Heiman HM-621THS User manual

● Adopts MCU Processing
● Smoke and Carbon Monoxide Dual Detection
● Different Smoke and CO Alarm Audios
● Manual Test / Auto-Reset
● Hush Function
● Low Voltage Compensation
● Temperature Compensation
● Low Battery Warning
● Auto-Check Malfunction in Smoke Chamber
● Anti-RF Interference (20V/m-1GHz)
● Dustproof, Mothproof, Anti-light Interference
● SMT Manufacture Technology with High Reliability
● Shockproof Design Suitable for Vehicle Use
INSTALLATION
1. Since Carbon Monoxide is a little lighter than air and smoke
generated in fires will rise in the air, normally the detector is
installed in a higher position. For wall mounted, install at
about 0.3-1.0m from ceiling. For ceiling mounted, normally
install at the ceiling center of the protected area (refer to the
following image)
2. Fix the detector base into a wall or ceiling with screws and
fasten the detector head on the base.
3. While installing at home, keep the detector away from your
gas stove to prevent flame roasting. Avoid installing in
places with heavy oil or smoke that may cause false alarm or
block the gas convection holes and influence the detector
sensitivity. Also do not install the detector near to exhaust
fans, windows, doors and in places with great vapor in
bathrooms.
CE I L I N G
F L O O R
DE T E C T O R
GASBURNER
User Manual of Smoke and Carbon Monoxide Detector
TECHNICAL PARAMETER
1
PRODUCT INTRODUCTION
PRODUCT PROFILE
FEATURES
Operating Voltage DC 3V (2pcs AA alkaline batteries)
Static Current ≤10uA
Alarm Current ≤25mA
Warm-Up Time 3 minutes
Hush Time 10 minutes
CO Alarm Level (X)
Smoke Sensitivity
Alarm Indication
Failure Indication
Sound Level
Alarm Audios
Working Environment
Installation Mode
Dimension
Execute Criterion
40ppm≤X<75ppm, alarm after 75 minutes
75ppm≤ <
≤, alarm after 30-50 secs (sensor
stabling time)
< 40ppm, alarm reset
X 200ppm, alarm after 25 minutes
200ppm X
0.16dB/m(±0.05dB/m)
Red LED
Yellow LED
≥85dB/3m
Smoke: Di - Di - Di... ; CO: DiDiDiDi...
-10°C ~ +50°C, Humidity≤95RH
Wall or Ceiling mounted
Φ110*45mm
EN50291, UL217, GB15322.5-233
This product is a combination unit of smoke and carbon
monoxide detector. The smoke chamber using the principle of
smoke particles reflecting infrared lights can accurately detect
the early smoke of a fire. And the gas detection adopts a carbon
monoxide electrochemical sensor to ensure stable and constant
performance. When concentration of the leaked carbon
monoxide or smoke density reaches the given alarm level, the
detector LED flashes red and buzzer gives out alarm sounds.
Besides suitable for early warning and protection of carbon
monoxide leakages or fires in houses, villas, factories,
shopping malls, warehouses, office buildings etc. indoor
places, this unit has a subtle shockproof design, which makes it
also suitable for vehicle use.
OPERATING PRINCIPLE
1. Insert 2pcs 1.5V AA batteries into the battery compartment.
The detector enters into warm-up status. LED flashes Green.
2. About 3 minutes later, the flashing Green LED goes out. And
the detector goes into normal working status. The LED
flashes Green once every 30s, indicating normal battery
supply.
1
Test & Hush Button
LED Indicator
Battery Compartment
M201-1EVer1.0

1
1. Replace the batteries with new ones in time on low battery
condition to ensure normal operation.
2. No block within a radius of 0.5m from the detector.
3.The horizontal distance from the detector to the air
conditioner outlet should not be less than 1.5m.
4. If needs to install the detector in an aisle ceiling with a width
less than 3m, choose a center position. Keep the distance
between the detectors less than 15m. The distance from the
detector to the end wall should not exceed half of the
distance between the detectors.
5. Clean the detector surface with soft brush every month to
ensure sensitivity. Do not spray air-freshers, hair gels,
paints or other aerosols near the detector.
6 . T h e l i f e s p a n o f t h e a d o p t e d c a r b o n m o n o x i d e
electrochemical sensor is 5 years. Replace the detector
immediately once its service life expires.
7. Do not use any detergents or solvents to clean the detector.
Chemicals may cause permanent damage or transient
pollution to the sensor.
8. For malfunction problems, contact your dealer. Do not
dismantle and try to repair it privately.
9. The detector can reduce accidents happening, but can not
guarantee a hundred percent safety. For safety consideration,
besides proper usage of the detector, pay attention to build
up safety consciousness and take preventive measures in
daily life.
10. Maintain the detector periodically as per requirements in
this manual.
EMERGENCY ALARM TREATMENTS
NOTES
3. The detector should be tested periodically during use. Short
press Test & Hush Button to run a test. The LED flashes Red
along with buzzer sounding for alarm indication. Smoke
alarm indication and carbon monoxide alarm indication will
be demonstrated in sequence. First is smoke alarm
indication: slow Di-Di-Di... audio along with the LED
flashing red at the same frequency, lasting for about 8s.
Then comes the carbon monoxide alarm indication: short
DiDiDiDi... audio along with the LED flashing red at the
same frequency, lasting also for about 8s. Do not test the
detector too often to save battery life. One a month is
recommended.
4. During alarming status, short press the Test & Hush Button.
Then the detector goes into mute status. The LED keeps
flashing red while the buzzer will stop sounding. If the
alarm status hasn’t been reset, the mute status will end
automatically in 10 minutes later. The buzzer sounds again.
If the alarm status is reset during the 10 minutes, the
detector recovers to normal working status.
5. The detector can auto check open circuit, short circuit and
other malfunctions in smoke chamber. During malfunction,
the LED flashes yellow, twice a minute along with buzzer
sounding to warn user.
6. When battery voltage < 2.4V, the detector will give out low
battery signal periodically. The LED flashes yellow, once
every 30s along with buzzer sounding. While the battery
voltage < 2.0V, the LED constant yellow and the detector
will restart in 32s due to low power. After warm-up and
rechecking the voltage, if still < 2.0V, operation repeats.
Treatments for carbon monoxide leakage alarm:
1. Shut off tube valves.
2. Do not plug or unplug electrical appliances.
3. Open windows to circulate the air.
4. Inspect the leakage reason and notify related departments or
professionals in time to deal with the situation. If it turns out
a false alarm, check if the installing position is improper.
Treatments for smoke alarm:
1. Inspect the causes. If it is caused by cigarette smoking or
other reasons and not a fire alarm, just remove the smoke
resource and the alarm will reset. If it is a false alarm, check
if the installing position is improper.
2. If a fire breaks out, in the early stage, use a fire extinguisher
to put out the fire.
3. If the fire is large, don’t panic. Escape asap and then call the
police.
User Manual of Smoke and Carbon Monoxide Detector
2
INDICATIONS SUMMARY
Indications Analysis Elimination
Afte r p o wer- o n,
LED flashes Green
Normal. Warm-up status. Goes out
3 minutes later. Detector enters into
normal working status.
+
+
After warm-up,
LED flashes Green
once every 30s
Normal indication for normal
working status and normal
battery supply
LED flashes Red
Normal. Caused by pressing Test &
Hush Button under alarm or testing
status. Detector enters into Mute
status.
Repress the Test
& Hush Button to
lift the mute status
LED flashes Yellow
once every 30s
along with buzzer
sounding
Low battery (<2.4V) Replace new
batteries
Replace new
batteries
LED constant
Yellow
Low battery ( that can not
support normal operation
<2.0V)
LED flashes Yellow
twice every minute
along with buzzer
sounding
Malfunction in smoke chamber
Contact your
dealer for
repairing or
replacement
M201-1EVer1.0
Other Heiman Security Sensor manuals
Popular Security Sensor manuals by other brands

Rae
Rae P-1400 Operation manual

FIREGUARD GLOBAL
FIREGUARD GLOBAL FG-BD100 Product introduction

Optex
Optex Smart Line SL-350 QNR installation instructions

Yates
Yates Y-530 user manual

Panasonic
Panasonic SF4B-F31G(V2) instruction manual

System Sensor
System Sensor 5451EIS Installation and maintenance instructions