Operating instructions
D
GB
F
NL
I
E
GB-1
03251234
Translation from the German
Pressure switches for gas
DG..B, DG..U
Please read and keep in a safe place
Please read through these instructions
carefully before installing or operating. Following the
installation, pass the instructions on to the operator.
This unit must be installed and commissioned in accord-
ance with the regulations and standards in force. These
instructions can also be found at www.docuthek.com.
Explanation of symbols
• , 1 , 2 , 3 ... = Action
▷= Instruction
Liability
We will not be held liable for damage resulting from
non-observance of the instructions and non-com-
pliant use.
Safety instructions
Information that is relevant for safety is indicated in
the instructions as follows:
DANGER
Indicates potentially fatal situations.
WARNING
Indicates possible danger to life and limb.
CAUTION
Indicates possible material damage.
All interventions may only be carried out by qualified
gas technicians. Electrical interventions may only be
carried out by qualified electricians.
Conversion, spare parts
All technical changes are prohibited. Only use OEM
spare parts.
Changes to edition 11.17
The following chapters have been changed:
– Declaration of conformity
Checking the usage
Gas pressure switches DG for monitoring increasing
and decreasing gas or air pressure.
Positive pressure Negative pressure
DG..B Gas, air, flue gas –
DG..U Gas, air, flue gas Air, flue gas
This function is only guaranteed when used within the
specified limits– see page3 (Technical data). Any
other use is considered as non-compliant.
Type code
Code Description
DG Pressure switch for gas
6 – 500 Max. setting in mbar
B
U
BN
UN
For increasing positive pressure
For increasing positive/negative/
differential pressure
For decreasing positive pressure
For decreasing positive/negative/
differential pressure
GWith gold-plated contacts
-3
-4
-5
-6
-9
Electrical connection
via screw terminals
via screw terminals, IP 65
4-pin plug, without socket
4-pin plug, with socket
4-pin plug, with socket, IP 65
K2
T
T2
N
Red/green pilot LED for 24 V DC/AC
Blue pilot lamp for 230 V AC
Red/green pilot LED for 230 V AC
Blue pilot lamp for 120 V AC
Part designations
1
2
3
4
Type label
DG
CE –
2
13
D-49018 Osnabrück, Germany
Safety
1Upper housing section
with cover
2Lower housing section
3Hand wheel
4M16 cable gland
Max. inlet pressure =
withstand pressure,
mains voltage,
ambient
temperature,
enclosure:
see type label.
GB-2
D
GB
F
NL
I
E
Installation
CAUTION
Please observe the following to ensure that the DG
is not damaged during installation and operation:
– Continuous operation with gases containing
more than 0.1 %-by-vol. H2S or ozone con-
centrations exceeding 200 µg/m³ accelerate
the ageing of elastomer materials and reduce
the service life.
– Use approved sealing material only.
– Dropping the device can cause permanent dam-
age. In this event, replace the entire device and
associated modules before use.
– Check max. ambient temperature – see
page3 (Technical data).
– When using silicone tubes, only use silicone
tubes which have been sufficiently cured.
– Vapours containing silicone can adversely affect
the functioning of electrical contacts.
– Condensation or vapours containing silicone
must not be allowed to get into the housing.
At subzero temperatures malfunctions/failures
due to icing can occur.
– When installing outdoors, place the DG in a
roofed area and protect from direct sunlight
(even IP65 version). To avoid condensation, a
cover with pressure equalization element (Order
No.74923391) can be used.
– Avoid strong impact on the unit.
– In case of highly fluctuating pressures, install a
restrictor orifice (Order No.75456321).
▷Installation position as required, preferably with
vertical diaphragm. Then the switching pointpS
corresponds to the scale valueSK set on the
hand wheel. In other installation positions, the
switching pointpSwill change and no longer
correspond to the scale valueSK set on the
hand wheel. Check the switching point.
p
s
=SK p
s
=SK+0,18 mbar p
s
=SK-0,18 mba
r
▷
The DG must not be in contact with masonry.
Minimum clearance 20mm.
▷Ensure that there is sufficient installation space.
▷Ensure unobstructed view of the hand wheel.
1 Disconnect the system from the electrical power
supply.
2 Shut off the gas supply.
3 Ensure that the pipeline is clean.
2
1
3
4
1 and 2
Positive pressure (Rp ¼)
3 and 4
Negative pressure (Rp 1
/8)
Connect Seal Free
Positive pres-
sure DG..U
1 2 3 or 4
2 1 3 or 4
Negative pres-
sure DG..U
3 4 1 or 2
4 3 1 or 2
Differential pres-
sure DG..U
1or 2for higher absolute pressure.
3or 4for lower absolute pressure.
Seal the ports that are not in use.
Positive pressure
DG..B 1– –
4 If the electrical contacts in the DG could be soiled
by dirt particles in the surrounding air or in the
medium, use a filter pad (Order No.74946199)
at port3/4. On IP65 units, the filter pad is fitted
as standard, see type label.
Wiring
▷If the DG..G has switched a voltage > 24 V and a
current > 0.1 A at cos φ = 1 or > 0.05 A at cos φ =
0.6 once, the gold plating on the contacts will have
been burnt through. It can then only be operated at
this power rating or higher power rating.
▷
Pressure switch DG can be used in Zone1
(21) and2 (22) hazardous areas if an isolating
amplifier is installed upstream in the safe area
as “Ex-i”equipment pursuant to EN60079-11
(VDE0170-7):2012.
▷
DG as “simple electrical equipment” pursuant to
EN60079-11:2012 corresponds to the Tempera-
ture classT6, GroupII. The internal inductance/
capacitance is Li= 0.2μH/Ci= 8pF.
CAUTION
Please observe the following to ensure that the DG
is not damaged during operation:
– Note the switching capacity, see page 3
(Technical data).
▷
In the case of low switching capacities, such as
24V, 8mA, for example, we recommend using an
RCmodule (22Ω, 1μF) in air containing silicone or oil.
1 Disconnect the system from the electrical power
supply.
M16 x 1,5:
ø 4–10 mm
3 42
5 6 7
▷
Contacts 3and 2close when subject to increas-
ing pressure. Contacts 1and 3close when sub-
ject to falling pressure.
GB-3
D
GB
F
NL
I
E
NO
2
NC
1
COM
3
L1
COM
3
NC
1
NO
2
Adjustment
▷
The switching point is adjustable via hand wheel.
1 Disconnect the system from the electrical power
supply.
2 Detach the housing cover, see page3 (Tech-
nical data).
3 Connect an ohmmeter.
NO
2
NC
1
COM
3
COM
3
NC
1
NO
2
0
1 cm = 1 mbar
4 Set the switching point using the hand wheel.
5 Connect a pressure gauge.
NO
2
NC
1
COM
3
COM
3
NC
1
NO
2
0
1 cm = 1 mbar
6 Apply pressure. In doing so, monitor the ohm-
meter and the pressure gauge.
Type
Adjusting
range*
[mbar]
Switching
differential**
[mbar]
Max. inlet
pressure
pmax [mbar]
DG 6 0.4 – 6 0.2 – 0.3 100
DG 10 1 – 10 0.25 – 0.4 500
DG 30 2.5 – 30 0.35 – 0.9 500
DG 50 2.5 – 50 0.8 – 1.5 500
DG 150 30 – 150 3 – 5 600
DG 400 50 – 400 5 – 15 600
DG 500 100 – 500 8 – 17 600
* Adjusting tolerance = ± 15% of the scale value.
** Mean switching differential at min. and max. setting.
▷
Deviation from the switching point during test-
ing pursuant to EN1854 Gas and air pressure
switches: ±15%. For DG6: EN1854 Air pressure
switches: ± 15% or ±0.1mbar.
▷
If the DG does not trip at the desired switching
point, correct the adjusting range using the hand
wheel. Relieve the pressure and repeat the process.
Tightness test
1 Shut off the downstream gas pipeline close to
the valve.
2 Open the valve and the gas supply.
▷Check all used ports for tightness.
N2
900 mbar
max. 2 bar
< 15 min
3 4
Maintenance
In order to ensure smooth operation: check the tight-
ness and function of the DG every year, or every six
months if operated with biogas.
▷A function check can be carried out in case of
decreasing pressure control e.g. with the PIA.
▷After carrying out the maintenance work, check
for tightness, see page3 (Tightness test).
Technical data
Gas type: natural gas, town gas, LPG (gaseous),
flue gas, biogas (max. 0.1%-by-vol. H2S) and air.
Max. inlet pressure pmax = withstand pressure,
see page 3 (Adjustment). Max. test pressure
for testing the entire system: temporarily <15min-
utes 2bar.
Switching capacity:
U I (cos φ = 1) I (cos φ = 0,6)
DG
24 – 250 V AC
0.05 – 5 A 0.05 – 1 A
DG..G 5 – 250 V AC 0.01 – 5 A 0.01 – 1 A
5 – 48 V DC 0.01 – 1 A
Maximum medium and ambient temperatures:
-20 to +80°C.
Long-term use in the upper ambient temperature range
accelerates the ageing of the elastomer materials and
reduces the service life (please contact manufacturer).
Storage temperature: -20 to +40°C.
Diaphragm pressure switch, silicone-free.
Diaphragm: NBR.
Housing: glass fibre reinforced PBT plastic with
low gas release.
Lower housing section: AlSi 12.
Enclosure: IP54 or IP65. Safety class: 1.
Line diameter: 0.5 to 1.8 mm (AWG 24 to AWG13).
Line entrance: M16 x 1.5, clamping range: diam-
eters of 4 to 10mm.
Electrical connection type: screw terminals.
Max. tightening torque, see Technical Information
bulletin DG (D, GB, F) – www.docuthek.com.
Weight: 270to320g.
Safety information, see Safety manual DG
(D, GB)– www.docuthek.com.
Designed lifetime
This information on the designed lifetime is based on
using the product in accordance with these operat-
ing instructions. Once the designed lifetime has been
reached, safety-relevant products must be replaced.
Designed lifetime (based on date of manufacture) in
accordance with EN 13611, EN 1854 for pressure
switches:
GB-4
D
GB
F
NL
I
E
Contact
If you have any technical questions, please contact
your local branch office/agent. The addresses are
available on the Internet or from ElsterGmbH.
We reserve the right to make technical modifications
in the interests of progress.
Elster GmbH
Strotheweg 1, D-49504 Lotte (Büren)
Tel. +49 541 1214-0
Fax +49 541 1214-370
[email protected], www.kromschroeder.com
Medium Designed lifetime
Switching cycles Time [years]
Gas 50,000 10
Air 250,000 10
You can find further explanations in the applicable
rules and regulations and on the afecor website
(www.afecor.org). This procedure applies to heating
systems. For thermoprocessing equipment, observe
local regulations.
Accessories
See Technical Information DG (D, GB, F) –
www.docuthek.com
Logistics
Transport
Protect the unit from external forces (blows, shocks,
vibration). On receipt of the product, check that the
delivery is complete, see page 1 (Part designa-
tions). Report any transport damage immediately.
Storage
Store the product in a dry and clean place.
Storage temperature: see page 3 (Technical data).
Storage time: 6 months before using for the first
time. If stored for longer than this, the overall service
life will be reduced by the corresponding amount of
extra storage time.
Packaging
The packaging material is to be disposed of in ac-
cordance with local regulations.
Disposal
Components are to be disposed of separately in
accordance with local regulations.
Certification
Declaration of conformity
We, the manufacturer, hereby declare that the prod-
uct DG with product ID No. CE-0085AP0467 com-
plies with the requirements of the listed Directives
and Standards.
Directives: 2009/142/EC – GAD (valid until 20 April
2018), 2014/35/EU – LVD
Regulation: (EU) 2016/426 – GAR (valid from
21April 2018)
Standards: EN 13611:2015+AC:2016,
EN1854:2010
The relevant product corresponds to the tested type
sample.
The production is subject to the surveillance
procedure pursuant to Directive 2009/142/EC AnnexII
paragraph 3 (valid until 20 April 2018) and to Regula
-
tion (EU) 2016/426 AnnexIII paragraph3 (valid from
21 April 2018).
Elster GmbH
Scan of the Declaration of conformity (D, GB) – see
www.docuthek.com
SIL, PL
The pressure switches are suitable for single-channel
systems (HFT = 0) up to SIL 2/PL d, and up to SIL3/
PL e when two redundant pressure switches are
installed in a double-channel architecture (HFT = 1),
provided that the complete system complies with the
requirements of EN 61508/ISO 13849. The safety
function value which is actually achieved is derived
by taking all components into account (sensor – logic
– actuator). For this, the demand rate and structural
measures to avoid/detect nonconformity are to be
observed (e.g. redundancy, diversity, monitoring).
Characteristic values for SIL/PL: HFT = 0 (1de-
vice), HFT = 1 (2 devices), SFF > 90, DC = 0,
type A/category B, 1, 2, 3, 4, high demand mode,
CCF>65, ß ≥ 2.
PFHD= λD= x nop
=
1
MTTFd
0.1
B10d
U I B10d value
24 V DC 10 mA 6,689,477
230 V AC 4 mA
24 V DC 70 mA 4,414,062
230 V AC 20 mA
230 V AC 2 A 974,800
RoHS compliant, Eurasian Customs Union,
AGA approved
Directive on the restriction of the use of haz-
ardous substances (RoHS) in China
Scan of the Disclosure Table China RoHS2 – see
certificates at www.docuthek.com
AGA

This manual suits for next models

8

Other Honeywell Switch manuals

Honeywell 968XTP User manual

Honeywell

Honeywell 968XTP User manual

Honeywell Micro Switch 91SE Series User manual

Honeywell

Honeywell Micro Switch 91SE Series User manual

Honeywell CSS-O-A300-001 User manual

Honeywell

Honeywell CSS-O-A300-001 User manual

Honeywell MICRO SWITCH BX2 Series User manual

Honeywell

Honeywell MICRO SWITCH BX2 Series User manual

Honeywell FF-SNC User manual

Honeywell

Honeywell FF-SNC User manual

Honeywell HBT083P User manual

Honeywell

Honeywell HBT083P User manual

Honeywell VC Series User manual

Honeywell

Honeywell VC Series User manual

Honeywell RPLS740B User manual

Honeywell

Honeywell RPLS740B User manual

Honeywell DG T Series User manual

Honeywell

Honeywell DG T Series User manual

Honeywell PLS550A User manual

Honeywell

Honeywell PLS550A User manual

Honeywell PLS731B User manual

Honeywell

Honeywell PLS731B User manual

Honeywell Krom Schroder DL A Series User manual

Honeywell

Honeywell Krom Schroder DL A Series User manual

Honeywell 5869 User manual

Honeywell

Honeywell 5869 User manual

Honeywell CENTRAL HUB User manual

Honeywell

Honeywell CENTRAL HUB User manual

Honeywell GKN Series User manual

Honeywell

Honeywell GKN Series User manual

Honeywell S688A User manual

Honeywell

Honeywell S688A User manual

Honeywell Home HS9HUB User manual

Honeywell

Honeywell Home HS9HUB User manual

Honeywell IP-AK2 Operator's manual

Honeywell

Honeywell IP-AK2 Operator's manual

Honeywell Q640 User manual

Honeywell

Honeywell Q640 User manual

Honeywell GSX Series User manual

Honeywell

Honeywell GSX Series User manual

Honeywell PEHA PHC User guide

Honeywell

Honeywell PEHA PHC User guide

Honeywell DCM/SN DIFF User manual

Honeywell

Honeywell DCM/SN DIFF User manual

Honeywell EVN2000 Series Installation instructions

Honeywell

Honeywell EVN2000 Series Installation instructions

Honeywell HBADZ600 User manual

Honeywell

Honeywell HBADZ600 User manual

Popular Switch manuals by other brands

Moxa Technologies NPort 1220 user manual

Moxa Technologies

Moxa Technologies NPort 1220 user manual

ABB EDS500 Series Operating	 instruction

ABB

ABB EDS500 Series Operating instruction

USB Share USB-201 user manual

USB Share

USB Share USB-201 user manual

TP-Link TL-SL1351 installation guide

TP-Link

TP-Link TL-SL1351 installation guide

ALTENBURGER ELECTRONIC AQStation Switch manual

ALTENBURGER ELECTRONIC

ALTENBURGER ELECTRONIC AQStation Switch manual

turck TBEN-L SE-M2 Series Instructions for use

turck

turck TBEN-L SE-M2 Series Instructions for use

ANTAIRA LNX-0602 series user manual

ANTAIRA

ANTAIRA LNX-0602 series user manual

ZKTeco AP100 Series quick start guide

ZKTeco

ZKTeco AP100 Series quick start guide

ITT Industries Neo-Dyn 801P5 Installation and operation manual

ITT Industries

ITT Industries Neo-Dyn 801P5 Installation and operation manual

BRUEL & KJAER UL-0265 quick start guide

BRUEL & KJAER

BRUEL & KJAER UL-0265 quick start guide

TP-Link TL-SG1008 installation guide

TP-Link

TP-Link TL-SG1008 installation guide

GRASS VALLEY GV K-FRAME XP Installation planning guide

GRASS VALLEY

GRASS VALLEY GV K-FRAME XP Installation planning guide

CAMBRIONIX SuperSync15 user manual

CAMBRIONIX

CAMBRIONIX SuperSync15 user manual

H3C S5500-EI series Operation manual

H3C

H3C S5500-EI series Operation manual

Scion-Tech PRO-6000B Series operating instructions

Scion-Tech

Scion-Tech PRO-6000B Series operating instructions

Speaka Professional 1082615 operating instructions

Speaka Professional

Speaka Professional 1082615 operating instructions

serverLink SL-421 user manual

serverLink

serverLink SL-421 user manual

Allied Telesis AT-8100L/8POE-E Specifications

Allied Telesis

Allied Telesis AT-8100L/8POE-E Specifications

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.