1Hearth & Home Technologies • AK-225 Outside Air Kit Instructions • 200-900L Rev. B • 11/13
Figure 1. Kit Contents
AK-225
Installation Instructions
Leave this manual with party responsible for use
and operation.
CAUTION! Risk of Cuts or Abrasions. Wear protective
gloves and safety glasses during installation. Sheet metal
edges are sharp.
CAUTION! Do not install damaged components. If you
received components that are damaged, contact your
dealer for assistance.
The Hearth Technologies AK-225 Air Kit is used to bring in
outside make-up and combustion air to Heat & Glo solid
wood fuel fireplaces and some gas fireplaces. Check the
fireplace instructions.
The air that is drawn into the fire chamber from outside
the home or unheated area helps relieve the demand for
combustion air being drawn into the fireplace from inside
the home.
Kit Contents:
(1) Duct Termination
(2) Side Collars
(1) Flex Duct
(4) 1-1/2 Inch Truss Head Screws
(3) 1/2 Inch Bit Tip Screws
(2) Plastic Tie Straps
For reference, see Figure 1.
DUCT TERMINATION SIDE COLLAR (2)
SCREWS
(QTY 4)
FLEX DUCT
PLASTIC TIE STRAPS (2)
SCREWS
(QTY 3)
NOTE: 4-inch Class 1 ducting material or metal duct may
be used with AK-225.
INSTALLATION PRECAUTIONS
The duct termination should be located so it is exposed to
an outdoor opening at least 100 square inches. If the duct
termination must be located in a crawl space or basement,
be sure the termination area has 100 square inches of
ventilation opening to outside air.
The duct termination must be located so it does not com-
pete for air flow with exhaust fans, gas vent hoods or
other air consuming devices or appliances. It must not
be obstructed by rafters, insulating materials, or other
obstructions. The less restrictive the air supply, the better
the AK-225 will perform.
INSTALLATION INSTRUCTIONS
Determine the location of the fireplace as described in the
fireplace installation manual. Then plan the location of the
duct termination and the route of the duct run between the
fireplace and the duct termination.
The duct run must be limited to a maximum distance of 40
feet from the fireplace pipe collar to duct termination. This
will provide the least restriction to air flow. No more than
four 90 degree elbows can be used. The duct run may be
horizontal, vertical inclined or any combination of these for
all models. Vertical duct runs must be at least three (3)
feet below the fireplace chimney flue exit. See Figure 2.
WARNING! Risk of Explostion! DO NOT install duct ter-
mination into area that cold contain flammable liquids or
fumes, such as an attic space or garage.
Hearth & Home Technologies • AK-225 Outside Air Kit Instructions • 200-900L Rev. B • 11/132
1. Remove and discard the outside air knockout (or cover
plate) located at the side or bottom of the fireplace. Use
care not to rub against the sharp edges of this opening
to avoid cuts. Some appliances may not have a cover
plate.
2. Attach the side collar with four (4) screws to the side or
bottom of the fireplace. Slide the duct over the collar and
attach the duct to the collar using the plastic tie straps
or three (3) screws (screws not provided). Continue
attaching the ducting together using three (3) screws
at each joint until you have installed sufficient duct to
arrive at the duct termination location.
3. Install the duct termination from the outside of the home
and cover it with the rain cap. Cut a hole in the desired
location approximately 4 1/2 inches in diameter, caulk
around the hole, and slide the termination through the
opening from outside the home. The termination/rain
cap should be caulked around its perimeter to assure
a tight seal. The rain cap opening should be positioned
downward. See Figure 3.
ATTIC
CEILING
DUCT
DUCT
TERMINATION
DUCT TERMINATION
MUST BE MORE THAN
3 FT BELOW CHIMNEY
40 FT MAX.
DUCT RUN
EXTERIOR
WALL
DUCT
TERMINATION
RAIN CAP
40 FT MAX.
DUCT RUN
DUCT
SOFFIT TERMINATION
EXTERIOR WALL TERMINATION
Figure 2. Soffit and Exterior Wall Termination
DUCT
TERMINATION
RAIN CAP
WALL
CAULKING
Figure 3. Termination Rain Cap
3Hearth & Home Technologies • AK-225 Outside Air Kit Instructions • 200-900L Rev. B • 11/13
Please contact your Hearth & Home Technologies dealer with any
questions or concerns.
For the location of your nearest Hearth & Home Technologies dealer,
please visit www.fireside.com.
Hearth & Home Technologies Inc.
7571 215th Street West, Lakeville, MN 55044
www.fireside.com
4. FOR MODELS EM-41 AND EM-48: Remove the 4
screws holding the cover plate over the outside air hole
in the side of the fireplace's outer skin. Attach the 2 foot
section of flex duct to one of the side collars with a plastic
tie strap. Insert the flex duct through the outer skin all
the way to the collar. Place the second side collar, (flat
side towards the unit) against the other collar and using
the screws previously removed, secure both collars to
the fireplace outer skin.
Follow previous instructions to run air duct to termina-
tion.
Open lower grille and attach the flex duct to the duct
collar on the underside of the fire chamber base. Secure
by using a plastic tie strap. See Figure 4.
BOTTOM
COLLAR
SIDE COLLAR
LOWER
GRILLE
FLEX DUCT
(CONNECTED TO COLLARS)
Figure 4. Attach the Flex Duct
NOTE: The outside air damper control for models EM-41
and EM-48 is located behind the lower grill in the middle of
the unit. To open the damper, pull the control rod forward
and left until the damper locks into open position. The
damper MUST be open for the unit to operate properly.
5. The AK-225 Outside Air Kit is now installed and ready
for use.
OPERATION PRECAUTIONS
AND INSTRUCTIONS
For all solid wood fuel fireplaces:
When operating with glass doors, open the doors and
close the fireplace outside air damper so your fire will be
started using room air. After the fire is well started, you
may open the outside air control and close the doors to
provide air to the fire.
For gas fireplaces:
When lighting your gas fireplace, you MUST always first
open the combustion air damper for the unit to operate and
the glass doors MUST be in place.
Periodically inspect the duct termination for any blockage.
Correct if necessary.
For maximum benefit and efficient usage, refer to operating
instructions in owner's manual.
Replacements parts and service may be obtained through
your dealer.

Other Hearth and Home Technologies Fan manuals

Hearth and Home Technologies GFK4B User manual

Hearth and Home Technologies

Hearth and Home Technologies GFK4B User manual

Hearth and Home Technologies GFK21B User manual

Hearth and Home Technologies

Hearth and Home Technologies GFK21B User manual

Hearth and Home Technologies 19263A User manual

Hearth and Home Technologies

Hearth and Home Technologies 19263A User manual

Popular Fan manuals by other brands

Sulion DENIM 1004847 manual

Sulion

Sulion DENIM 1004847 manual

DeWalt DXF1616 instruction manual

DeWalt

DeWalt DXF1616 instruction manual

Bimar VC82 Instruction booklet

Bimar

Bimar VC82 Instruction booklet

Kichler Lighting Szeplo II instruction manual

Kichler Lighting

Kichler Lighting Szeplo II instruction manual

Clarke air CHV18WF Operation & maintenance instructions

Clarke

Clarke air CHV18WF Operation & maintenance instructions

Dimplex DCPF50MB instruction manual

Dimplex

Dimplex DCPF50MB instruction manual

Hunter 42652-01 Installation and operation manual

Hunter

Hunter 42652-01 Installation and operation manual

Faber FEF 12HD instruction manual

Faber

Faber FEF 12HD instruction manual

Hunter 23933 Parts guide

Hunter

Hunter 23933 Parts guide

D+H RZN 4402-K V2 Instructions for use

D+H

D+H RZN 4402-K V2 Instructions for use

Harbor Breeze 40093 manual

Harbor Breeze

Harbor Breeze 40093 manual

Somogyi HOME SFS 40 instruction manual

Somogyi

Somogyi HOME SFS 40 instruction manual

Vortice VORT NRG EC 3000 Operating and Commissioning Instructions

Vortice

Vortice VORT NRG EC 3000 Operating and Commissioning Instructions

Pichler LG 100 UP OPERATING AND INSTALLATION Manual

Pichler

Pichler LG 100 UP OPERATING AND INSTALLATION Manual

Black & Decker FD1600 user manual

Black & Decker

Black & Decker FD1600 user manual

Vent-Axia NBR DMEV 100 Installation and wiring instructions

Vent-Axia

Vent-Axia NBR DMEV 100 Installation and wiring instructions

ACME YH-40A-0 quick start guide

ACME

ACME YH-40A-0 quick start guide

Hinkley HIGHLAND instruction manual

Hinkley

Hinkley HIGHLAND instruction manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.