L7224U OIL AND ELECTRIC BOILER ELECTRONIC AQUASTAT®CONTROLLER
3 69-1720EFS—07
New Installation
Order well assemblies separately; refer to Table 1 and
form no. 68-0040, Immersion Wells and Compression
Fittings for Temperature Controllers. Boilers usually have
tappings that allow the well to be mounted horizontally so
boiler water of average temperature can circulate freely
over the well. See Fig. 1 for mounting dimensions.
1. Turn off all power and drain the boiler, if applicable.
2. If no tapping is provided, prepare properly sized and
threaded tapping near the top of the boiler.
3. Sparingly coat the well threads with pipe dope.
NOTE: Do not attempt to tighten by using the case
as a handle.
4. Install the well in the boiler tapping and tighten
securely.
5. Refill boiler and check for water leakage.
6. Identify if installation requires vertical or horizontal
mounting.
7. Remove the well knockout, for either vertical or
horizontal mounting, by carefully prying the
knockout from the back of the case, using a
flat-bladed screw driver. Refer to Fig. 2.
8. Loosen but do not remove the well clamp screw.
9. Fit the case into the well so the clamp on the case
slides over the flange on the well.
10. Securely tighten the clamp screw.
11. Insert the sensor element into the well until it
bottoms. (If necessary, slightly bend the wire inside
the case to hold the sensor against the bottom of
the well.)
12. Turn power ON.
13. Set High Limit, Low Limit and Differentials to the
settings recommended by the boiler OEM. (See
OPERATION section, also refer to INSTALLATION
steps 6 and 7.)
Fig. 2.
Removing horizontal or vertical mounting
knockout.
IMPORTANT
Best thermal response is obtained with a well
that snugly fits the sensor. Insert the sensor until
it rests against the bottom of the well. Use a well
of correct length and bend the wiring, if neces-
sary, to hold the bulb against the bottom of the
well.
If the well is not a snug fit on the sensor, use the
heat-conductive compound (furnished with
TRADELINE®models) as follows: Fold the
plastic bag of compound lengthwise and twist it
gently. Then snip off end of bag and work the
open end of the bag all the way into the well.
Slowly pull out the bag while squeezing it firmly
to distribute compound evenly in the well. Bend
the wiring, if necessary, to hold the sensor
against the bottom of the well and to hold outer
end of the sensor in firm contact with the side of
the well. See Fig. 3. Wipe excess compound
from the outer end of the well.
Fig. 3. Position of sensor in immersion well.
Flush-Mounted Aquastat
Replacement
Turn off all power and remove the old controller. Refer to
the cover insert of the old controller to identify and tag
each external lead as it is disconnected. If the old well is
unsuitable for the new installation, remove it and replace it
with a suitable new well. If the old well is suitable, use it.
See Fig. 1 and 4 for mounting tab location.