manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. Honeywell
  6. •
  7. Control Unit
  8. •
  9. Honeywell ADEMCO 4229 Assembly instructions

Honeywell ADEMCO 4229 Assembly instructions

ADEMCO 4229
WIRED ZONE EXPANDER/RELAY MODULE
INSTALLATION AND SETUP GUIDE
GENERAL INFORMATION
The ADEMCO 4229 Wired Zone Expander/Relay Module
adds up to eight end-of-line resistor supervised zones and
two dry form C (SPDT) relay outputs to compatible control
communicators via the control’s keypad wiring.
The module may be mounted within the control’s cabinet (if
room permits), or remotely. If mounted remotely, there are
provisions to tamper-protect the unit. Communication to the
module is supervised so that it cannot be disconnected from
the keypad wiring without detection by the control. If the
wiring is cut, a tamper or alarm signal will result, to indicate
that this device (and possibly other similarly connected
devices) has become inoperative.
IMPORTANT: Some carbon monoxide detectors may not be
compatible with the ADEMCO 4229 hardwire zone
expanders. When using carbon monoxide detectors in
systems that support the 4229 zone expanders, install the
detectors only on the basic hardwire zones of the system
control panel, and NOT on the zone expanders.
INSTALLATION
When the module is to be mounted inside the control’s
cabinet
, it should be mounted horizontally. Insert self-
tapping screws (provided) in two adjacent raised tabs at the
back of the cabinet. Leave the heads projecting 1/8”. Hang
the module on the screw heads via two of the slotted holes
on the back of its housing. In this case, the module’s cover
need not be tamper protected.
See the control’s instructions
for additional information.
When the module is to be mounted remotely
, holes on its
back permit it to be mounted horizontally or vertically.
Wires
can exit from the side or the breakout on the back of its
housing. Place DIP switch #8 in the OFF position and,
when the installation is completed, the module’s cover put
on. A magnet in the cover, positioned near a reed switch in
the unit, will cause a tamper signal to be sent to the control if
the cover is removed.
Affix the connections label that accompanies the unit to the
inside of the module’s cover (if the cover is to be used)) or to
the inside of the control’s cover
CONNECTIONS AND SETTINGS
See the table and the diagram on the reverse side.
Make protection zone connections
to 12-position terminal
block TB1. Each zone that is used must have a 2K ohm
end-of-line resistor connected
across the end of its loop
,
as shown.
If a zone is not programmed, the resistor need not be used.
The method of programming each zone for type of alarm
and reporting code to the central monitoring station varies
with the control to which the module is connected. Refer to
the installation instructions for that control unit.
Set the DIP switch to one of 31 addresses, as shown in the
table on the reverse side
, so the control can identify the
module and communicate with it properly.
The address to
be set is determined by the particular control to be used,
and the control’s installation instructions must be consulted.
As shipped, the DIP switch is set for an address of “0.”
Zone A can be set for a fast response time
of 10ms to an
open circuit, if desired, by setting position 1 of the DIP
switch to “OFF.”As shipped, it is set to “ON”for a response
time of 300ms, as shown in the table on the reverse side.
All of the module’s other protection zones have a nominal
response time of 300ms.
Connections to the module’s two relays are made via the 7-
conductor cord provided.
Refer to the control’s installation
instructions for specific information on how to program the
control’s various activation options for the relays.
Connections to the control’s keypad wiring points
can be
made via 4-position terminal block TB2, the 4-pin plug, or
both (wire color connections are the same)
SPECIFICATIONS
Physical 6-7/16”W x 4-1/4”H x 1-1/4”D
(163mm x 108mm x 32mm)
Electrical
Input Voltage: 12VDC (from control’s remote keypad
connection points)
Input Current: 30mA (relays off)
100mA (relays on)
Relay Contact
Rating: 2A max. at 28VDC/AC
ÊN8910V2OŠ
N8910V2 5/11 Rev. B
4229 ADDRESS SETTINGS
SWITCH
NUMBER ("—" means "OFF")
012
345678910 11 12 13 14 15
2
ON
—
ON —ON —ON —ON —ON —ON —ON —
3
ON ON
—
—ON ON ——ON ON ——ON ON ——
4
ON ON ON ON ————ON ON ON ON ————
5
ON ON ON ON ON ON ON ON ————————
12 34 5
➞
OFF ON
DIP SWITCH: (WHITE AREAS DENOTE SWITCH HANDLES)
4229-003-V1
POSITIONS 2-6:
POSITION 1:
DETERMINE ZONE EXPANDER'S ADDRESS. CONSULT CONTROL'S INSTRUCTIONS
FOR ADDRESS USE.
SWITCH SETTING SHOWN SET FOR ADDRESS "0".
DETERMINES ZONE A's RESPONSE TIME:
ON = NORMAL (300MS) RESPONSE, SHOWN (AS SHIPPED).
OFF = FAST (10MS) RESPONSE TO AN OPEN.
6
ON ON ON ON ON ON ON ON
678
16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31
ON —ON —ON —ON —ON —ON —ON —ON —
ON ON ——ON ON
—
—ON ON ——ON ON ——
ON ON ON ON ——
—
—ON ON ON ON ————
ON ON ON ON ON ON ON ON ————————
————————
——————
—
—
ON ON ON ON ON ON ON ON
POSITION 7:
POSITION 8:
DIP SWITCH POSITION #7: NOT USED LEAVE ON
DIP SWITCH POSITION #8: CASE TAMPER ON = DISABLED OFF= ENABLED
NOTE: ADDRESSES 16-31 MAY NOT BE AVAILABLE; CONSULT THE HOST CONTROL PANEL
INSTALLATION INSTRUCTIONS.
EOLR value is 2K ohms.
GRN
BLK
(–) GROUND
RED
(+) 12V
YEL
PIN
1
4
3
2
1
ZONES
DIP SWITCH
FOR SETTING
ADDRESS AND
ZONE "A" RESPONSE
TB1
WIRED ZONE
EXPANDER/RELAY
MODULE
TB2
RELAY
2
RELAY
1
DATA OUT
TO CONTROL
DATA IN
FROM CONTROL
REED
(TAMPER)
SWITCH
TERMINATE EACH PROGRAMMED ZONE
WITH 2K OHM END-OF-LINE RESISTOR
(EACH ZONE'S MAX. LOOP RESISTANCE:
300 OHMS + EOL)
4-PIN
CONSOLE
PLUG
EITHER
OR BOTH
CAN BE
USED
4229-004-V1
23456178
BRN
WHT
GRY
VIO
BLK
YEL
ORG
NO
NC
C
GND
NO
NC
C
RLY
1
RLY
2
RELAYS
"OFF"
RELAY
CONNECTOR
{
{
{
1
2
3
4
5811
2
1346
7910 12
ABC DFGH
E
2K
FOR LIMITATIONS OF THE ENTIRE ALARM SYSTEM, REFER TO THE INSTALLATION AND SETUP GUIDE FOR THE CONTROL
PANEL WITH WHICH THIS DEVICE IS USED.
For the latest warranty information, please go to:
http://www.security.honeywell.com/hsc/resources/wa
2 Corporate Center Drive, Suite 100
P.O. Box 9040, Melville, NY 11747
Copyright © 2008 Honeywell International Inc.

Other Honeywell Control Unit manuals

Honeywell AlarmNet IGSMHS Assembly instructions

Honeywell

Honeywell AlarmNet IGSMHS Assembly instructions

Honeywell MAXON 8730 Series User manual

Honeywell

Honeywell MAXON 8730 Series User manual

Honeywell 4219 Assembly instructions

Honeywell

Honeywell 4219 Assembly instructions

Honeywell T7270A2001 User manual

Honeywell

Honeywell T7270A2001 User manual

Honeywell TS131 User manual

Honeywell

Honeywell TS131 User manual

Honeywell Centraline FALCON User manual

Honeywell

Honeywell Centraline FALCON User manual

Honeywell SG160S User manual

Honeywell

Honeywell SG160S User manual

Honeywell V305 Series User manual

Honeywell

Honeywell V305 Series User manual

Honeywell NK298S User manual

Honeywell

Honeywell NK298S User manual

Honeywell DCCC6500 User manual

Honeywell

Honeywell DCCC6500 User manual

Honeywell S4560 User manual

Honeywell

Honeywell S4560 User manual

Honeywell NOTIFIER FW-MM User manual

Honeywell

Honeywell NOTIFIER FW-MM User manual

Honeywell VR8200A User manual

Honeywell

Honeywell VR8200A User manual

Honeywell D15SN A Series User manual

Honeywell

Honeywell D15SN A Series User manual

Honeywell Ex-Or MLSUC500 User manual

Honeywell

Honeywell Ex-Or MLSUC500 User manual

Honeywell REDLINK ERM5220R Operation manual

Honeywell

Honeywell REDLINK ERM5220R Operation manual

Honeywell Resideo ADEMCO 4101SN V-Plex Assembly instructions

Honeywell

Honeywell Resideo ADEMCO 4101SN V-Plex Assembly instructions

Honeywell SV2 Series User manual

Honeywell

Honeywell SV2 Series User manual

Honeywell 5496 User manual

Honeywell

Honeywell 5496 User manual

Honeywell DCCC6500 User manual

Honeywell

Honeywell DCCC6500 User manual

Honeywell PENA D MLS2000SSP Installation and operation manual

Honeywell

Honeywell PENA D MLS2000SSP Installation and operation manual

Honeywell 7800 SERIES User manual

Honeywell

Honeywell 7800 SERIES User manual

Honeywell V4730C User manual

Honeywell

Honeywell V4730C User manual

Honeywell V5055A User manual

Honeywell

Honeywell V5055A User manual

Popular Control Unit manuals by other brands

ITC Elio 610-00007 Replacement instructions

ITC

ITC Elio 610-00007 Replacement instructions

bee 71MS Operating and assembly instruction

bee

bee 71MS Operating and assembly instruction

STMicroelectronics STM32 Series quick start guide

STMicroelectronics

STMicroelectronics STM32 Series quick start guide

Beck 12-8062-31 Replacement instructions

Beck

Beck 12-8062-31 Replacement instructions

Samsung MIM-H03 User & installation manual

Samsung

Samsung MIM-H03 User & installation manual

W.E.S.T. Elektronik POS-124-A-PDP Technical documentation

W.E.S.T. Elektronik

W.E.S.T. Elektronik POS-124-A-PDP Technical documentation

Allmatic ACTION Instructions for installation

Allmatic

Allmatic ACTION Instructions for installation

Libre LS6-N22S user manual

Libre

Libre LS6-N22S user manual

Toshiba GN-4030 manual

Toshiba

Toshiba GN-4030 manual

Pickering 40-297A user manual

Pickering

Pickering 40-297A user manual

Cisco Catalyst 9400 Series Installation note

Cisco

Cisco Catalyst 9400 Series Installation note

Gewiss MSX/M 250c quick start guide

Gewiss

Gewiss MSX/M 250c quick start guide

Advantech WISE-4610 Series Startup manual

Advantech

Advantech WISE-4610 Series Startup manual

LigoWave LigoPTP 3-18 Quick installation guide

LigoWave

LigoWave LigoPTP 3-18 Quick installation guide

GRAUPNER 34002 manual

GRAUPNER

GRAUPNER 34002 manual

Armstrong The Brain DRV25 manual

Armstrong

Armstrong The Brain DRV25 manual

Alpha Group Out Back Power MATE Series overview

Alpha Group

Alpha Group Out Back Power MATE Series overview

Wurth Elektronik Proteus-E Reference manual

Wurth Elektronik

Wurth Elektronik Proteus-E Reference manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.