manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. Honeywell
  6. •
  7. Smoke Alarm
  8. •
  9. Honeywell 5806W3 Assembly instructions

Honeywell 5806W3 Assembly instructions

General Information
Before installing detectors, please thoroughly read these installation
instructions and Guide for Proper Use of System Smoke Detectors
(A05-1003-002), which provides detailed information on detector
spacing, placement, zoning, wiring, and special applications. Copies
of this manual are available from Honeywell.
NOTICE: This manual should be left with the owner/user of
this equipment.
IMPORTANT: This detector must be tested and maintained regularly
following NFPA 72 requirements. The detector should be cleaned at
least once a year.
General Description
The 5806W3 photoelectronic smoke detector with built-in wireless
transmitter is intended for use with wireless alarm systems that
support 5800 series devices. Refer to control/communicator installation
instructions for compatibility. The 5806W3 smoke detector can be
used with any 5800 series wireless receiver/transceiver for residential
installations. For commercial installations, the 5881ENHC or
the 5883H receiver is required. The transmitter can send alarm,
tamper, maintenance (when control panels are equipped to process
maintenance signals), and battery condition messages to the system’s
receiver. The maintenance signal fully complies with the sensitivity
test requirement specified in NFPA 72, 7-2.2 and is approved by UL.
Refer to the wireless system’s instructions for the maximum number
of transmitters that can be supported.
The 5806W3 incorporates a state-of-the-art optical sensing chamber
and an advanced microprocessor. The microprocessor allows the
detector to automatically maintain proper operation at factory
calibrated detection levels, even when sensitivity is altered due to the
presence of contaminants settling into the unit’s smoke chamber. In
order for this feature to work properly, the chamber must never be
opened while power is applied to the smoke detector. This includes
cleaning, maintenance or screen replacement.
The 5806W3 contains a piezoelectric horn which generates the ANSI
S3.41 temporal pattern in an alarm condition. In alarm, a message is
also sent to the wireless control panel and the smoke detector’s zone
number is displayed at the console. The alarm message is transmitted
every 4 seconds until the smoke condition has cleared and the
detector has reset. During an alarm condition, pressing the detector’s
test switch will silence the piezoelectric horn for 5 minutes. Once
the detector has reset, a RESTORE message is transmitted to the
control panel and the transmitter’s zone number can be cleared from
the panel. The built-in Drift Compensation algorithm automatically
maintains the sensitivity of the detector. Once the detector reaches its
limit of compensation, it transmits a maintenance signal to the panel.
The mounting base installation is simplified by the incorporation of
features compatible with drywall fasteners or other methods that
provide a method for securing the detector in place.
5806W3 Photoelectronic Smoke Detector
with Built-in Wireless Transmitter
INSTALLATION AND SETUP GUIDE
I56-3022-004R
Two LEDs and a sounder on the detector provide local visual and
audible indication of the detector’s status:
Table 1: Detector LED Modes
Green LED Red LED Piezoelectric
Horn
Power Up Blinks every
5 sec
Blinks every
5 sec Off
Normal (standby) Blinks every
10 sec Off Off
Out of Sensitivity Off Blinks every
5 sec Off
Smoke Alarm Off Blinks every
1 sec Temporal Pattern
Low Battery Off Blinks every
45 sec
Chirp every 45
sec after LED
blinks for 7 days
During initial power-up, the red and green LEDs will blink
synchronously once every 5 seconds. It will take approximately 20
seconds for the detector to finish the power-up cycle (see Table 1).
After power-up has completed and the detector is functioning normally
within its listed sensitivity range, the green LED blinks once every
10 seconds. If the detector is in need of maintenance because its
sensitivity has shifted outside the listed limits, the red LED blinks
once every 5 seconds. When alarm has been activated by smoke, the
red LED blinks every 1 second. The LED indication must not be used
in place of the tests specified under Testing. If the detector senses a
low battery condition, the red LED blinks once every 45 seconds.
To measure the detector’s sensitivity, the i3 Series Model SENS-RDR
Infrared Sensitivity Reader tool (see Figure 4) should be used. Refer to
instruction manual D100-98-00 for proper use of the SENS-RDR.
Low Battery Detection
The 5806W3 is powered by a single 3-volt CR123A or DL123A Lithium
battery (included). The detector checks for a low battery at least
every 65 minutes. If a low battery is detected, the transmitter sends
a low battery message to the control panel, which beeps and displays
the detector’s zone number. In addition, the red LED of the 5806W3
will blink every 45 seconds and the test switch will be disabled. This
condition will exist for a minimum of 7 days, and then the detector’s
horn will “chirp” about every 45 seconds. Pressing the test switch
during this time will silence the chirps for 12 hours. The battery
should be replaced BEFORE the chirps begin. Be sure to replace the
battery with a fresh one.
- 1 -
Battery Installation and Replacement
To replace the battery:
1. Remove the detector from its mounting base by twisting the detector
counterclockwise. Remove the battery, and dispose properly.
2. To ensure proper power-down sequence, wait a minimum of 20
seconds before installing new battery.
3. Install a new 3-volt CR123A Lithium battery in the battery
compartment. Follow the polarity diagram inside the compartment.
4. Reinstall the smoke detector onto the mounting base by turning
the detector clockwise.
5. Test the detector as described in the TESTING SIGNAL
STRENGTH section of this manual. The green LED should blink
about once every 10 seconds to indicate normal operation. If the
battery is not installed correctly, the smoke detector will not
operate and the battery may be damaged. If the detector does not
appear to be sending a signal during any of the tests, check for
correct battery installation and for a fully charged battery.
TEST SWTICH
RED LED
GREEN LED
S0289-00
Figure 1. 5806W3 Wireless Smoke Detector
Programming
The smoke detector must be enrolled in the control panel before it can
operate in the system. The 5806W3 smoke protection zone must be
enrolled as Loop 1 and “Input Type” 3 (supervised RF).
If programmed, this smoke detector is capable of monitoring the
additional condition of Maintenance (transmitted as Loop 2). Tamper
is transmitted as Loop 4, but does not require programming. To take
advantage of the value added feature of Maintenance, you must
program each loop as a separate zone in the 5800 series wireless
compatible panel.
1. Enter the control’s Zone Programming mode.
2. Enter the zone number to be programmed.
3. Enter the applicable zone type when prompted. Program
 •Loop1(Smoke)asaFirezone(type9or16),
 •Loop2(High/LowMaintenance)asa24-Hr.Troublezone(type
19), and
NOTE: Loop 2 High/Low Maintenance is supported only on
commercial control panels such as the Vista-128FBP.
4. When prompted, enter Input Type 03 (3 on some controls)
– Supervised RF Transmitter.
5. When prompted for the serial number, transmit from the detector
by activating the tamper switch. To do this, hold the base of the
detector in one hand, and rotate the detector counter-clockwise
on the base until it snaps open. Then return to clockwise position
until the detector snaps into place.
6. When the serial number is displayed, transmit from the detector
a second time by activating the tamper switch again as described
in Step 5. The current loop number (4) will begin to flash.
7. Manually change the loop number to the desired loop number for
the zone (according to the application).
8. When programming for this zone is complete, program other
zones for the transmitter as necessary (except for Tamper Loop
4, which does not require programming).
WARNING: The fire protection zone enrolled must always be
Loop 1. Otherwise, fire annunciations will not be reported by the
control.
9. Exit Programming mode when programming is complete, and
test the detector. Refer to the Testing Section.
See the control unit’s installation instructions for further details.
Mounting
First, determine the best location for the smoke detector, one that
provides a strong wireless transmission path and proper smoke
detection.AGOOD TRANSMISSION PATH MUST BE ESTABLISHED
FROM THE PROPOSED MOUNTING LOCATION BEFORE
PERMANENTLY INSTALLING THE DETECTOR. To check, perform
the test described in the TESTING SIGNAL STRENGTH section of
this manual. Prior to mounting the detector to the mounting base,
you must “enroll” the detector’s serial number into the system (see
the PROGRAMMING section). To mount the detector, perform the
following steps:
1. Once a suitable location has been determined, install the
mounting base on the ceiling or on the wall (if local ordinances
permit). Use the two screws and anchors provided.
2. Turn the detector in a clockwise direction in the mounting base
until it clicks into place.
3. Test the detector immediately after completing the installation
(as described in the TESTING section of this manual) and refer
to the control system’s instructions for additional information
concerning the use of wireless smoke detectors.
DIRECT MOUNT HOLES
TAMPER RESISTANT TA B
(CUT OFF SMALL TAB TO ACTIVATE
TAMPER RESIST FEATURE)
TAMPER RELEASE TAB
S0290-00
Figure 2. Detector Mounting Base
S0162-01
Figure 3. Mount Detector Across Ceiling Panel Support
DO NOT attach the detector to removable ceiling
panels. Attach the detector across panel support as
shown in Figure 3.
- 2 -
Dust covers are an effective way to limit the entry of dust into the
smoke detector sensing chamber during construction. However, they
may not completely prevent airborne dust particles from entering the
detector. Therefore, it is recommended that the detectors be removed
before beginning construction or other dust producing activity. When
returning the system to service, be sure to remove the dust covers
from any detectors that were left in place during construction.
Smoke detectors are not to be used with detector guards unless the
combination has been evaluated and found suitable for that purpose.
Tamper Protection
This detector has a built-in tamper switch that will cause a CHECK
signal to be displayed at the console of the alarm system if it is
removed from its mounting base. The 5806W3 detector includes a
tamper-resistant feature that prevents removal from the mounting
base without the use of a tool. To engage the tamper-resistant feature,
cut the small plastic tab located on the mounting base (Figure 2), and
then install the detector. To remove the detector from the base once it
has been made tamper resistant, use a small screwdriver to depress
the square tamper release tab, located on the skirt of the mounting
base, and turn the detector counterclockwise.
Testing the Sensor
NOTE: Before testing, notify the central station that the smoke
detector system is undergoing maintenance, in order to prevent
unwanted alarms.
During initial power-up, do not use SENS-RDR or canned smoke to
test the detector. The SENS-RDR and canned aerosol can be used
after power-up sequence has completed. Detectors must be tested
after installation and following periodic maintenance. The 5806W3
may be tested as follows:
A. Test Switch
1. A recessed test switch is located on the detector housing (see
Figure 4).
2. Push and hold the recessed test switch for a minimum of 5
seconds. Use a small screwdriver or Allen key with maximum
diameter of 0.18 inch (the alarm panel will trigger and then the
smoke detector will go into alarm. If the tool is removed from the
recessed switch the sounder will shut off.)
If the detector is within the listed sensitivity limits, the LED on
the detector should blink once per second and the horn should
sound within 3 seconds.
POSITION SENS-RDR A T AN ANGLE ON
THE OVAL AREA OR AT THE CHAMBER
OPENING BY THE WORD “PAINT”
RECESSED
TEST
SWITCH
LED
PUSH RECESSED
SWITCH WITH A
0.18˝ MAX.
DIAMETER TOOL
S0308-00
Figure 4. Recessed Test Switch Opening and SENS-RDR Position
B. Smoke Entry Test
Hold a smoldering punk stick or cotton wick at the side of the detector
and gently blow smoke through the detector until the unit alarms.
Canned aerosol is also an acceptable method.
Smoke detection testing is recommended for verifying system
protection capability.
A detector that fails to activate with this test should first be cleaned
as outlined in this manual’s MAINTENANCE section. If the detector
still fails to activate, return for repair.
Testing Signal Strength
NOTE: Remove battery tab before installation.
This test should be performed in accordance with NFPA 72 inspection,
testing and maintenance requirements to determine a strong
communication path with the control panel.
1. Activate the wireless system’s GO/NO GO TEST mode from
the keypad.
2. Depress and hold the smoke detector’s TEST switch. If the
detector has not previously detected a low battery condition
and it is within proper sensitivity limits, the detector should
immediately transmit an alarm signal to the control panel.
The built-in horn will start to sound about 2.5 seconds after
depressing the button.
3. The wireless system’s keypad should emit at least three audible
sounds when the alarm transmission is received and will display
the transmitting detector’s zone number.
4. When the console has received the test signal, release the TEST
switch. The horn will immediately stop and a few seconds later
the detector’s zone number will clear from the console display.
5. If the console does not respond as noted, check the polarity of the
battery and be sure it is fresh. If this is an initial installation,
try moving the detector to another location that provides proper
reception. Also be sure that the detector has been “enrolled” by
the control panel (see PROGRAMMING). Then, repeat the test.
6. Turn off the system’s TEST mode from the keypad (security
code + OFF).
Testing Programmed Loops
This test should be performed before installation to ensure that all
loops intended to be used have been programmed and are operational
in the system.
1. Activate the system’s TRANSMITTER ID SNIFFER mode from
the keypad (see the control panel’s instructions). All programmed
wireless zones will be displayed, one by one, on the system
keypad. Make sure all smoke detector zones are displayed in
the sequence. (If they are not, recheck that all zones have been
properly programmed.)
2. With the detector mounted to the bracket, press the smoke
detector’s TEST switch. All zones associated with the smoke
detector should disappear from the keypad on the next display
cycle. This means that the system has received a transmission
from each loop you programmed.
3. When testing is complete, enter the Installer code + the OFF key
to exit TEST mode.
When all system testing has been completed, notify the central station
that the system is back on line.
- 3 -
Maintenance
NOTE: Before performing maintenance on the detector, notify the
proper authorities and the central station that maintenance is being
performed and the system will be temporarily out of service. Disable
the zone or system undergoing maintenance to prevent any unwanted
alarms, and follow this procedure exactly, referring to Figure 5.
1. Remove the detector housing from the base by twisting
counter-clockwise.
2. Remove the battery from the unit.
3. Wait 20 seconds. (To ensure proper power-down sequence, the
battery must be removed from detector for a minimum of 20
seconds before continuing to the next step.)
4. Remove the detector cover by turning counter-clockwise.
5. Vacuum the cover or use canned air to remove any dust or debris.
6. Remove the top half of the screen/sensing chamber by lifting
straight up (see Figure 5).
7. Vacuum or use canned air to remove any dust or particles that
are present on all chamber sections.
8. Replace the top half of the screen/sensing chamber by aligning
the arrow on the screen/sensing chamber with the arrow on the
housing. Press down firmly until the screen/sensing chamber is
fully seated.
9. Replace the detector cover by placing it over the screen/sensing
chamber and turning it clockwise until it snaps into place.
Specifications
Power Source: One 3-volt CR123A Lithium Battery (included). (Replace with Duracell DL123A, Sanyo CR123A,
Panasonic CR123A or ADEMCO 466.)
Height: 2.3 inches (58 mm)
Diameter: 5.3 inches (135 mm) with mounting base
Weight: 8.5 oz. (241 g) without battery
Operating Ambient Temperature Range: 32° to 100°F (0° to 38°C)
Operating Humidity Range: 0% to 95% Relative Humidity
Agency Listings: UL 268 – Commercial and Residential Installations
Please refer to insert for the Limitations of Fire Alarm Systems
FOR WARRANTY INFORMATION AND FOR DETAILS REGARDING THE LIMITATIONS OF THE ENTIRE ALARM SYSTEM, REFER TO THE INSTALLATION INSTRUCTIONS FOR THE
RECEIVER/CONTROL WITH WHICH THIS DEVICE IS USED.
This device complies with Part 15 of the FCC rules and RSS210 of Industry Canada. Operation is subject to the following two conditions: (1) This device may not cause harmful interference, and
(2) This device must accept any interference received, including interference that may cause undesired operation.
Unauthorized changes or modifications could void the user’s authority to operate the equipment
HW-500-000 I56-3022-004R
10. Reinstall the battery into the battery compartment noting proper
orientation. The red and green LEDs will flash once every 5
seconds for approximately 20 seconds until the power-up cycle is
complete.
11. Reinstall the detector and test (see the Testing section).
12. Notify the central station when the system is back in service.
IMPORTANT: If this procedure is not followed exactly, the
detector may indicate a maintenance trouble after the power-up
sequence is complete. If this happens, remove the battery for 20
seconds and then reinstall.
REMOVABLE
DETECTOR
COVER
SCREEN/SENSING
CHAMBER
(TOP HALF)
DETECTOR HOUSING
S0111-00
Figure 5. Removing Screen/Sensing Chamber
2 Corporate Center Drive, Melville, NY 11747
Copyright © 2008 Honeywell International Inc.
www.honeywell.com/security

Other Honeywell Smoke Alarm manuals

Honeywell SS4-A HART User manual

Honeywell

Honeywell SS4-A HART User manual

Honeywell FAAST LT User manual

Honeywell

Honeywell FAAST LT User manual

Honeywell Silent Knight SK-Duct User manual

Honeywell

Honeywell Silent Knight SK-Duct User manual

Honeywell DFS8MS User manual

Honeywell

Honeywell DFS8MS User manual

Honeywell DFS8MS User manual

Honeywell

Honeywell DFS8MS User manual

Honeywell D355PL User manual

Honeywell

Honeywell D355PL User manual

Honeywell SK-Beam User manual

Honeywell

Honeywell SK-Beam User manual

Honeywell GasAlert Extreme User manual

Honeywell

Honeywell GasAlert Extreme User manual

Honeywell Notifier NBG-12LX User manual

Honeywell

Honeywell Notifier NBG-12LX User manual

Honeywell NOTIFIER NFXI-ASD11 Quick start guide

Honeywell

Honeywell NOTIFIER NFXI-ASD11 Quick start guide

Honeywell LT-200 MI-FL20 Series User manual

Honeywell

Honeywell LT-200 MI-FL20 Series User manual

Honeywell Notifier FDU-80 User manual

Honeywell

Honeywell Notifier FDU-80 User manual

Honeywell DFS8MS User manual

Honeywell

Honeywell DFS8MS User manual

Honeywell FCI 2151 User manual

Honeywell

Honeywell FCI 2151 User manual

Honeywell TC846A1005 User manual

Honeywell

Honeywell TC846A1005 User manual

Honeywell ALL-SPEC User manual

Honeywell

Honeywell ALL-SPEC User manual

Honeywell DFO800M User manual

Honeywell

Honeywell DFO800M User manual

Honeywell SiXSMOKE-CN User manual

Honeywell

Honeywell SiXSMOKE-CN User manual

Honeywell TC842B1007 User manual

Honeywell

Honeywell TC842B1007 User manual

Honeywell Fire Sentry SS4-AUV User manual

Honeywell

Honeywell Fire Sentry SS4-AUV User manual

Honeywell Fire-Lite Alarms BEAM355A User manual

Honeywell

Honeywell Fire-Lite Alarms BEAM355A User manual

Honeywell Xtralis FAAST FLEX FLX-010 User manual

Honeywell

Honeywell Xtralis FAAST FLEX FLX-010 User manual

Honeywell DFS8MS User manual

Honeywell

Honeywell DFS8MS User manual

Honeywell TC842B1007AE User manual

Honeywell

Honeywell TC842B1007AE User manual

Popular Smoke Alarm manuals by other brands

brennenstuhl BR 5232 operating instructions

brennenstuhl

brennenstuhl BR 5232 operating instructions

Pyrotector 30-3003 instructions

Pyrotector

Pyrotector 30-3003 instructions

Universal Security Instruments MC304S manual

Universal Security Instruments

Universal Security Instruments MC304S manual

bolid DIP-34A-03 instruction manual

bolid

bolid DIP-34A-03 instruction manual

Mini Gadgets BB2Smoke10 user manual

Mini Gadgets

Mini Gadgets BB2Smoke10 user manual

FAAST XS 7100X Comprehensive user's guide

FAAST

FAAST XS 7100X Comprehensive user's guide

Firex TPCI user manual

Firex

Firex TPCI user manual

jablotron SD-280 manual

jablotron

jablotron SD-280 manual

Matelec Residential FPC-30028 Owner's operation manual

Matelec

Matelec Residential FPC-30028 Owner's operation manual

Mustang TENO Assembly instruction

Mustang

Mustang TENO Assembly instruction

brennenstuhl BR 102-F owner's manual

brennenstuhl

brennenstuhl BR 102-F owner's manual

Tanda TXC3150 Installation and operation manual

Tanda

Tanda TXC3150 Installation and operation manual

Xtralis VESDA VLS Product guide

Xtralis

Xtralis VESDA VLS Product guide

Nexa GNS-2236/RF manual

Nexa

Nexa GNS-2236/RF manual

Vanguard V5 Operator's manual

Vanguard

Vanguard V5 Operator's manual

Abus RWM165 user manual

Abus

Abus RWM165 user manual

Abus FURM30000 user manual

Abus

Abus FURM30000 user manual

Proflex CERAMIHEAT smoke monster  Pro S 25 user manual

Proflex

Proflex CERAMIHEAT smoke monster Pro S 25 user manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.