
2
2.
.INSTALLATION
INSTALLATION
When install the unit, please follow the following principle:
4.1.The height difference between the indoor unit and the outdoor unit
should not exceed 5m;
4.2.The connection pipe length should be not less than 1m;
4.3.The longest connection pipe is 15m
4.4. Normally, the connection pipe does not exceed 5m, if the connection
pipe exceed 5m, it should add some gas for the unit, the amount of the gas
that recharged is based on the diameter and length of the liquid pipe, and the
recharged gas Xg=(the liquid pipe length -5m)*(*sheet*g/m), for example, for
one heat pump single split air conditioner, if the diameter of the liquid pipe is
Ф9.53 , and the liquid pipe length is 7m, it means that it should charge
(7m-5m)*50g/m=100g gas for the unit refer to the following sheet:
The diameter for the
connection pipe(mm) single split air
conditioner
Liquid pipe Gas pipe cooling only
(g/m)
heat pump(g/
m)
Ф6.35 Ф9.53 or
Ф12.7 15 20
Ф6.35 or
Ф9.53
Ф15.88 or
Ф19.05 15 50