Yes
No: Not alarm
Yes: Alarm
>>:--Alarm when counter our(10..10000000)
This parameter set the ON alarm overflow time.counter
Options:10..10000000
>>:--Alarm telegram interval when counter out(1..255s)
This parameter is set ON counter overflow alarm interval.
Options: 1..255s
>>:--Alarm telegram number(1..255,0-unlimited)
This parameter set the ON counter overflow alarm number.
Options:0-unlimited
1..255
---The switch state on bus voltage fail
When bus voltage failure and the function will be executed. Three
choices will be available as following:
Options: Unchange
ON
OFF
Unchange: The channel switch position unchanged after bus voltage
failure
ON: The channel position will be switch ON after bus voltage failure
OFF: The channel position switch OFF after bus voltage failure
---The operation of switch after bus voltage recovery
When power on and the bus voltage recovery, This function will be
executed. four choices will be available as following:
Options: Unchange
Recovery
ON
OFF
Unchange: The channel switch position unchanged after bus voltage
recovery.
Recovery: After bus voltage recovery, The channel switch position
will be back to the state of the power-down previous.
ON: The channel position will switch ON after bus voltage recovery.

HDL KNX / EIB SwitchActuators
_____________________________________________________________________________________
Guangzhou Hedong Electronic Co.,Ltd (HDL) www.hdlchina.com 19/58
OFF: The channel position will switch OFF after bus voltage recovery.
Show the function page
If this parameter is activated, and channel function page will be
showed. The function page Include Time, Scene, Threshold, Blinds
and Logic. Details see the following sections.
3.5.1 Channel function
Thefollowingwilldescribe detail the functions parameter setup of the
channel.
3.5.2 Channel function parameter
Fig4: Channel function windows
In normal case, The each channel function is disabled, If enabled and
the channel function will be valid.
---Enable function “time”
If set to Enable, and the time function will be enable .
Options: Disable
Enable
Disable: disable time function.

HDL KNX / EIB SwitchActuators
_____________________________________________________________________________________
Guangzhou Hedong Electronic Co.,Ltd (HDL) www.hdlchina.com 20/58
Enable: enable time function.
---Enable function "scene"
If set to Enable, and the scene function will be enable.
Options: Disable
Enable
Disable: disable scene function.
Enable: enable scene function.
---Enable function "threshold"
If set to Enable, the Threshold function will be enable.
Options: Disable
Enable
Disable: disable Threshold function.
Enable: enable Threshold function.
---Enable function "blinds"
If set to Enable, the Blinds function will be enable.
Options: Disable
Enable
Disable: Disable Blinds function.
Enable: Enable Blinds function.
---Enable function "logic"
If set to Enable, the Logic function will be Enable.
Options:Disable
Enable
Disable: Disable Logic function.
Enable: Enable Logic function.
This manual suits for next models
2
Table of contents
Other HDL Controllers manuals
Popular Controllers manuals by other brands

Emerson
Emerson Fisher L2 instruction manual

Parker
Parker 514C product manual

SolPad
SolPad SolarIQ 500HD-W-6-4G installation guide

TELECO AUTOMATION
TELECO AUTOMATION TVRGBDU868ST24 Mounting

Lutron Electronics
Lutron Electronics seeTouch installation instructions

Garnet
Garnet SPILLSTOP ULTRA 815-UHP/H user manual

Automated Logic
Automated Logic M4106nx Technical instructions

Eurapo
Eurapo OMNIBUS 360 MAINTENANCE and Operation manual

Victor
Victor EDGE ESS3 PARTS, SERVICE & REPAIR BULLETIN

Elko
Elko LIC-1 manual

Cooper
Cooper CEAG GHG 635 GHG 635 operating instructions

PlaneWave Instruments
PlaneWave Instruments EFA instructions