Honeywell SPM Flex User manual

SPM Flex®Single Point
Monitor Gas Detector
Quick Start Guide
Warnings and cautions
• Operate and service the SPM Flex gas detector only as specied in this
quick start guide and the accompanying manual. Failure to do so may
impair the protection provided by the detector and may also void the
warranty.
• The battery is not eld-replaceable. Return the unit to Honeywell
Analytics if a battery replacement is necessary.
• Risk of re and burns. Do not open, crush, heat above 140ºF (60ºC), or
incinerate. Follow manufacturer’s instructions.
• Protection afforded by the SPM Flex gas detector may be impaired if it
is not used according to the manufacturer’s instructions.
• Do not operate two-way radios near the detector.
• Calibration, set-up, and test modes are intended for use by trained
personnel or service engineers only. Access to these modes can be
passcode protected.
• Follow local and site procedures when working with the SPM Flex
gas detector. If needed, ensure that the associated control panel is
inhibited in order to prevent false alarms. The following procedures
must be followed carefully and performed only by suitably trained
personnel.
• Use only accessories and parts meeting or exceeding Honeywell
Analytics’ specications.
WARNING
!
• The SPM Flex detector must be installed only by qualied professional
personnel in accordance with local codes.
• The safety of any system incorporating the SPM Flex gas detector is
the responsibility of the assembler of the system.
• Position a permanently-installed SPM Flex gas detector so that it does
not interfere with access to the dedicated circuit breaker.
• Use the supplied power adaptor/connector only. (The adaptor is rated
for indoor use only.)
• Do not leave the optics gate open. Doing so may allow pressurized
gases to escape through the tubing into the unit and then into the local
environment.
CAUTION
!
Unpacking the box
The contents of the box:
• the SPM Flex gas detector
• the handle assembly (for portable models only)
• power adaptor and cable
• shoulder strap (for portable models only)
• mounting bracket (for xed units only)
• a CD containing the Technical Manual
• this Quick Start Guide
Save the packaging to re-use for service requests.
External connections
The detector is supplied with weather-sealed connectors for power,
Ethernet, and communications (for relays or 4-20 mA). See the SPM Flex
manual if the detector is being mounted in a xed location.
Portable detectors must be charged at least four hours. (They can be used
while charging.) Honeywell Analytics recommends leaving the detector
connected to the power source/charger when not in use to keep the battery
fully charged.
Figure 1: terminals and ports
Turning the detector on and off
Figure 2: SPM Flex buttons and color LCD display
1. Verify that the rocker switch under the cover is in the on position.
(Typically, it is switched off only for transport or service.) Do not power
up the detector with a ash drive attached.
2. Press and hold the Power/Cancel button until the green LED begins
blinking. The detector will then complete the start-up sequence.
3. To turn the detector off, press and hold the Power/Cancel button for 5
seconds or select “Power Off” from the menu.
Navigation
All SPM Flex menus are navigated by the four buttons shown in Figure 2.
Pressing either of the arrows or the Accept/Select button will access the
menu from the main display screen. The arrows are used to scroll up and
down through lists of options. The Accept/Select button is used to initiate a
highlighted option. During navigation, the Power/Cancel button will cancel a
command or, when pressed for more than 3 seconds, it will exit to the main
display.
The display
Figure 3 shows the common elements of the display.
Figure 3:
Battery
indicator
Clock
Sound
on/o
Current status indicator
Concentration
indicator
Monitor mode
Indicator
Gas name
Gas concentration
Units
Bar graph
w/upper, lower
alarm limits
Status bar
SPM Flex display - In Monitor mode
In the status bar, the color of the status bar changes according to the
conditions (blue = out of Monitor mode, green = status OK, yellow = fault,
red = alarm).
See Figure 10 (over) for the detector’s menu map.
The interface consists of a color LCD, a 4-button keypad, and four color
status LEDs. The menu options are navigated using these buttons:
Interface Button Function
Up arrow Scroll up through lists of options
Down arrow Scroll down through lists of options
Accept/Select Accept a highlighted option
Power/Cancel Cancel
The four LEDs provide at-a-glance information about the current state of
the detector:
LED Description
Red solid Alarm 1
blinking Alarm 2
Green blinking The detector is active
Yellow solid Maintenance fault
blinking Instrument fault
Blue solid Connected to external power
Figure 4: Main menu Figure 5: Out of monitor mode
Figure 6: Alarm mode Figure 7: Maintenance fault
Part No. 1998M0846
Revision 1
August 2014
Opening the Chemcassette®cartridge door
Figure 8: Opening the Chemcassette cartridge door
Loading a Chemcassette®cartridge
Figure 9: Loading a Chemcassette cartridge
1. Navigate to the “Change Chemcassette” menu option.
2. Follow the on-screen instructions to install or change the cartridge.
3. Remove the paper optics card from the gate.
4. Insert the Chemcassette cartridge in the detector (it will t in only one
orientation). The take-up spindle rotates slightly to allow the cartridge
to snap into place easily.
5. Close the cover.
6. A summary of the current conguration will be displayed. Select
either to enter monitor mode or to remain out of monitor mode (i.e.,
idle).
Removing a Chemcassette®cartridge
1. Navigate to Maintenance > Open/Close gate.
2. Select “Open Gate.”
3. Remove the cartridge.
4. Select “Close Gate.”
5. Inert the optics card in the gate if the detector will be stored or
transported.
Changing the selected gas
1. While out of monitor mode, navigate to Set-up > Monitoring > Gas.
2. Select “Current gas” and pick the desired gas from the selection box
3. Select “Save.”
Entering monitor mode
From the main menu, navigate to the “Monitor Mode” option and select
“Enter monitor mode.”
1. If a Chemcassette cartridge has been installed, the detector will enter
Monitor Mode.
2. If a Chemcassette cartridge has not been installed, a user with
the necessary passcode can inititate the Chemcassette wizard.
Otherwise, the detector will not enter monitor mode.
Wiring and tubing
The SPM Flex detector has exible installation options to allow the user to
select the one most suitable for a specic application. The 4-20 mA output
is a three-wire connection that is congurable as sink, source, or isolated.
The detector is equipped with three relays.
Sample Tubing Specications
Description Maximum
Inlet
Tubing length, ft. (m) 100 (30) 66 (20) 33 (10) 0
Transport time (sec) 19 13 71
Flow rate (cc/min.) 700-1200 (flow is set and controlled per calibration)
Tubing OD, in. (mm) 0.25 (6.35)
Tubing ID, in. (mm) 0.125 (3.18)
Outlet
Tubing length, ft. (m) 100 (30)
Tubing OD, in. (mm) 0.25 (6.35)
Tubing ID, in. (mm) 0.188 (4.76)
The overall maximum load on the pump between the inlet and the exhaust should not exceed 10 inches H2O.
Use Teon Fluorinated Ethylene Polymer (FEP) tubing to ensure proper
sample transport.
NOTE
!
The SPM Flex detector is supplied with the standard Ethernet, power,
and communications connectors installed. The Ethernet connector can
be removed and provides a 1-inch conduit port which allows a direct
connection to the PCB communication terminals. Refer to the
Wiring and
tubing
section of the user manual for more information.
Attaching the shoulder strap
If the shoulder strap is to be used with a portable detector, attach its
spring clips to each of the rings on the detector’s handle.
Product label
Have questions?
Honeywell Analytics
405 Barclay Boulevard
Lincolnshire, Ilinois 60069
Tel: +1 847 955 8200
Toll free: +1 800 538 0363
Fax: +1 847 955 8208
[email protected]
Main Menu
Login/Logout
Reset Alarms & Faults
Reset all Silence
audio alarm
Monitor Mode
Enter
monitor mode
Out of
monitor mode
Change Chemcassette
Review Mode
Event
History
Gas
Settings Network Additional
Status
Output
State SoftwareTrend/Plot
Chem-
cassette
Maintenance
Inhibit
Summary
4-20 mA
Current Loop
Flow Char-
acterization
Open/Close
Gate
Update
Program
Setup
General Monitoring Latching Outputs Network Configuration
Manager
Security
Test
Power Off
Optics
Verification Simulate Force
Relay
Force
4-20 mA
Figure 10. SPM Flex menu map
Menu Map
Figure 11. SPM Flex label

Other manuals for SPM Flex

3

Other Honeywell Security Sensor manuals

Honeywell Miller User manual

Honeywell

Honeywell Miller User manual

Honeywell RAELink3 2.4GHz User manual

Honeywell

Honeywell RAELink3 2.4GHz User manual

Honeywell Gamewell FCI 2151 User manual

Honeywell

Honeywell Gamewell FCI 2151 User manual

Honeywell C7076D Operation manual

Honeywell

Honeywell C7076D Operation manual

Honeywell Miller DuraHoist Operator's manual

Honeywell

Honeywell Miller DuraHoist Operator's manual

Honeywell Midas User manual

Honeywell

Honeywell Midas User manual

Honeywell Filtrex TC844A1007 User manual

Honeywell

Honeywell Filtrex TC844A1007 User manual

Honeywell 5800CO Assembly instructions

Honeywell

Honeywell 5800CO Assembly instructions

Honeywell ESSER 784763 User manual

Honeywell

Honeywell ESSER 784763 User manual

Honeywell Connected Home CAMIR-8EZS User manual

Honeywell

Honeywell Connected Home CAMIR-8EZS User manual

Honeywell Miller Revolution Harness User manual

Honeywell

Honeywell Miller Revolution Harness User manual

Honeywell 5800COMBO User manual

Honeywell

Honeywell 5800COMBO User manual

Honeywell Ex-Or LS3043DR User manual

Honeywell

Honeywell Ex-Or LS3043DR User manual

Honeywell 1031030 User manual

Honeywell

Honeywell 1031030 User manual

Honeywell C7962B Operation manual

Honeywell

Honeywell C7962B Operation manual

Honeywell FIRE-LITE ALARMS SD365CO User manual

Honeywell

Honeywell FIRE-LITE ALARMS SD365CO User manual

Honeywell FF-SPS4 Series User manual

Honeywell

Honeywell FF-SPS4 Series User manual

Honeywell SIXCO User manual

Honeywell

Honeywell SIXCO User manual

Honeywell FS24X User manual

Honeywell

Honeywell FS24X User manual

Honeywell SN0500 Operation manual

Honeywell

Honeywell SN0500 Operation manual

Honeywell SiX Series User manual

Honeywell

Honeywell SiX Series User manual

Honeywell Purple Peeper C7012A User manual

Honeywell

Honeywell Purple Peeper C7012A User manual

Honeywell 5800PIR User manual

Honeywell

Honeywell 5800PIR User manual

Honeywell NOTIFIER IRX-751CTEM User manual

Honeywell

Honeywell NOTIFIER IRX-751CTEM User manual

Popular Security Sensor manuals by other brands

Interlogix RF-EV1012PI-K4 installation manual

Interlogix

Interlogix RF-EV1012PI-K4 installation manual

HDE V-WATCH Operating instructions manual

HDE

HDE V-WATCH Operating instructions manual

CP EBDHS-KNX Product guide

CP

CP EBDHS-KNX Product guide

AJAX LeaksProtect quick start guide

AJAX

AJAX LeaksProtect quick start guide

Cofem A30X Series Wiring diagram

Cofem

Cofem A30X Series Wiring diagram

Vive LVA1055 user manual

Vive

Vive LVA1055 user manual

Satel APD-100 quick start guide

Satel

Satel APD-100 quick start guide

Novatest ZBL-U5 Series instruction manual

Novatest

Novatest ZBL-U5 Series instruction manual

Siemens FDO421 installation instructions

Siemens

Siemens FDO421 installation instructions

SICK KTX-WB9214125A Series manual

SICK

SICK KTX-WB9214125A Series manual

Lightning Protection International Guardian System 5 installation manual

Lightning Protection International

Lightning Protection International Guardian System 5 installation manual

Online Electronics ID5000A operating manual

Online Electronics

Online Electronics ID5000A operating manual

Stanley S100 user manual

Stanley

Stanley S100 user manual

FCS PCorr+ user guide

FCS

FCS PCorr+ user guide

Apollo ORBIS ORB-OH-13003-APO Product guide

Apollo

Apollo ORBIS ORB-OH-13003-APO Product guide

Siemens Sinteso FD20 Guideline

Siemens

Siemens Sinteso FD20 Guideline

AVS OUTSPIDER PA manual

AVS

AVS OUTSPIDER PA manual

Enerlites HMOS installation instructions

Enerlites

Enerlites HMOS installation instructions

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.