manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. HMS
  6. •
  7. Switch
  8. •
  9. HMS HMS-EN2MB-R Assembly instructions

HMS HMS-EN2MB-R Assembly instructions

Other manuals for HMS-EN2MB-R

1

Other HMS Switch manuals

HMS Anybus AWB5011 User guide

HMS

HMS Anybus AWB5011 User guide

HMS Anybus AWB5001 Installation and operating manual

HMS

HMS Anybus AWB5001 Installation and operating manual

HMS Anybus AWB4005 User guide

HMS

HMS Anybus AWB4005 User guide

HMS Anybus AWB5005 Installation instructions

HMS

HMS Anybus AWB5005 Installation instructions

Popular Switch manuals by other brands

SMC Networks SMC6224M Technical specifications

SMC Networks

SMC Networks SMC6224M Technical specifications

Aeotec ZWA003-S operating manual

Aeotec

Aeotec ZWA003-S operating manual

TRENDnet TK-209i Quick installation guide

TRENDnet

TRENDnet TK-209i Quick installation guide

Planet FGSW-2022VHP user manual

Planet

Planet FGSW-2022VHP user manual

Avocent AutoView 2000  AV2000BC AV2000BC Installer/user guide

Avocent

Avocent AutoView 2000 AV2000BC AV2000BC Installer/user guide

Moxa Technologies PT-7728 Series user manual

Moxa Technologies

Moxa Technologies PT-7728 Series user manual

Intos Electronic inLine 35392I operating instructions

Intos Electronic

Intos Electronic inLine 35392I operating instructions

Cisco Catalyst 3560-X-24T Technical specifications

Cisco

Cisco Catalyst 3560-X-24T Technical specifications

Asante IntraCore IC3648 Specifications

Asante

Asante IntraCore IC3648 Specifications

Siemens SIRIUS 3SE7310-1AE Series Original operating instructions

Siemens

Siemens SIRIUS 3SE7310-1AE Series Original operating instructions

Edge-Core DCS520 quick start guide

Edge-Core

Edge-Core DCS520 quick start guide

RGBLE S00203 user manual

RGBLE

RGBLE S00203 user manual

Thrustmaster FLIGHT SIMULATOR X quick guide

Thrustmaster

Thrustmaster FLIGHT SIMULATOR X quick guide

Southwire SURGE GUARD 41390 RVC troubleshooting guide

Southwire

Southwire SURGE GUARD 41390 RVC troubleshooting guide

Buhler Nivotemp NT 61 Brief instructions

Buhler

Buhler Nivotemp NT 61 Brief instructions

Kramer VS-41HDCP user manual

Kramer

Kramer VS-41HDCP user manual

Techly IDATA AU-270 user manual

Techly

Techly IDATA AU-270 user manual

Belkin F1U109 user manual

Belkin

Belkin F1U109 user manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.

HMS-EN2MB-R Linking Device
INSTALLATION SHEET
HMS Industrial Networks AB
Web: www.anybus.com
Tel: +46 35 172900
E-mail: [email protected]
SP2093, rev 1.02, March 2017. www.anybus.com
Device Front
Top View
Power:
(+) +24 V DC
(-) GND
(A) FE
SD card slot:
Modbus-TCP Connector:
Pin no Description
1 TX+
2 TX-
3 RX+
6 RX-
4, 5, 7, 8 Termination
18
Bottom View
(Front)
Further informaon and documents about this product can be found at
the product pages on www.anybus.com.
1
2
3
5
6
7
8
4
EtherNet/IP
Connector:
Pin no Description
1 TX+
2 TX-
3 RX+
6 RX-
4, 5, 7, 8 Termination
18
USB port:
Connect a PC to the USB port
for firmware upgrades.
LED Indicators
No Name Indication Meaning
Module Status
EtherNet/IP
Off
Alternating red/green
Flashing green
Green
Flashing red
Red
Power off
Boot sequence
Idle
Running
Major or minor recoverable error
Major or minor unrecoverable error
(Exception state or FATAL)
Network Status
EtherNet/IP
Off
Green
Flashing green
Red
Flashing red
No power or no IP address
Online, one or more connections estab-
lished (CIP Class 1 or 3)
Online, no connections established
Duplicate IP address, FATAL error
One or more connections timed out (CIP
Class 1 or 3)
EtherNet/IP
Ethernet Link 1
and 2
Off
Flashing green
Flashing yellow
No link
Receiving/transmitting Ethernet packets
at 100 Mbit
Receiving/transmitting Ethernet packets
at 10 Mbit
SD Card Green
Red
Accessing SD card
Failure
Modbus-TCP
Status
Off
Green
Flashing green
Flashing red
Red
Power off
Communicating with Modbus-TCP network
Idle
Transaction error or timeout
Fatal error
Modbus-TCP
Ethernet Link 1
and 2
Off
Flashing green
Flashing yellow
No link
Receiving/transmitting Ethernet packets
at 100 Mbit
Receiving/transmitting Ethernet packets
at 10 Mbit
1
2
34
5
6
78
Installation and Startup Summary
• Aach the linking device to the DIN-rail.
• Connect the device to the EtherNet/IP network.
• Connect the device to the Modbus-TCP network.
• Turn on the device (+24 V DC).
• Assign an IP address to the device using BOOTP-DHCP server.
• Start the Studio 5000 soware.
• Search in the catalogue for the HMS-EN2MB-R.
• Add the device to the Ethernet network in the I/O configuraon.
• In the general tab, assign a name and the previously chosen IP
address to the device.
• Configure the device using the configuraon manager and down-
load the configuraon to the device.
• Set up the EtherNet/IP communicaon according to the device
configuraon.
Technical Details
• Power supply:
24 V DC (-15% to +20%).
• Power consumpon:
Maximum power consumpon is 300 mA @ 24 V DC.
Typical power consumpon: 150 mA @ 24 V DC.
• Surrounding temperature
70 degrees C @ 225 mA @ 24 V DC.
• Funconal Earth (FE):
Internal connecon to FE via DIN-rail or, if the DIN-rail can not be
used, via the power connector.
Note: Make sure the DIN-rail is properly connected to FE.
For maintenance and support, contact the HMS support department.
Contact informaon is available at the support pages on
www.anybus.com.
X1.1
X1.2
X3
X2.2
X2.1
HMS-EN2MB-R Linking Device
INSTALLATION SHEET
Further informaon and documents about this product can be found at
the product pages on www.anybus.com.
Supply voltage: The linking device requires a regulated 24 (20.4-28.8V)
VDC power source.
Field wiring terminal markings (wire type Cu only, 14-30AWG)
“Use 105oC copper (Cu) wire only”
Terminal ghtening torque (5-7 lb-in).
Use in Overvoltage Category I Polluon Degree 2 Environment.
Install in an enclosure considered representave of the intended use.
To comply with ATEX direcves, the equipment must be installed within
an IP54 enclosure and must be installed with a transient suppressor on
the supply that does not exceed 140% (33.6 V DC) of the nominal rated
supply voltage.
Operang temperature/Surrounding temperature:
-25oto +60odegrees C @ 300 mA @ 24 V DC.
NOTE: If the surrounding temperature exceeds +40° C, install the unit
with at least 10 mm of air on each side.
Maximum surface temperature: 135 degrees C.
Pressure: 850 - 1050 millibar.
This product is designed to safely operate in class I, division 2 Hazard-
ous locaon according to ANSI/ISA 12.12.01-2015 and category 3, zone
2 according to EN 60079-0 and EN 60079-15.
SUITABLE FOR USE IN CLASS I, DIVISION 2, GROUPS A, B, C AND D HAZ-
ARDOUS LOCATIONS, OR NONHAZARDOUS LOCATIONS ONLY.
Additional Installation and Operating
Instructions
This product is in accordance with the EMC direcve 2014/30/EU through
conformance with the following standards:
• EN 61000-6-4
Emission standard for industrial environment
EN 55016-2-3, Class A
• EN 61000-6-2
Immunity for industrial environment
EN 61000-4-2
EN 61000-4-3
EN 61000-4-4
EN 61000-4-5
EN 61000-4-6
EMC Compliance (CE)
Warnings
• WARNING - EXPLOSION HAZARD - SUBSTITUTION
OF ANY COMPONENTS MAY IMPAIR SUITABILITY
FOR CLASS I, DIVISION 2.
• WARNING - EXPLOSION HAZARD - WHEN IN HAZ-
ARDOUS LOCATIONS, TURN OFF POWER BEFORE
REPLACING OR WIRING MODULES.
• WARNING - EXPLOSION HAZARD - DO NOT DIS-
CONNECT EQUIPMENT WHILE THE CURCUIT IS
LIVE OR UNLESS THE AREA IS KNOWN TO BE
FREE OF IGNITABLE CONCENTRATIONS.
• WARNING - EXPLOSION HAZARD- THE USB CON-
NECTOR IS NOT FOR USE IN HAZARDOUS LOCA-
TIONS AND FOR TEMPORARY CONNECTION ONLY.
DO NOT USE, CONNECT OR DISCONNECT UNLESS
THE AREA IS KNOWN TO BE NONHAZARDOUS.
CONNECTION OR DISCONNECTION IN AN EXPLO-
SIVE ATMOSPHERE COULD RESULT IN AN EXPLO-
SION.
• WARNING - EXPLOSION HAZARD - DO NOT CON-
NECT OR DISCONNECT THE SD CARD UNLESS
THE AREA IS KNOWN TO BE NONHAZARDOUS.
CONNECTION OR DISCONNECTION IN AN EXPLO-
SIVE ATMOSPHERE COULD RESULT IN AN EXPLO-
SION.
• WARNING - INSTALL IN AN ENCLOSURE CON-
SIDERED REPRESENTATIVE OF THE INTENDED
USE. TO COMPLY WITH ATEX DIRECTIVES, THE
EQUIPMENT MUST BE INSTALLED WITHIN AN IP54
ENCLOSURE AND MUST BE INSTALLED WITH A
TRANSIENT SUPPRESSOR ON THE SUPPLY THAT
DOES NOT EXCEED 140% (33.6 V DC) OF THE
NOMINAL RATED SUPPLY VOLTAGE.
Atex Certification
EX nA IIC T4 Gc
II 3 G
Demko 12 ATEX 1062524X
Y
DIN-rail Mounting
Ensure that the DIN-rail fastening
mechanism on the back of the module
is in a fixed and closed posion, i. e.
that it is pushed all the way up.
To mount the device, first hook it on
to the DIN-rail (1), then push it against
the DIN-rail to make it snap on (2).
To unmount the device, use a screw-
driver to push the DIN-rail fastening
mechanism on the back of the device
down unl it locks in a fixed and open
posion (1). Then unhook the device
from the DIN-rail (2).
Note: Do not leave the device with the DIN-rail fastening mechanism in a fixed
and open posion. This may cause unneccessary wear on the fastening mecha-
nism, so that it cannot be used efficiently. Be sure to push the DIN-rail fastening
mechanism back into the fixed and closed posion aer unmounng the device,
with reference to the picture below.
HMS-EN2MB-R
Tsurrounding = 70oC @ 225mA @24VDC Ityp: 150mA
Label Markings
Surrounding air
temperature and
electrical rangs
Cerficaon markings
Warnings
HMS Industrial Networks AB
Staonsgatan 37
302 45 Halmstad
Sweden
UL Certification
Ind. Contr. Eq./Haz.Loc.
22ZB, E214107
67AM, E203225
CL1, DIV 2, GP A, B, C, D
TEMP CODE T4