Hitachi Relion 650 Series User manual

Relion 650 SERIES
650 series
Version 2.2 IEC
Operation manual


Document ID: 1MRK500128-UEN
Issued: June 2023
Revision: H
Product version: 2.2
© 2017 - 2023 Hitachi Energy. All rights reserved

Copyright
This document and parts thereof must not be reproduced or copied without written permission from
Hitachi Energy, and the contents thereof must not be imparted to a third party, nor used for any
unauthorized purpose.
The software and hardware described in this document is furnished under a license and may be used
or disclosed only in accordance with the terms of such license.
This product includes software developed by the OpenSSL Project for use in the OpenSSL Toolkit
(https://www.openssl.org/). This product includes cryptographic software written/developed by: Eric
Young ([email protected]) and Tim Hudson ([email protected]).
Trademarks
ABB is a registered trademark of ABB Asea Brown Boveri Ltd. Manufactured by/for a Hitachi Energy
company. All other brand or product names mentioned in this document may be trademarks or
registered trademarks of their respective holders.
Warranty
Please inquire about the terms of warranty from your nearest Hitachi Energy representative.

Disclaimer
The data, examples and diagrams in this manual are included solely for the concept or product
description and are not to be deemed as a statement of guaranteed properties. All persons
responsible for applying the equipment addressed in this manual must satisfy themselves that each
intended application is suitable and acceptable, including that any applicable safety or other
operational requirements are complied with. In particular, any risks in applications where a system
failure and/or product failure would create a risk for harm to property or persons (including but not
limited to personal injuries or death) shall be the sole responsibility of the person or entity applying
the equipment, and those so responsible are hereby requested to ensure that all measures are taken
to exclude or mitigate such risks.
This document has been carefully checked by Hitachi Energy, but deviations cannot be completely
ruled out. In case any errors are detected, the reader is kindly requested to notify the manufacturer.
Other than under explicit contractual commitments, in no event shall Hitachi Energy be responsible
or liable for any loss or damage resulting from the use of this manual or the application of the
equipment.

Conformity
This product complies with the directive of the Council of the European Communities on the
approximation of the laws of the Member States relating to electromagnetic compatibility (EMC
Directive 2004/108/EC) and concerning electrical equipment for use within specified voltage limits
(Low-voltage directive 2006/95/EC). This conformity is the result of tests conducted by Hitachi
Energy in accordance with the product standard EN 60255-26 for the EMC directive, and with the
product standards EN 60255-1 and EN 60255-27 for the low voltage directive. The product is
designed in accordance with the international standards of the IEC 60255 series.

Table of contents
Section 1 Introduction....................................................................................................5
1.1 This manual...........................................................................................................................5
1.2 Intended audience.................................................................................................................5
1.3 Product documentation......................................................................................................... 5
1.3.1 Product documentation set..................................................................................................5
1.3.2 Document revision history...................................................................................................6
1.3.3 Related documents............................................................................................................. 7
1.4 Document symbols and conventions.....................................................................................8
1.4.1 Symbols...............................................................................................................................8
1.4.2 Document conventions........................................................................................................9
Section 2 Safety information....................................................................................... 11
2.1 Symbols on the product.......................................................................................................11
2.2 Warnings..............................................................................................................................11
2.3 Caution signs.......................................................................................................................12
2.4 Note signs........................................................................................................................... 13
Section 3 Environmental aspects............................................................................... 15
3.1 Sustainable development....................................................................................................15
3.2 Disposing of the IED............................................................................................................15
Section 4 Overview ......................................................................................................17
4.1 Local HMI............................................................................................................................ 17
4.1.1 Display...............................................................................................................................18
4.1.2 LEDs..................................................................................................................................20
4.1.3 Keypad.............................................................................................................................. 21
4.1.4 Local HMI functionality...................................................................................................... 24
4.1.4.1 Status indication...........................................................................................................24
4.1.4.2 Protection and alarm indication....................................................................................24
4.1.4.3 Parameter management ............................................................................................. 26
4.1.4.4 Front communication....................................................................................................26
4.1.4.5 Single-line diagram...................................................................................................... 27
4.1.4.6 Operation indication symbols....................................................................................... 27
4.2 Authorization....................................................................................................................... 27
4.3 Communication................................................................................................................... 29
4.4 PCM600 tool........................................................................................................................30
4.4.1 Connectivity packages...................................................................................................... 30
Section 5 Using the HMI...............................................................................................33
5.1 Using the local HMI............................................................................................................. 33
5.1.1 On-screen keyboard..........................................................................................................33
5.1.2 Logging on.........................................................................................................................34
5.1.3 Logging off.........................................................................................................................35
1MRK500128-UEN Rev. H Table of contents
650 series 1
Operation manual
© 2017 - 2023 Hitachi Energy. All rights reserved

5.1.4 Turning the display backlight on........................................................................................36
5.1.5 Selecting local or remote use............................................................................................36
5.1.6 Identifying the device.........................................................................................................36
5.1.7 Adjusting the display contrast............................................................................................37
5.1.8 Changing the local HMI language..................................................................................... 37
5.1.9 Navigating in the menu......................................................................................................37
5.1.9.1 Menu structure............................................................................................................. 38
5.1.9.2 Scrolling the display..................................................................................................... 38
5.1.9.3 Changing the default view............................................................................................39
5.1.10 Using function buttons.......................................................................................................39
5.1.11 Using the single-line diagram............................................................................................39
5.1.12 Browsing setting values.....................................................................................................40
5.1.13 Editing values....................................................................................................................41
5.1.13.1 Editing numerical values.............................................................................................. 41
5.1.13.2 Editing string values..................................................................................................... 43
5.1.13.3 Editing enumerated values...........................................................................................44
5.1.13.4 Changing time settings in LHMI................................................................................... 44
5.1.14 Saving settings..................................................................................................................44
5.1.15 Clearing and acknowledging............................................................................................. 45
5.1.16 Using the local HMI help................................................................................................... 45
Section 6 IED operation .............................................................................................. 47
6.1 Normal operation.................................................................................................................47
6.2 Disturbance identification.................................................................................................... 47
6.2.1 Disturbance recording triggering ...................................................................................... 47
6.2.2 Disturbance record analysis .............................................................................................48
6.2.3 Disturbance reports ..........................................................................................................48
6.2.4 IED self-supervision.......................................................................................................... 48
6.2.5 Non-operative functions.................................................................................................... 48
6.3 IED parameterization ..........................................................................................................49
6.3.1 IED settings for IED functionality.......................................................................................49
6.3.2 IED settings for different operating conditions...................................................................49
Section 7 Operating procedures................................................................................. 51
7.1 Monitoring............................................................................................................................51
7.1.1 Indications......................................................................................................................... 51
7.1.1.1 Using auto-indication messages.................................................................................. 51
7.1.1.2 Monitoring alarm data.................................................................................................. 52
7.1.1.3 Monitoring an internal IED fault ...................................................................................52
7.1.2 Measured and calculated values.......................................................................................53
7.1.2.1 Measured values..........................................................................................................53
7.1.2.2 Using the local HMI for monitoring............................................................................... 53
7.1.3 Recorded data...................................................................................................................53
7.1.3.1 Creating disturbance recordings.................................................................................. 54
7.1.3.2 Monitoring disturbance recorder data.......................................................................... 54
7.1.3.3 Controlling and reading disturbance recorder data ..................................................... 55
7.1.3.4 Monitoring events.........................................................................................................56
Table of contents 1MRK500128-UEN Rev. H
2650 series
Operation manual
© 2017 - 2023 Hitachi Energy. All rights reserved

7.1.4 Remote monitoring............................................................................................................56
7.1.4.1 Monitoring the IED remotely.........................................................................................56
7.2 Controlling........................................................................................................................... 57
7.2.1 Controlling circuit breakers and disconnectors..................................................................57
7.3 Resetting the IED................................................................................................................ 57
7.3.1 Clearing and acknowledging via the local HMI..................................................................57
7.4 Changing the IED functionality............................................................................................58
7.4.1 Defining the setting group................................................................................................. 58
7.4.1.1 Activating a setting group.............................................................................................58
7.4.1.2 Browsing and editing setting group values...................................................................59
7.4.2 Activating LEDs.................................................................................................................61
Section 8 Troubleshooting ..........................................................................................63
8.1 Fault tracing.........................................................................................................................63
8.1.1 Identifying hardware errors................................................................................................63
8.1.2 Identifying runtime errors...................................................................................................63
8.1.3 Identifying blocked functions............................................................................................. 63
8.1.4 Identifying communication errors...................................................................................... 63
8.1.4.1 Checking the communication link operation.................................................................63
8.1.4.2 Checking the time synchronization.............................................................................. 64
8.1.5 Running the display test....................................................................................................64
8.1.6 Diagnosing the IED status via the LHMI hint menu...........................................................64
8.2 Indication messages............................................................................................................66
8.2.1 Internal faults.....................................................................................................................66
8.2.2 Warnings........................................................................................................................... 67
8.2.3 Additional indications.........................................................................................................68
8.3 Correction procedures.........................................................................................................68
8.3.1 Creating user accounts and setting and changing passwords..........................................68
8.3.1.1 Changing the password from the LHMI........................................................................68
8.3.2 Identifying IED application problems.................................................................................69
8.3.2.1 Inspecting the wiring.................................................................................................... 69
Section 9 Glossary....................................................................................................... 71
Appendix Third Party Copyright Notices....................................................................79
1.1 PG Custom License: Cyotec License..................................................................................79
1.1.1 CyoEncode 1.0.1...............................................................................................................79
1.2 Carnegie Mellon University License....................................................................................79
1.2.1 Cyrus SASL 2.1.26............................................................................................................79
1.3 Gary McNickle MD5 C++ Library License........................................................................... 80
1.3.1 Gary McNickle MD5 C++ Implementation 1......................................................................80
1.4 PG Custom License: LGPL 2.1 with Libtool Exception....................................................... 80
1.4.1 GNU Libtool release-1-4b..................................................................................................80
1.5 Creative Commons Zero v1.0 Universal............................................................................. 81
1.5.1 SipHash 1.0.......................................................................................................................81
1.6 CMU License.......................................................................................................................83
1.6.1 Net-SNMP 5.9.3................................................................................................................ 83
1MRK500128-UEN Rev. H Table of contents
650 series 3
Operation manual
© 2017 - 2023 Hitachi Energy. All rights reserved

1.7 MIT License.........................................................................................................................83
1.7.1 libexpat 2.5.0, Net-SNMP 5.9.3.........................................................................................83
1.8 BSD 3-clause "New" or "Revised" License......................................................................... 84
1.8.1 Net-SNMP 5.9.3................................................................................................................ 84
1.9 Open LDAP Public License v2.8......................................................................................... 84
1.9.1 OpenLDAP 2.4.46............................................................................................................. 84
1.10 OpenSSL Combined License..............................................................................................85
1.10.1 OpenSSL 1.1.1t.................................................................................................................85
1.11 Berkeley Public License (BSD 2.0 -)................................................................................... 87
1.11.1 vfprintf.c 1.0.......................................................................................................................87
Table of contents 1MRK500128-UEN Rev. H
4650 series
Operation manual
© 2017 - 2023 Hitachi Energy. All rights reserved

Section 1 Introduction
1.1 This manual GUID-AB423A30-13C2-46AF-B7FE-A73BB425EB5F v21
The operation manual contains instructions on how to operate the IED once it has been
commissioned. The manual provides instructions for the monitoring, controlling and setting of the
IED. The manual also describes how to identify disturbances and how to view calculated and
measured power grid data to determine the cause of a fault.
1.2 Intended audience GUID-C9B8127F-5748-4BEA-9E4F-CC762FE28A3A v11
This manual addresses the operator, who operates the IED on a daily basis.
The operator must be trained in and have a basic knowledge of how to operate protection equipment.
The manual contains terms and expressions commonly used to describe this kind of equipment.
1.3 Product documentation
1.3.1 Product documentation set GUID-3AA69EA6-F1D8-47C6-A8E6-562F29C67172 v16
IEC07000220-4-en.vsd
Planning & purchase
Engineering
Installing
Commissioning
Operation
Maintenance
Decommissioning
Deinstalling & disposal
Application manual
Operation manual
Installation manual
Engineering manual
Communication
protocol manual
Cyber security
deployment guideline
Technical manual
Commissioning manual
IEC07000220 V4 EN-US
Figure 1: The intended use of manuals throughout the product lifecycle
The engineering manual contains instructions on how to engineer the IEDs using the various tools
available within the PCM600 software. The manual provides instructions on how to set up a PCM600
1MRK500128-UEN Rev. H Section 1
Introduction
650 series 5
Operation manual
© 2017 - 2023 Hitachi Energy. All rights reserved

project and insert IEDs to the project structure. The manual also recommends a sequence for the
engineering of protection and control functions, as well as communication engineering for IEC 61850.
The installation manual contains instructions on how to install the IED. The manual provides
procedures for mechanical and electrical installation. The chapters are organized in the chronological
order in which the IED should be installed.
The commissioning manual contains instructions on how to commission the IED. The manual can
also be used by system engineers and maintenance personnel for assistance during the testing
phase. The manual provides procedures for the checking of external circuitry and energizing the IED,
parameter setting and configuration as well as verifying settings by secondary injection. The manual
describes the process of testing an IED in a station which is not in service. The chapters are
organized in the chronological order in which the IED should be commissioned. The relevant
procedures may be followed also during the service and maintenance activities.
The operation manual contains instructions on how to operate the IED once it has been
commissioned. The manual provides instructions for the monitoring, controlling and setting of the
IED. The manual also describes how to identify disturbances and how to view calculated and
measured power grid data to determine the cause of a fault.
The application manual contains application descriptions and setting guidelines sorted per function.
The manual can be used to find out when and for what purpose a typical protection function can be
used. The manual can also provide assistance for calculating settings.
The technical manual contains operation principle descriptions, and lists function blocks, logic
diagrams, input and output signals, setting parameters and technical data, sorted per function. The
manual can be used as a technical reference during the engineering phase, installation and
commissioning phase, and during normal service.
The communication protocol manual describes the communication protocols supported by the IED.
The manual concentrates on the vendor-specific implementations.
The point list manual describes the outlook and properties of the data points specific to the IED. The
manual should be used in conjunction with the corresponding communication protocol manual.
The cyber security deployment guideline describes the process for handling cyber security when
communicating with the IED. Certification, Authorization with role based access control, and product
engineering for cyber security related events are described and sorted by function. The guideline can
be used as a technical reference during the engineering phase, installation and commissioning
phase, and during normal service.
1.3.2 Document revision history GUID-BD82A13A-6FA0-4E33-BDBF-23B5A0CF968F v4
Document
revision
Date Product revision History
- 2017–05 2.2.0 First release for product version 2.2
A 2017-10 2.2.1 Ethernet ports with RJ45 connector added. enhancements/
updates made to GENPDIF, ZMFPDIS and ZMFCPDIS.
B 2018-03 2.2.1 Document enhancements and corrections
C 2019-05 2.2.1 PTP enhancements and corrections
D Document not released
E 2020-09 2.2.4 Minor document enhancements and corrections
Table continues on next page
Section 1 1MRK500128-UEN Rev. H
Introduction
6650 series
Operation manual
© 2017 - 2023 Hitachi Energy. All rights reserved

Document
revision
Date Product revision History
F 2021-06 2.2.5 Minor document enhancements and corrections
G 2022-07 2.2.5.4 Introduced RIA600, which is a software implementation of the
IED LHMI panel.
H 2023-06 2.2.6 Minor document enhancements and corrections
1.3.3 Related documents GUID-94E8A5CA-BE1B-45AF-81E7-5A41D34EE112 v10
Documents related to REB650 Document numbers
Application manual 1MRK505388-UEN
Commissioning manual 1MRK505390-UEN
Product guide 1MRK505391-BEN
Technical manual 1MRK505389-UEN
Type test certificate 1MRK505391-TEN
Documents related to REC650 Document numbers
Application manual 1MRK511423-UEN
Commissioning manual 1MRK511425-UEN
Product guide 1MRK511426-BEN
Technical manual 1MRK511424-UEN
Type test certificate 1MRK511426-TEN
Documents related to RED650 Document numbers
Application manual 1MRK505393-UEN
Commissioning manual 1MRK505395-UEN
Product guide 1MRK505396-BEN
Technical manual 1MRK505394-UEN
Type test certificate 1MRK505396-TEN
Documents related to REL650 Document numbers
Application manual 1MRK506381-UEN
Commissioning manual 1MRK506383-UEN
Product guide 1MRK506384-BEN
Technical manual 1MRK506382-UEN
Type test certificate 1MRK506384-TEN
1MRK500128-UEN Rev. H Section 1
Introduction
650 series 7
Operation manual
© 2017 - 2023 Hitachi Energy. All rights reserved

Documents related to REQ650 Document numbers
Application manual 1MRK505383-UEN
Commissioning manual 1MRK505385-UEN
Product guide 1MRK505386-BEN
Technical manual 1MRK505384-UEN
Type test certificate 1MRK505386-TEN
Documents related to RET650 Document numbers
Application manual 1MRK504169-UEN
Commissioning manual 1MRK504171-UEN
Product guide 1MRK504172-BEN
Technical manual 1MRK504170-UEN
Type test certificate 1MRK504172-TEN
650 series manuals Document numbers
Operation manual 1MRK500128-UEN
Engineering manual 1MRK511420-UEN
Installation manual 1MRK514027-UEN
Communication protocol manual, DNP3 1MRK511413-UUS
Communication protocol manual, IEC 60870-5-103 1MRK511416-UEN
Communication protocol manual, IEC 61850 Edition 1 1MRK511414-UEN
Communication protocol manual, IEC 61850 Edition 2 1MRK511415-UEN
Communication protocol manual, LON 1MRK511417-UEN
Communication protocol manual, SPA 1MRK511418-UEN
Point list manual, DNP3 1MRK511419-UUS
Accessories guide IEC: 1MRK514012-UEN
Cyber security deployment guideline 1MRK511421-UEN
Connection and Installation components 1MRK513003-BEN
Test system, COMBITEST 1MRK512001-BEN
Application guide, Communication set-up 1MRK505382-UEN
1.4 Document symbols and conventions
1.4.1 Symbols GUID-2945B229-DAB0-4F15-8A0E-B9CF0C2C7B15 v13
The electrical warning icon indicates the presence of a hazard which could result in
electrical shock.
The warning icon indicates the presence of a hazard which could result in personal injury.
Section 1 1MRK500128-UEN Rev. H
Introduction
8650 series
Operation manual
© 2017 - 2023 Hitachi Energy. All rights reserved

The caution hot surface icon indicates important information or warning about the
temperature of product surfaces.
Class 1 Laser product. Take adequate measures to protect the eyes and do not view
directly with optical instruments.
The caution icon indicates important information or warning related to the concept
discussed in the text. It might indicate the presence of a hazard which could result in
corruption of software or damage to equipment or property.
The information icon alerts the reader of important facts and conditions.
The tip icon indicates advice on, for example, how to design your project or how to use a
certain function.
Although warning hazards are related to personal injury, it is necessary to understand that under
certain operational conditions, operation of damaged equipment may result in degraded process
performance leading to personal injury or death. It is important that the user fully complies with all
warning and cautionary notices.
1.4.2 Document conventions GUID-96DFAB1A-98FE-4B26-8E90-F7CEB14B1AB6 v9
• Abbreviations and acronyms in this manual are spelled out in the glossary. The glossary also
contains definitions of important terms.
• Push button navigation in the LHMI menu structure is presented by using the push button icons.
For example, to navigate between the options, use and .
• HMI menu paths are presented in bold.
For example, select Main menu/Settings.
• LHMI messages are shown in Courier font.
For example, to save the changes in non-volatile memory, select Yes and press .
• Parameter names are shown in italics.
For example, the function can be enabled and disabled with the Operation setting.
• Each function block symbol shows the available input/output signal.
• the character ^ in front of an input/output signal name indicates that the signal name may
be customized using the PCM600 software.
• the character * after an input signal name indicates that the signal must be connected to
another function block in the application configuration to achieve a valid application
configuration.
• Dimensions are provided both in inches and millimeters. If it is not specifically mentioned then
the dimension is in millimeters.
1MRK500128-UEN Rev. H Section 1
Introduction
650 series 9
Operation manual
© 2017 - 2023 Hitachi Energy. All rights reserved

10

Section 2 Safety information
2.1 Symbols on the product GUID-E48F2EC3-6AB8-4ECF-A77E-F16CE45CA5FD v4
All warnings must be observed.
Read the entire manual before doing installation or any maintenance work on the product.
Class 1 Laser product. Take adequate measures to protect your eyes and do not view
directly with optical instruments.
Do not touch the unit in operation. The installation shall take into account the worst case
temperature.
2.2 Warnings IP1504-1 v2
Observe the warnings during all types of work related to the product.
GUID-C9B6638A-57E7-4E05-9A33-A60E359C54AF v1
Only electrically skilled persons with the proper authorization and knowledge of any
safety hazards are allowed to carry out the electrical installation.
M2366-2 v2
National and local electrical safety regulations must always be followed. Working in a
high voltage environment requires serious approach to avoid human injuries and damage
to equipment.
M2362-2 v1
Do not touch circuitry during operation. Potentially lethal voltages and currents are
present.
M2364-2 v1
Always use suitable isolated test pins when measuring signals in open circuitry.
Potentially lethal voltages and currents are present.
M2370-2 v1
Never connect or disconnect a wire and/or a connector to or from a IED during normal
operation. Hazardous voltages and currents are present that may be lethal. Operation
may be disrupted and IED and measuring circuitry may be damaged.
GUID-BEDD698E-356C-4CF9-9DAE-64DB3CEADEAD v1
Dangerous voltages can occur on the connectors, even though the auxiliary voltage has
been disconnected.
1MRK500128-UEN Rev. H Section 2
Safety information
650 series 11
Operation manual
© 2017 - 2023 Hitachi Energy. All rights reserved

M2369-2 v3
Always connect the IED to protective earth, regardless of the operating conditions. This
also applies to special occasions such as bench testing, demonstrations and off-site
configuration. This is class 1 equipment that shall be earthed.
M2367-2 v1
Never disconnect the secondary connection of current transformer circuit without short-
circuiting the transformer’s secondary winding. Operating a current transformer with the
secondary winding open will cause a massive potential build-up that may damage the
transformer and may cause injuries to humans.
M2372-2 v1
Never remove any screw from a powered IED or from a IED connected to powered
circuitry. Potentially lethal voltages and currents are present.
SEMOD168311-3 v1
Take adequate measures to protect the eyes. Never look into the laser beam.
GUID-11CCF92B-E9E7-409C-84D0-DFDEA1DCBE85 v2
The IED with accessories should be mounted in a cubicle in a restricted access area
within a power station, station or industrial or retail environment.
2.3 Caution signs IP1503-1 v1
GUID-5D1412B8-8F9D-4D39-B6D1-60FB35797FD0 v3
Whenever changes are made in the IED, measures should be taken to avoid inadvertent
tripping.
GUID-F2A7BD77-80FB-48F0-AAE5-BE73DE520CC2 v1
The IED contains components which are sensitive to electrostatic discharge. ESD
precautions shall always be observed prior to touching components.
M2695-2 v2
Always transport PCBs (modules) using certified conductive bags.
M2696-2 v1
Do not connect live wires to the IED. Internal circuitry may be damaged
M2697-2 v2
Always use a conductive wrist strap connected to protective earth when replacing
modules. Electrostatic discharge (ESD) may damage the module and IED circuitry.
M2698-2 v2
Take care to avoid electrical shock during installation and commissioning.
Section 2 1MRK500128-UEN Rev. H
Safety information
12 650 series
Operation manual
© 2017 - 2023 Hitachi Energy. All rights reserved

M2693-2 v2
Changing the active setting group will inevitably change the IED's operation. Be careful
and check regulations before making the change.
2.4 Note signs IP1497-1 v1
M19-2 v3
Observe the maximum allowed continuous current for the different current transformer
inputs of the IED. See technical data.
1MRK500128-UEN Rev. H Section 2
Safety information
650 series 13
Operation manual
© 2017 - 2023 Hitachi Energy. All rights reserved

14
Other manuals for Relion 650 Series
1
Table of contents
Other Hitachi Control System manuals
Popular Control System manuals by other brands

ETC
ETC sensor+ CEM+ Configuration manual

Rockwell Automation
Rockwell Automation CENTERLINE 2100 instruction manual

Pentair
Pentair SunTouch Installation and user guide

IV Produkt
IV Produkt IVC3 Basic Manual

S&S Northern
S&S Northern Merlin 1000VW+ Installation, operating and maintenance

Cleode
Cleode ZigBee user manual