manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. Honeywell
  6. •
  7. Control Unit
  8. •
  9. Honeywell 4219 Assembly instructions

Honeywell 4219 Assembly instructions

Other Honeywell Control Unit manuals

Honeywell 7800 SERIES User manual

Honeywell

Honeywell 7800 SERIES User manual

Honeywell RMG 213 Guide

Honeywell

Honeywell RMG 213 Guide

Honeywell LYNX TOUCH 2 Series User manual

Honeywell

Honeywell LYNX TOUCH 2 Series User manual

Honeywell IDENT-KEY Series Instruction manual

Honeywell

Honeywell IDENT-KEY Series Instruction manual

Honeywell V100P User manual

Honeywell

Honeywell V100P User manual

Honeywell Notifier FMM-1 User manual

Honeywell

Honeywell Notifier FMM-1 User manual

Honeywell Kromschroder GIK Series User manual

Honeywell

Honeywell Kromschroder GIK Series User manual

Honeywell SUPER TRADELINE VR8300A User manual

Honeywell

Honeywell SUPER TRADELINE VR8300A User manual

Honeywell Ex-Or CDH8U5 Installation and operation manual

Honeywell

Honeywell Ex-Or CDH8U5 Installation and operation manual

Honeywell Fire-Lite Alarms CRF-300-6 User manual

Honeywell

Honeywell Fire-Lite Alarms CRF-300-6 User manual

Honeywell W6215 Series Operation manual

Honeywell

Honeywell W6215 Series Operation manual

Honeywell ADEMCO 4190SN Assembly instructions

Honeywell

Honeywell ADEMCO 4190SN Assembly instructions

Honeywell SLATE User manual

Honeywell

Honeywell SLATE User manual

Honeywell 3GL User manual

Honeywell

Honeywell 3GL User manual

Honeywell PRO4200 User manual

Honeywell

Honeywell PRO4200 User manual

Honeywell S7800A User manual

Honeywell

Honeywell S7800A User manual

Honeywell SM150 User manual

Honeywell

Honeywell SM150 User manual

Honeywell KT73 User manual

Honeywell

Honeywell KT73 User manual

Honeywell 7800 SERIES User manual

Honeywell

Honeywell 7800 SERIES User manual

Honeywell D06F User manual

Honeywell

Honeywell D06F User manual

Honeywell BA295S User manual

Honeywell

Honeywell BA295S User manual

Honeywell LTE-L57V User manual

Honeywell

Honeywell LTE-L57V User manual

Honeywell EXCEL 12 W7704B1002 User manual

Honeywell

Honeywell EXCEL 12 W7704B1002 User manual

Honeywell Hometronic HB 05 User manual

Honeywell

Honeywell Hometronic HB 05 User manual

Popular Control Unit manuals by other brands

Festo Compact Performance CP-FB6-E Brief description

Festo

Festo Compact Performance CP-FB6-E Brief description

Elo TouchSystems DMS-SA19P-EXTME Quick installation guide

Elo TouchSystems

Elo TouchSystems DMS-SA19P-EXTME Quick installation guide

JS Automation MPC3034A user manual

JS Automation

JS Automation MPC3034A user manual

JAUDT SW GII 6406 Series Translation of the original operating instructions

JAUDT

JAUDT SW GII 6406 Series Translation of the original operating instructions

Spektrum Air Module System manual

Spektrum

Spektrum Air Module System manual

BOC Edwards Q Series instruction manual

BOC Edwards

BOC Edwards Q Series instruction manual

KHADAS BT Magic quick start

KHADAS

KHADAS BT Magic quick start

Etherma eNEXHO-IL Assembly and operating instructions

Etherma

Etherma eNEXHO-IL Assembly and operating instructions

PMFoundations Attenuverter Assembly guide

PMFoundations

PMFoundations Attenuverter Assembly guide

GEA VARIVENT Operating	 instruction

GEA

GEA VARIVENT Operating instruction

Walther Systemtechnik VMS-05 Assembly instructions

Walther Systemtechnik

Walther Systemtechnik VMS-05 Assembly instructions

Altronix LINQ8PD Installation and programming manual

Altronix

Altronix LINQ8PD Installation and programming manual

Eaton Powerware Series user guide

Eaton

Eaton Powerware Series user guide

WAGO 750-407/040-000 manual

WAGO

WAGO 750-407/040-000 manual

Sony CCU-590 Operation manual

Sony

Sony CCU-590 Operation manual

Graco 25D614 instructions

Graco

Graco 25D614 instructions

Task Force Tips YE-RF-900 Instructions for installation, safe operation and maintenance

Task Force Tips

Task Force Tips YE-RF-900 Instructions for installation, safe operation and maintenance

Shini SPV-U Series manual

Shini

Shini SPV-U Series manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.

4219
Wired Zone Expander Module
INSTALLATION AND SETUP GUIDE
GENERAL INFORMATION
This module adds up to eight end-of-line resistor supervised zones
to compatible control/communicators via the control’s keypad
wiring.
The module may be mounted within the control’s cabinet (if room
permits) or remotely. If mounted remotely there are provisions to
tamper protect the unit. Communication to the module is
supervised so that it cannot be disconnected from the keypad wiring
without detection by the control. If the wiring is cut a tamper
alarm or signal will result to indicate that this device (and possibly
other similarly connected devices) has become inoperative.
IMPORTANT: Some carbon monoxide detectors may not be
compatible with the Honeywell 4219 hardwire zone expanders.
When using carbon monoxide detectors in systems that support the
4219 zone expanders install the detectors only on the basic
hardwire zones of the system control panel and NOT on the zone
expanders.
INSTALLATION
1. Power should be disconnected before proceeding.
2.
Be sure to mount the 4219 before making any wire
connections.
When the module is mounted remotely holes on the back of the
module’s housing permit it to be mounted horizontally or vertically.
Wires can exit from the side or the breakout on the back of its
housing. For tamper protection attach the tamper magnet
(provided) (Figure 1) to the module inside cover. Place DIP switch
position #8 in the OFF position. Affix the connections label that
accompanies the module to the inside of the module’s cover. When
the installation is complete put the modules cover on. The magnet
attached to the cover positioned near the reed switch will cause a
tamper signal to be sent to the control if the cover is removed.
When the module is to be mounted inside the control’s cabinet
mount it horizontally to the raised tabs at the back of the cabinet.
Insert self-tapping screws (provided) in two adjacent raised tabs at
the back of the cabinet. Leave the heads projecting 1/8”. Hang the
module on the screw heads via two slotted holes on the back of the
module’s housing. When the module is installed in the control’s
cabinet it need not be tamper protected.
NOTE: For EN50131-3 compliance a tie-wrap must be secured
around the case of a remotely mounted 4219
Apply tie-wrap around the case to the right of the large zone wire
opening (4-inch case width) This is in opposition of the tamper
switch and magnet
Affix the connections label that accompanies the module to the
inside of the control’s cover.
See the control’s installation and setup guide for additional
information.
CONNECTIONS AND SETTINGS
Make protection zone connections to the module’s 12-position
terminal block TB1. Each zone that is used must have a 2K-ohm
end-of-line resistor connected across the end of its loop as shown
in Figure 2.
CE
•For CE installations ADEMCO N6361 EMI
suppression bead is required. Refer to the
N6361 installation guide for wire routing
instructions.
1. INSERT BOTTOM TABS FIRST.
2. ENGAGE TOP WITH CLIP. 4219-002-V0
Figure 1. Tamper Magnet Installation
If a zone is not programmed the resistor need not be used. The
method of programming each zone for the type of alarm and
reporting code to the central monitoring station varies with the
control to which the module is connected. Refer to the Installation
and Setup Guide for that control unit.
Set the DIP Switch to one of 31 addresses as shown in Figure 3 so
the control can identify the module and communicate with it
properly. The address to be set is determined by the particular
control to be used and the control’s installation instructions must
be consulted. As shipped the DIP Switch is set for an address of
“0”.
Zone A can be set for fast response time of 10ms to an open circuit
if desired by setting position 1 of the DIP Switch to “OFF”. As
shipped it is set to “ON” for a response time of 300ms as shown in
the table below. All other module protection zones have a nominal
response time of 300ms.
Connections to the control’s keypad wiring points can be made via
4-terminal block TB2 or the 4-pin plug (wire color connections are
the same).
SPECIFICATIONS
Physical 6-7/16”W x 4-1/4”H x 1-1/4” D (163mm
x 108mm x 32mm)
Electrical
Input Voltage: 12VDC (from control’s remote keypad
connection points)
Current:
30mA
4219
GRN
BLK
(–) GROUND
RED
(+) 12VDC
YEL
4321
ZONES ABCDFG H
TB1
TB2
4-PIN CONSOLE PLUG
CONNECTIONS
SAME
AS TB2
1
2
3
4DATA OUT
TO CONTROL
DATA IN
FROM CONTROL
TERMINATE EACH
PROGRAMMED ZONE
WITH 2K OHM
END-OF-LINE RESISTOR
(EACH ZONE'S MAX.
LOOP RESISTANCE:
300 OHMS + EOL)
5811
REED (TAMPER) SWITCH
2
E
134 6 7910 12
DIP SWITCH FOR SETTING
ADDRESS AND ZONE A RESPONSE
NOTE
FOR CE INSTALLATIONS A
N6361EMI SUPPRESSION
BEAD IS REQUIRED.
4219-SOC-V2
2 3 4 5 61
ON
7 8
Figure 2. Summary of Connections
EOLR value is 2K ohms.
UL
For UL installations, use 14-22AWG wire, and no more than one wire may be connected per terminal.
42 19 A DD R ES S SE TT IN GS 

SWITCH
NUMBER ("—" means "OFF")
0 1 2
3 4 5 6 78910 11 12 13 14 15
2
ON
—
ON — ON — ON — ON — ON — ON — ON —
3
ON ON
—
— ON ON — — ON ON — — ON ON — —
4
ON ON ON ON — — — — ON ON ON ON — — — —
5
ON ON ON ON ON ON ON ON — — — — — — — —
1 2 3 4 5
➞
OFF ON
DIP SWITCH: (WHITE AREAS DENOTE SWITCH HANDLES)
4219-001-V0
POSITIONS 2-6:
POSITION 1:
DETERMINE ZONE EXPANDER'S ADDRESS. CONSULT CONTROL'S INSTRUCTIONS
FOR ADDRESS USE. SWITCH SETTING SHOWN SET FOR ADDRESS "0".
DETERMINES ZONE A's RESPONSE TIME:
ON = NORMAL (300MS) RESPONSE, SHOWN (AS SHIPPED).
OFF = FAST (10MS) RESPONSE TO AN OPEN.
6
ON ON ON ON ON ON ON ON
6 7 8
16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31
ON — ON — ON — ON — ON — ON — ON — ON —
ON ON — — ON ON
—
— ON ON — — ON ON — —
ON ON ON ON — —
—
— ON ON ON ON — — — —
ON ON ON ON ON ON ON ON — — — — — — — —
— — — — — — — —
— — — — — —
—
—
ON ON ON ON ON ON ON ON
POSITION 7:
POSITION 8:
DIP SWITCH POSITION #7: NOT USED LEAVE ON
DIP SWITCH POSITION #8: CASE TAMPER ON = DISABLED OFF= ENABLED
NOTE: ADDRESSES 16-31 MAY NOT BE AVAILABLE; CONSULT THE HOST CONTROL PANEL
INSTALLATION INSTRUCTIONS.
Figure 3. DIP Switch Settings
SEE THE CONTROL PANEL’S INSTALLATION AND SETUP GUIDE FOR COMPLETE INFORMATION
REGARDING THE LIMITATIONS OF THE ENTIRE SECURITY SYSTEM.
Federal Communications Commission (FCC) Part 15
The user shall not make any changes or modifications to the equipment unless authorized by the Installation Instructions or User's Manual. Unauthorized changes
or modifications could void the user's authority to operate the equipment.
FCC CLASS B STATEMENT:
This equipment has been tested to FCC requirements and has been found acceptable for use. The FCC requires the following statement for your information:
This equipment generates and uses radio frequency energy and if not installed and used properly, that is, in strict accordance with the manufacturer's instructions,
may cause interference to radio and television reception. It has been type tested and found to comply with the limits for a Class B computing device in accordance
with the specifications in Part 15 of FCC Rules, which are designed to provide reasonable protection against such interference in a residential installation.
However, there is no guarantee that interference will not occur in a particular installation. If this equipment does cause interference to radio or television reception,
which can be determined by turning the equipment off and on, the user is encouraged to try to correct the interference by one or more of the following measures:
• If using an indoor antenna, have a quality outdoor antenna installed.
• Reorient the receiving antenna until interference is reduced or eliminated.
• Move the radio or television receiver away from the receiver/control.
• Move the antenna leads away from any wire runs to the receiver/control.
• Plug the receiver/control into a different outlet so that it and the radio or television receiver are on different branch circuits.
• Consult the dealer or an experienced radio/TV technician for help.
FCC/IC STATEMENT
This Class B digital apparatus complies with Canadian ICES-003.
Cet appareil numérique de la classe B est conforme à la norme NMB-003 du Canada.
This device complies with Part 15 of the FCC rules and RSS 210 of Industry Canada. Operation is subject to the following two conditions: (1) This device may not
cause harmful interference, and (2) This device must accept any interference received, including interference that may cause undesired operation.
Cet appareil est conforme à la partie 15 des règles de la FCC & de RSS 210 des Industries Canada. Son fonctionnement est soumis aux conditions suivantes: (1)
Cet appareil ne doit pas causer d' interferences nuisibles. (2) Cet appareil doit accepter toute interference reçue y compris les interferences causant une reception
indésirable.
ÊN8924V3nŠ
N8924V3 5/11 Rev. C
For the latest warranty information, please go to:
http://www.security.honeywell.com/hsc/resources/wa
2 Corporate Center Drive, Suite 100
P.O. Box 9040, Melville, NY 11747
Copyright © 2008 Honeywell International Inc.
CONTROL PANELS | ECP BUS
4219
Call 1-800-467-5875 for more information.
Description:
Addressable eight-zone expander for Honeywell
ECP bus addressable systems
Product advantages:
■Can be located anywhere along the four-wire
addressable ECP bus
■Simple DIP switch addressing to select range of
zone numbers
■Adds up to eight class B zone inputs to an ECP bus
addressable system, each with 1K end-of-line resistors
■Class B loops provide a broad, 300 ohm tolerance
■Supervised for open, shorted and normal circuit
conditions
■UL Listed for commercial burglary applications
Recommended use:
Use for commercial systems when deploying
conventional detectors in an ECP zone expandable
system
Mounting recommendations:
■On a flat surface, centrally located to monitor
up to eight zones from nearby detectors
■Locate anywhere on the ECP bus
Compatibility:
■All VISTA control panels that are compatible with
ECP bus zone expandability such as VISTA-20P
and VISTA-21iP
■Not compatible with V-Plex control panels
Product dimensions:
6.438" W x 4.25" H x 1.25" D
Power:
■Supplied by the control panel’s four-wire ECP bus:
30mA at 12VDC
■External power supply option: 30mA at 12VDC
(maximum)
Temperature:
32º F to 122º F (0º C to 50º C)
Humidity:
5-95% relative, non-condensing
Included items:
Eight 1K end-of-line resistors
Listings:
UL Listed to UL1610, UL1635, UL464, UL609,
UL365, UL1641, UL985, UL1023
13
123456789 101112 1
2
3
4GRN DATA OUT
TO CONTROL
BLK (–) GROUND
RED (+) 12V
YEL DATA IN
FROM CONTROL
4
3
2
1
TERMINATE EACH
PROGRAMMED ZONE
WITH 1000 OHM
END-OF-LINE RESISTOR
(EACH ZONE'S MAX.
LOOP RESISTANCE:
300 OHMS + E.O.L.)
ZONES: A B C D E F G H
1K
▲▲
▲▲
DIP SWITCH
FOR SETTING ADDRESS
AND ZONE A RESPONSE
REED (TAMPER) SWITCH
TAMPER JUMPER POSITION
4219 IN CABINET
(NOT TAMPERED)
4219 REMOTE
(TAMPER PROTECTED)
TB1
4219
TB2
4-PIN CONSOLE PLUG
CONNECTIONS SAME
AS TB2