Heatwagon VG1000 Manual

Construction
Heater
VG1000
C US
Dept. of Buildings
29-05-E
Installation and Maintenance Manual
Please retain this manual for future reference.
342 N. Co. Rd. 400 East
Va paraiso, IN 46383
219-464-8818 • Fax 219-462-7985
www.heatwagon.com
Revision 12-14
For your safety: Do not use this heater in
a space where gaso ine or other iquids
having f ammab e vapors are stored.

I PORTANT INFOR ATION! READ FIRST
The heater is designed for use as a construction heater under ANSI Z83.7a-2000. Heater is not in-
tended for use in pest remediation. The primary purpose of construction heaters is to provide
temporary heating of buildings under construction, alteration, or repair and to provide emergency
heat. Properly used, the heater provides safe, economical heating. Products of combustion are
vented outside the area being heated.
The heater IS NOT designed as an Unvented Gas Fired Room Heater under ANSI-Z21.11.2 and
SHOULD NOT be used in the home.
ANSI A119.2(NFPA 501C)-1987 Recreational Vehicle Standard prohibits the installation or storage
of LP-gas containers even temporarily inside any recreational vehicle. The standard also prohibits
the use of Unvented Heaters in such vehicles.
NFPA-58 1989 STANDARD FOR THE STORAGE AND
HANDLING OF LIQUEFIED PETROLEU GASES
Use of the heater must be in accordance with this Standard and in compliance with all governing
state and local codes. Storage and handling of propane gas and propane cylinders must be in ac-
cordance with NFPA 58 and all local governing codes.
We cannot anticipate every use which may be made for our heaters. CHECK WITH YOUR LOCAL
FIRE SAFETY AUTHORITY IF YOU HAVE QUESTIONS ABOUT LOCAL REGULATIONS.
Other standards govern the use of fuel gases and heat producing products in specific applications.
Your local authority can advise you about these.
FOR YOUR SAFETY
DO NOT USE THIS HEATER IN A SPACE WHERE GASOLINE OR OTHER LIQ-
UIDS HAVING FLA ABLE VAPORS ARE STORED OR USED.
CONSTRUCTION HEATER GENERAL HAZARD WARNING:
Failure to comply with the precautions and instructions provided with this heater, can
result in death, serious bodily injury and property loss or damage from hazards of fire,
explosion, burn, asphyxiation, carbon monoxide poisoning, and/or electrical shock.
Only persons who can understand and follow the instructions should use or service
this heater.
If you need assistance or heater information such as an instruction manual, labels,
etc., contact your local Heat Wagon dealer or the manufacturer.
WARNING
Fire, burn, inhalation, and explosion hazard. Keep solid combustibles, such as build-
ing materials, paper or cardboard, a safe distance away from the heater as recom-
mended by the instructions. Never use the heater in spaces which do or may contain
volatile or airborne combustibles, or products such as gasoline, solvents, paint thin-
ner, dust particles or unknown chemicals.
Not for home or recreational vehicle use!
If you have read this entire manual and you still have ques-
tions, please call us at 219-464-8818

Table of Contents:
Page
Safety & Caution . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4
Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4
Operating Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8
Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .13
Illustrated Parts Breakdown . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .16
Wiring Diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .23
Senso . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .23
Exhaust Flue Pipe Guidelines . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .29
Installation and Maintenance Manual
Model VG1000
Construction Heater
342 N. Co. Rd. 400 East • Val araiso, IN 46383
219-464-8818 • 888-432-8924 • Fax 800-255-7985
www.heatwagon.com
WARRANTY
This heater is guaranteed against defective materials and workmanship for one (1) year from Heat Wagon invoice
date.
Warranty repairs may be made only by an authorized, trained and certified Heat Wagon dealer. Warranty repairs by
other entities will not be considered. Warranty claims must include model number and serial number. Components
are guaranteed to the extent of the component manufacturer’s warranty.
LI ITATIONS
Warranty claims for service parts (wear parts) such as spark plugs, igniters, and flame rods will not be allowed. Di-
agnostic parts such as voltage meters and pressure gauges are not warrantable. Evidence of improper fuel usage,
fuel pressures outside of manufacturer’s specification, poor fuel quality, improper electric power, misapplication
and/or evidence of abuse may be cause for rejection of warranty claims.
Labor, travel time, mileage and shipping charges will not be allowed. Minor adjustments to heaters are the respon-
sibility of the dealer. Defective parts must be tagged and held for possible return to the factory for 60 days from
date of repair. The factory will provide a return goods authorization, (RGA) for defective parts to be returned. No
warranty will be allowed for parts not purchased from Heat Wagon.

SAFETY & CAUTION
• Instructions given in this manual and the applicable regulation of the local authorities
must be followed.
• The unit may be operated only by those persons who have been instructed in its proper use.
• The unit is to be installed and operated in such a way as to ensure the safety of employees and
surroundings.
• Never cover the unit’s air openings.
• Always ensure adequate fresh air supply to the unit.
• Never stand in front of the discharge end of the heater.
• Keep a minimum clearance of 10 feet from the fuel source. Storing and use of liquid fuel must
comply with the regulation and instructions given by the local authorities.
• Unit’s emitted noise level at the range of 3 feet: 74 dBA.
• Do not introduce foreign objects into the unit.
• Do not expose the unit to direct water jets.
• All electric cables outside the unit are to be protected against damage.
• Always disconnect the unit from power supply and turn off the gas supply when maintenance
or service is being performed.
• IF NOT OPERATED WITHIN GUIDELINES OF THESE OPERATING INSTRUCTIONS,
ANUFACTURER WILL NOT BE HELD RESPONSIBLE AND WARRANTY
WILL BECO E VOID.
4
SPECIFICATIONS
odel No. VG1000
Fuels: Vapor Propane or Natural Gas
Gas Inlet 1-1/4” FNPT (Both Wayne & Midco Burner)
Capacity: 1,000,000 BTU/HR
Blower: 4,075 CFM 5.0HP 2.0”SP
Electrical Rating: 240 Volts, 1Ø 30 Amps
Fuel Consumption: NG-1000 CFH / Propane-11 GPH
Remote Thermostat: On/Off
Max. Discharge Temp.: 200ºF @ 0ºF Ambient
Duct Size: 20” Dia., 200 ft. max (straight)
Shp. Dimensions: 120”L x 31.5”W x 54”H
Weight (approximate): 1,300 lbs.
Gas Supply: Inlet Pressure anifold Pressure Pilot Orifice
idco Burner ax W.C. in W.C. W.C.
Vapor Propane 14” W.C. 9” W.C. 2.6” .046
Natural Gas 14” W.C. 9” W.C. 4.1” .052
Wayne Burner ax W.C. in W.C. W.C.
Vapor Propane 14” W.C. 9” W.C. 3.0” N/A
Natural Gas 14” W.C. 9” W.C. 4.6” N/A

OPERATING INSTRUCTIONS
INSTALLATION
• When transporting, use all four lifting eyes in upper corners or forklift openings in the base of
the units.
• Place the unit on a level and non-combustible surface.
• Minimum clearances from combustibles:
- outlet, minimum 10 feet
- sides, minimum 3 feet
- top, minimum 3 feet
- flue pipe exhaust, gas discharge minimum 2 feet
• Manufacturer recommends a free zone of 5 feet around the unit and a minimum distance of 10
feet at the unit’s flue gas openings are to be maintained.
• If the unit is placed indoors, secure an adequate fresh air opening for the burner combustion air.
• The unit may not be installed and operated in premises where explosive or combustible fumes
or dust are present. Always check the regulation of local authorities.
• Be certain that neither the air inlet nor the air outlet is obstructed.
FUEL SUPPLY
• This heater is shipped as either natural gas or vapor propane. Check for proper pilot orifice in
burner (Midco burner only).
Natural Gas .052
Vapor Propane .046
• Be certain to use adequate hose or pipe size to ensure proper volume and pressure.
See Chart Below.
For supply pressures greater than 1/2psi
• A regulator must be installed on the heater to ensure that the pressure to the heater does not
exceed 1/2 psi inlet pressure. Excessive pressures over 1/2 psi (14” W.C.) will damage controls
and void warranty.
5
NATURAL GAS QUICK
REFERENCE HOSE
Hose BTU
Le gth 1 Millio
i Feet <1PSI 1PSI 2PSI 5PSI
10 1-1/2 1-1/4 3/4 3/4
25 2 1-1/4 3/4 3/4
35 2 1-1/4 3/4 3/4
50 2 1-1/4 1-1/4 3/4
75 2 1-1/4 1-1/4 3/4
100 2 1-1/4 1-1/4 3/4
125 2-1/2 1-1/2 1-1/4 3/4
150 2-1/2 1-1/2 1-1/4 3/4
175 2-1/2 1-1/2 1-1/4 3/4
200 2-1/2 1-1/2 1-1/4 3/4
VAPOR PROPANE QUICK
REFERENCE HOSE
Hose BTU
Le gth 1 Millio
i Feet 1/2PSI 10PSI
10 1-1/4 3/4
25 1-1/4 3/4
35 1-1/4 3/4
50 - 3/4
75 - 3/4
100 - 3/4
125 - 3/4
150 - 3/4
175 - 3/4
200 - 3/4

FUEL SUPPLY (CONTINUED)
• Ensure that for the surrounding temperature, size and capacity of the propane supply cylinder
is adequate to provide the rated Btu/hr input to the heater.
• Visually inspect the hose assembly and ensure that it is protected from traffic, building
materials, and contact with hot surfaces. If it is evident that there is excessive abrasion or wear,
or the hose is cut, replace it immediately.
• Purge air from line and wait 10 minutes for gas to dissipate.
• After installation, check the hose assembly for gas leaks by applying a water and soap solution
to each connection.
• Fuel hose must be UL approved.
• The installation of this heater to a natural gas supply must confirm with all applicable local
codes or, in the absence of local codes, with the National Fuel Ga Code ANSI Z223.1/NFPA 54.
For vapor propane, refer to standard for Storage and Handling of Liquified Petroleum Ga e
ANSI/NFPA 58.
ELECTRICAL
• Electric cable extensions must be connected by qualified authorized electricians based on the
unit capacity and cable length.
• Connect unit to a power supply with a suitable appliance receptacle (30 Amp). Green
indicator lamp will light up.
• Confirm voltage at heater connection (208V min.) to ensure proper operation.
EXHAUST FLUE PIPE
• The unit is to be connected to a flue pipe with adequate draft, to ensure the proper start and
operation of the unit. Refer to page 27.
• The flue pipe is to be made of non-combustible material and clearances from combustible
materials must be a minimum 8 inches (temperature of flue gases is approximately 410º F).
• The flue pipe and its installation must comply with the regulations and instructions given by
the local authorities.
START UP
• Only people trained in the operation and supervision of this heater should operate
and maintain the unit.
• Check the unit to make certain that there are no visible defects on the control and safety
devices and that the unit has been installed correctly.
1. Open door at back of unit (control box compartment).
2. Check that the control switch in the control box is in position “0” (STOP).
3. Pre-select desired room temperature on the room thermostat. The temperature must be set
higher than the ambient temperature.
4. Open all possible shut-off devices of the fuel supply lines and push the reset on the low
pressure gas switch (Wayne Burner Only).
6

START UP (CONTINUED)
5. Turn the control switch in control box to position “1” (HEATING).
6. When the ambient temperature level is lower than thermostat setting, the burner switches
on automatically. The fan does not switch on until the set temperature (104ºF) of the heat-
exchanger has been reached (will take approximately 1-5 minutes).
7. The green indicator lamps for “heating on” and “fan on” will light up now.
8. Close the door in order to protect the unit against unauthorized adjustments.
• After startup, the heater is operated automatically by the room thermostat and governed by all
control devices, including the safety limit controls.
• The room thermostat (TSTAT) and burner sensor control the running sequences of the
burner and the fan sensor controls the fan function.
• Overheat limit reset (STB) controls and shuts off the heater (burner) in the case of overheating.
• The unit can also be used for ventilation purposes only, if needed.
1. Turn the control switch in control box to position “2” (VENTILATION).
2. The unit is now in the continuous ventilating mode.
3. Heating is not possible in this mode.
DUCTING (Warm Air)
• Minimum clearance from combustible materials is 4 inches.
• Use steel ducting or fabric ducting capable of withstanding maximum temperature of 300ºF.
• Maximum length of duct: 200’ (straight).
• Duct diameter: 20”.
• Make certain that the duct is safely and properly fastened to the warm air outlet.
• Avoid sharp bends and corners to ensure maximum air flow and avoid back pressure that can
cause heat accumulation in heater.
• FAILURE TO COMPLY WITH THESE RECOMMENDATIONS COULD RESULT IN SHUTDOWN
OF THE HEATER.
SHUT DOWN
• Turn control switch to position “0” (STOP).
• Close fuel supply.
Important!
The air supply fan continues running for several minutes to cool down the combustion
chamber/heat exchanger. The fan can restart several times before finally switching off!
WARNING!
ELECTRICAL POWER TO THE UNIT AY BE DISCONNECTED IN E ERGENCY SITUATIONS
ONLY. OTHERWISE, DO NOT STOP THE UNIT BY DISCONNECTING POWER. UNIT NEEDS
TO COOL DOWN USING ITS OWN FAN. FAILURE TO CO PLY WITH PROPER SHUT-DOWN
PROCEDURES CAN CAUSE DA AGE TO THE CO BUSTION CHA BER, HEAT
EXCHANGER, SAFETY FEATURES AND VOID WARRANTY.
7

8
1. Turn the
heater to
position #1
and nothing
happens.
2. The heater
runs for a little
while, but
shuts down. It
won’t come on
again until the
limit switch is
reset.
• Power supply cord
• Burner reset button on the burner flame
safeguard control box is engaged
• verheat limit switch is tripped
• Burner motor relay
• Burner sensor
• Heater control unit (HCU)
• Incorrect burner manifold pressure
• Restricted airflow
• verheat limit switch
• Test for 240 volts (min 208) between L1 and L2 on the main terminal block.
• Reset the blue button on the flame safeguard control.
• Reset the switch, which is located in the burner compartment on the gray box
on the left hand side of the burner.
• Burner motor relay is located in the main control box (K2). Check between
ground and L1, then ground and T1 for 120 volts. If less than 105 volts replace
relay.
• n the heater control unit (HCU) disconnect the wires from terminals X10 and
X11. Using an ohm meter, check the resistance between the two wires for a
reading. Compare to Sensor Resistance Chart page 25.
Replace sensor if reading is out of range.
• n the main terminal block, check for 120 volts between terminals 8 and N
when the 3-position switch is in the HEAT position. If less than 105 volts,
replace HCU.
• (Midco Burner) Use a low pressure gauge (0-15 inches of water column) with a
1/4” NPT inlet. Install gauge in the pressure tap port located on the output side
of the last gas solenoid valve in line. Run unit and adjust the manifold
pressure by turning the pressure adjusting screw (located in the center of the
Maxitrol RV81 regulator) in or out until the gauge reads 2.6 inches of W.C. for
propane or 4.1 inches of W.C. for natural gas. (Wayne Burner) 3 inches of W.C.
for propane or 3.5 inches of W.C. for natural gas.
• Check for dirt or ice buildup on the air inlet or blower wheel. If using duct on
the air outlet, ensure the back pressure does not exceed a static pressure of
.2” W.C. Check with magnehelic gauge if necessary.
• Adhere to the proper shut down procedures.
Power must remain at the unit until it cools down fully. Blower will shut down on
its own when cool. Test overheat limit switch for continuity between
the two male terminals at room temperature. Replace if overheat limit switch
fails test. The limit switch is located in the upper left hand corner of burner
compartment.
VG1000 TROUBLESHOOTING
Symptom Possible Causes Possible Solutions

9
3. Burner motor
comes on,
but the heater
won’t ignite.
• Fuel pressure or volume
• Air inlet damper adjustment
• Ignition electrode
• Electronic igniter
• Burner airflow switch
• Gas valve
• Use a low pressure gauge (0-15 inches of water column) with 1/8” NPT inlet.
Install gauge in the pressure tap port located on the output side of the gas
valve. Run the heater. Adjust the pressure by turning the pressure adjusting
screw (located on the input side top of the gas valve) counter clockwise until
the gauge reads the proper manifold pressure. Refer to pipe sizing charts in
the Heat WagonEngineering Guide. Heater requires 9-14” W.C. inlet pressure.
Ensure proper purge procedure (see Fuel Supply Installation).
• Rough setting at 1/2 open. Minor adjustments from the rough settings can be
made to achieve a smooth sounding burner with no soot from the flue pipe.
Insert volt meter probes into provided + and – terminals on the Honeywell
Flame Safeguard Control. Set the volt meter on DC volts and run the heater.
Adjust the air damper until the volt meter reads the highest voltage between 2
and 5 volts.
• Clean with fine sandpaper. Make sure it is free from buildup or cracks.
• Turn off the gas valve, turn on the burner. Use insulated pliers to hold the
ignition wire and short it to ground. Pull the wire away from ground slowly. A
rainbow colored arc should travel between the wire and the ground at a
distance of 3/8 of an inch for a duration of 4-5 seconds.
• The burner airflow switch (located above blue Honeywell safeguard control) will
not allow power to the flame safeguard control when it is open. Check the
tubes supplying air to the switch for any restrictions. NLY AS A TEST, wire
around the air switch. If this test solves the problem, adjust or replace the
switch (Midco Burner nly).
• If there is power at the flame safeguard control and no power out to the
solenoid valves, replace the flame safeguard control. Check for continuity
between the terminals on the solenoid valve coil. If no continuity, replace gas
valve.
VG1000 TROUBLESHOOTING
Symptom Possible Causes Possible Solutions

4. The heater
has a loud
rumbling
sound.
5. The heater
blows black
smoke out of
the vent stack.
• Air damper setting
• Dirt on burner blower wheel
• Flue pipe setup or flue pipe
restrictions
• Gas manifold pressure
• Heat exchanger
• Air damper setting
• Dirt on burner blower wheel
• Flue pipe setup or flue pipe
restrictions
• Gas manifold pressure
• Heat exchanger
• Rough setting at 1/2 open. Minor adjustments from the rough settings can be
made to achieve a smooth sounding burner with no soot from the flue pipe.
Insert volt meter probes into provided + and – terminals on the Honeywell
Flame Safeguard Control. Set the volt meter on DC volts and run the heater.
Adjust the air damper until the volt meter reads the highest voltage between 2
and 5 volts.
• Clean the burner blower wheel with a small brush
• Refer to the flue pipe chart in this manual. Check flue for restriction
• Use a low pressure gauge (0-15 inches of water column) with 1/8” NPT inlet.
Install gauge in the pressure tap port located on the output side of the gas
valve. Run the heater. Adjust the pressure by turning the pressure adjusting
screw (located on the input side top of the gas valve) counter clockwise until
the gauge reads the proper manifold pressure. Refer to pipe sizing charts in
the Heat Wagon Engineering Guide. Heater requires 9-14” W.C. inlet pressure.
• Refer to the cleaning instructions in this manual.
• Rough setting at 1/2 open. Minor adjustments from the rough settings can be
made to achieve a smooth sounding burner with no soot from the flue pipe.
Insert volt meter probes into provided + and – terminals on the Honeywell
Flame Safeguard Control. Set the volt meter on DC volts and run the heater.
Adjust the air damper until the volt meter reads the highest voltage between 2
and 5 volts.
• Clean the burner blower wheel with a small brush
• Refer to the flue pipe chart in this manual. Check flue for restriction
• Use a low pressure gauge (0-15 inches of water column) with 1/8” NPT inlet.
Install gauge in the pressure tap port located on the output side of the gas
valve. Run the heater. Adjust the pressure by turning the pressure adjusting
screw (located on the input side top of the gas valve) counter clockwise until
the gauge reads the proper manifold pressure. Refer to pipe sizing charts in
the Heat Wagon Engineering Guide. Heater requires 9-14” W.C. inlet pressure.
• Refer to the cleaning instructions in this manual.
VG1000 TROUBLESHOOTING
Symptom Possible Causes Possible Solutions
10

6. The burner
seems to
cycle on and
off more
frequently
than what it
should.
7. The burner
starts, but the
main fan
never comes
on.
• Gas manifold pressure
• Dirt on main air blower or setup
of outlet air duct
• Burner sensor
• Heater Control Unit (HCU)
• Fan sensor
• Heater Control Unit (HCU)
• Blower motor relay
• Current overload on blower motor
• Blower motor
• Use a low pressure gauge (0-15 inches of water column) with 1/8” NPT inlet.
Install gauge in the pressure tap port located on the output side of the gas
valve. Run the heater. Adjust the pressure by turning the pressure adjusting
screw (located on the input side top of the gas valve) counter clockwise until
the gauge reads the proper manifold pressure. Refer to pipe sizing charts in
the Heat Wagon Engineering Guide. Heater requires 9-14” W.C. inlet pressure.
• Check for dirt or ice buildup on the air inlet or blower wheel. If using duct on
the air outlet, ensure the back pressure does not exceed a static pressure of
.5” W.C.
• n the heater control unit (HCU) disconnect the wires from terminals X10 and
X11. Using an ohm meter, check the resistance between the two wires for a
reading. Compare to Sensor Resistance Chart page 25. Replace sensor if
reading out of range.
• If all of the above check good, replace the HCU.
• n the heater control unit (HCU) disconnect the wires from terminals X12 and
X13. Using an ohm meter, check the resistance between the two wires for a
reading. Compare to Sensor Resistance Chart page 25.
• Turn the 3-position main switch to the fan position. If the blower runs, check the
fan sensor. If it is good, replace the HCU.
• Turn the 3-position main switch to the fan position. If the relay pulls in, check
for voltage between the L1 and L2 terminals. Then check the voltage between
terminals T1 and T2. The voltage should be the same. If it is less than 105
volts, replace the relay.
• Push the reset button on the overload between terminals A1 and A2 on the
motor relay. If there is no voltage, replace the overload.
• Turn the 3-position main switch to the fan position. Check for voltage between
terminals T1 and T2 on the motor relay. If the voltage checks at 120 volts,
replace the motor.
VG1000 TROUBLESHOOTING
Symptom Possible Causes Possible Solutions
11

8. The burner
continues to
run, but the
fan cycles on
and off.
• Gas manifold pressure
• Fuel supply pressure and
volume
• Fan sensor
• Heater Control Unit (HCU)
• Use a low pressure gauge (0-15 inches of water column) with 1/8” NPT inlet.
Install gauge in the pressure tap port located on the output side of the gas
valve. Run the heater. Adjust the pressure by turning the pressure adjusting
screw (located on the input side top of the gas valve) counter clockwise until
the gauge reads the proper manifold pressure. Refer to pipe sizing charts in
the Heat Wagon Engineering Guide. Heater requires 9-14” W.C. inlet pressure.
• Use a low pressure gauge (0-15 inches of water column) with 1/8” NPT inlet.
Install gauge in the pressure tap port located on the output side of the gas
valve. Run the heater. Adjust the pressure by turning the pressure adjusting
screw (located on the input side top of the gas valve) counter clockwise until
the gauge reads the proper manifold pressure. Refer to pipe sizing charts in
the Heat Wagon Engineering Guide. Heater requires 9-14” W.C. inlet pressure.
• n the heater control unit (HCU) disconnect the wires from terminals X12 and
X13. Using an ohm meter, check the resistance between the two wires for a
reading. Compare to Sensor Resistance Chart page 25. If the test falls out of
this range, replace fan sensor.
• Turn the 3-position main switch to the fan position. If the blower runs, check the
fan sensor. If it is good, replace the HCU.
VG1000 TROUBLESHOOTING
Symptom Possible Causes Possible Solutions
12

13
AINTENANCE
Prior to starting any maintenance work be sure to disconnect unit from power supply until
unit cools down fully and fan shuts off! (Shut Down Procedures page 7)
To ensure the proper function of the unit, it must be serviced on regular basis. Maintenance can
be performed, excluding the control devices and safety limit controls, by an authorized trained &
certified Heat Wagon dealer. The control devices and safety limit controls do not need routine
maintenance. If these items fail they must be replaced.
- Do not use any aggressive cleaning agents, which are harmful or environmentally unfriendly,
when cleaning the unit.
- Do not use water jet when cleaning the unit.
- Pressurized air may be used for maintenance. Be careful not to damage the fan blower wheel
with too much pressure.
- Check whether the unit is free from mechanical damage, replace faulty parts as necessary.
- Check fan blower wheel of the fan at regular intervals and clean it when needed.
- Check functionality of control and safety devices regularly.
- Have the flue gas values of the burner checked regularly by authorized agents.
- Be sure to store the unit in a dust free and dry place when it is not used for a long period of
time. Cover the exhaust flue to prevent entry of foreign objects.

14
SERVICE
• The complete unit, including heat exchanger, combustion chamber and burner should be
cleaned from dust and dirt after every heating period, at a minimum of once per year.
-Removal of combustion chamber:
For proper cleaning of the unit, manufacturer recommends removal of the complete
combustion chamber with heat exchanger.
-Disassembling of burner:
1. Disassemble four tightening bolts on the combustion chamber flange and remove burner’s
mounting flange. Take care not to damage the flange seal.
2. Pull out the burner. Take care not to damage the burner head and power cable.
Next step:
1. Pull off collar (1) from flue gas adapter after having removed the fixing screws.
2. Disassemble flue gas adapter (2) from combustion chamber and pull it off.
3. Disassemble center side panel (3) and insulation (4).
Manufacturer recommends removing the left center side panel (seen from the control
box end).
4. Disassemble tightening bolts at supports of combustion chamber (5) and pull out
combustion chamber sideways.
Important! Take care not to bend or damage supports of combustion chamber!

15
-Heat exchanger
When cleaning the heat exchanger:
1. Disassemble revision cover of heat exchanger (1).
2. Be careful not to tear or damage gasket.
3. Pull all flue gas suppressors (5) (all 15 pcs) out
from flue gas passages. Do not bend them.
4. Clean all flue gas passages (6) with a brush or
vacuum cleaner.
5. Clean flue gas suppressors or replace them, as
necessary.
6. Check gasket of revision cover and replace, as
necessary.
-Combustion chamber
When cleaning the combustion chamber:
1. Clean combustion chamber (7) through its opening (8) with a vacuum cleaner.
-Burner
When servicing the burner:
1. Read the operating and maintenance instructions of the gas burner.
2. Make sure that the burner is exclusively maintained by authorized agents.
-Re-assembly of the unit.
-Heat exchanger:
1. Replace all removed parts in reverse order.
2. Make sure that the gaskets and the revision cover (1) are correctly seated.
-Combustion chamber and burner:
1. Carefully assemble combustion chamber into unit and adjust it. Hand tighten bolts (final
tightening after installing the burner’s mounting flange).
2. Install burner’s mounting flange.
3. Check flange gasket and replace, if necessary.
4. Tighten the screws of combustion chamber supports.
5. Remount all trim panels.
6. Remount flue gas adapter, check gaskets and replace, if necessary.
7. Install burner to the mounting flange. Take care not to damage the burner head and power
cable.
8. Re-install all connections and joints and check them thoroughly.
9. Put unit into service and check proper function of all operating modes.
10. Adjust the burner, if necessary.
Important!
An operation or use other than that indicated in these instructions is prohibited!

16
VG1000
PARTS
BREAKDOWN
ITE PART# DESCRIPTION
1 HWP 214401 Flue Gas Adapter
2 HWP 214402 Cover Plate, Rear
3 HWP 214403 Connecting Profile
4 HWP 214404 Cover Plate, Front
5 HWP 214405 Crane Eye (4)
6 HWP 214406 Air Outlet Adapter
7 HWP 20529 Flange Seal
8 HWP 20471 Oil Burner Flange
9 HWP 110121 Fuel Filter
10 HWP 110008 Oil Burner
HWP 110008B Gas Burner
11 HWP 214411 Burner Compartment Door
12 HWP 214412 Base
13 HWP 214413 Oil Collector
14 HWP 214414 Insulation, Center (left/right)
15 HWP 214415 Insulation, Burner End (left/right)
16 HWP 214416 Side Panel, Burner End
(2, with louvres)
17 HWP 214417 Side Panel, Center (left/right)
18 HWP 214418 Air Inlet Adapter
(1, left/right/right options)
19 HWP 214419 Louvre Panel, Fan End
(2, left/right/right options)
20 HWP 214420 Upper Side Panel, Fan End (2)
21 HWP 214421 Radial Fan
22 HWP 214422 Door Belt
ITE PART# DESCRIPTION
23 HWP 214423 Control Compartment Door
24 HWP 214424 Main Control Box
25 HWP SM6162 Fan Motor
26 HWP A68 V-Belt (2 Required)
27 HWP 214427 Guide Rail (2 Required)
28 HWP 214428 Combustion Chamber &
Heat Exchanger
29 HWP 214429 Air Outlet Cone
Not Shown
HWP 214430 Top Radiation Shield
HWP 214432 Revision Cover
HWP 214433 Gasket for Revision Cover
HWP 214434 Flue Gas Suppressors
HWP 214435 Drive Pulley, Fan
HWP 214500 Centrifical Clutch/Motor Sheave
HWP 214501 11-3/8” Fan Sheave
HWP 214502 Sheave Bushing Fan
HWP 3070 Heat Wagon Logo Decal
HWP 214490 Smoke Flue w/Raincap
HWP 842920 Cover for Honeywell Flame
Safeguard Control
HWP 86250F Fiberglass Gasket Material
HWP 20529 Burner Gasket
Also see Control Box Parts page 28.

ITE PART# DESCRIPTION
1 HWP 6712-05 Flame retention plate with mounting
2 HWP 6736-00 Adj. alloy sleeve
3 HWP 6755-10 Drawer assembly with pilot and vent tube
5 HWP 3197-50 Motor mounting plate
6A HWP 3246-08 Air shutter
7 HWP 6734-00 Air shutter shaft
8 HWP 3152-01 Quadrant - for air shutter adjustment
9 HWP 6724-10 Blower inlet screen
10B HWP 3627-50 G58 & G69-7” diameter x 3-1/2” wide
11B HWP 8437-15 G58-1/2 HP 115/230/1/60
12 HWP 6717-90 Flamerod wire replacement kit
13 HWP 5616-90 Strain relief bushing for spark cable
14 HWP 8409-10 Silicone boot
15 HWP 8502-05 Spark cable
16 HWP 6725-90 Pilot with flamerod and spark rod
17 HWP 6717-00 Flamerod and insulator assembly
18 HWP 6720-90 Mounting clamp for flamerod assembly
19 HWP 6725-50 Spark rod and insulator assembly
20 HWP 6764-00 Spark rod retainer assembly w/O-ring seal
21 HWP 8432-07 Spark rod retainer O-ring
22 HWP 8402-00 Gas safety shut-off valve - 1/8” NPT
23 HWP 8447-22 Ignition trans 120/1/60
24 HWP 6729-91 Pilot air tube blower housing
25C HWP 6766-02 Nat. G58 gas #55 Dr. (.052), air #26 Dr. (.147)
25G HWP 6766-07 Prop G58 gas #56 Dr. (.046), air #26 Dr. (.147)
26 HWP 8429-19 RM7895A Controller
27 HWP 8429-22 ST7800 for RM7895 30 seconds
28 HWP 8429-27 R7847A for RM7895 rectification amplifier
30 HWP 8429-16 O7800 sub-base
32 HWP 8425-19 Blower air switch
33 HWP 8418-21 1” diaphragm valve
34 HWP 8402-06 1-1/4” safety valve
35A HWP 8416-02 RV61 1-1/4” Maxitrol gas pressure regulator
36 HWP 2933-50 On/off butterfly valve
44 HWP 8400-10 Pilot pressure regulator
Not Shown
HWP HV1169 Gauge 15” W.C. Low Pressure (2)
17
IDCO BURNER
PARTS BREAKDOWN

WAYNE BURNER
PARTS BREAKDOWN
18

ITE PART# DESCRIPTION
1 63587-001 Housing LC1000 Base Burner
2 20370-004 Box, unction Deep Mach
3 62407-001 Igniter, Transformer 120V
4 13801 Fitting, Conduit 3/8
5 13034 Bushing, Snap
6 63747-001 Fitting, Adapter
7 550052 Fitting, Hose
8 63599-001 Motor, 1/2HP 120V
9 63593-001 Plate, Sense Bushing
10 62389-002 Bushing, Terminal
11 13026 Bushing, Strain Relief
12 100985-003 Tube, Clear Vinyl 1/4 x 9.5
13 62909-004 Wire, Ignition
14 100408-002 Nut, Lock 1/4 - 20 HXSR
15 63743-001 Wire, Sense Electrode (not shown)
16 63263-005 Switch, Air Sensing
17 LC1000 WHEEL Blower Wheel
20 63769-001 Bracket, Control Mounting “L”
21 63770-XXX (See Bom) Primary Control
22 63771-001 Wiring Subbase
ITE PART# DESCRIPTION
23 63773-XXX (See Bom) Amplifier, Flame
24 63774-XXX (See Bom) Timer, Purge
25 63497-003 Wire, Control Sense
26 31954-001 Strain Relief, Low Profile
27 13801-002 Fitting, Conduit
28 15323 Connector, Conduit
29 100196-019 Conduit, Flex 3/8” x 12
30 14429 Connector, Conduit Duplex
31 100196-016 Conduit, Flex 3/8” x 19.50
32 15731 Screw, 6-32 Hexslt
33 18001 Screw, 1/4-20 x .75
34 62960-001 Decal, Carbon Dioxide Warning
35 63538-001 Decal, Pressure Regulator
36 100010 Decal, Wayne Logo
37 101267-001 Decal, Wayne Logo
38 61756-002 Tag, Wiring Supply
39 63528-003 Decal, Connect To Gas Train
40 63528-004 Decal, Connect to 120V
41 63748-XXX (See Bom) Decal, Rating
42 63749-001 Decal, Nighthawk
Not Shown
HWP HV1169 Gauge 15” W.C. Low Pressure (2)
63804-001 Electrode
63805-001 Flame Sensor
WAYNE BURNER
PARTS BREAKDOWN
19

20
WAYNE BURNER
SERVICING
ELECTRODE
SETTING
Table of contents
Other Heatwagon Heater manuals

Heatwagon
Heatwagon HVF110 User manual

Heatwagon
Heatwagon VG400 Manual

Heatwagon
Heatwagon VF400 Manual

Heatwagon
Heatwagon DG250 Manual

Heatwagon
Heatwagon S1505A Manual

Heatwagon
Heatwagon HRF115 Manual

Heatwagon
Heatwagon S1505 Manual

Heatwagon
Heatwagon 750NEF Manual

Heatwagon
Heatwagon VG500 Manual

Heatwagon
Heatwagon 4200 Manual

Heatwagon
Heatwagon 950H(L) Manual

Heatwagon
Heatwagon S405 Manual

Heatwagon
Heatwagon P4000 Manual

Heatwagon
Heatwagon p1800 Manual

Heatwagon
Heatwagon VG600A Manual

Heatwagon
Heatwagon 1800 Manual

Heatwagon
Heatwagon Jumbo 600 Manual

Heatwagon
Heatwagon 1800B(L) Manual

Heatwagon
Heatwagon HVF110 Manual

Heatwagon
Heatwagon DF400 Manual