MEC-18x User Manual |Code M01C230116| Jan. 16th,2023 Ver2.13 1/4
MEC-18x
1.Dimensions and Panel mounting
Installation Precautions
-The thickness of the mounting panel should be in the range from 0.8 to 2.0mm;
-Please ensure that the working environment of the controller meets the requirements in the
technical parameters before installation;
-Do not install the instrument in damp or dirty places; in fact, it is suitable for use in places with
ordinary or normal levels of pollution. Keep the area around the instrument cooling slots adequately
ventilated.
2.Wiring diagrams
3.Panel and operation
3.1 Indicator light description
-Compressor:Lights up when Compressor is working, flashes when the compressor
starts with a delay, and goes out the rest of the time;
-Defrost:Lights up when the defrost is working, and goes out the rest of the time;
-Fan:Lights up when the fan is working, and goes out the rest of the time;
-Drip:Lights up when dripping, and goes off the rest of the time;
-Set:Lights up when the shutdown temperature or other parameters are set,
and goes off the rest of the time;
-Door:Lights up when the door is open, and goes off when the door is closed;
3.2 Key function
Set button | Set
-Pressing SET button for 3s to display the value of set point;
-Switch menu and display interface;
-Press and hold the setting interface for 3 seconds to enter the recorder time setting
interface;
Up button |
-Scrolls through menu items and decreases values;
-Transfer the data from the controller to copy key;
Down button |
-Scrolls through menu items and decreases values;
-Transfer the date from the copy key to the controller;
Enter/Defrost button |
-Check the temperature of evaporator sensor ( If enabled );
-Save the parameters and exit the parameter setting interface;
-Pressing the key for 3 seconds to start manual defrost, or manually terminate
defrost/defrost drip state;
Key combination | +
-Press 5S to display “cFg”, configure the recorder parameters, clear the previously
recorded data, and start recording.
3.3 Normal operations
How to change the shutdown temperature and other parameters
Note(1):If there is no operation for more than 30 seconds, give up parameter modification
and exit parameter modification;
Note(2):If you forget your password, please call the manufacturer.
How to view the control probe temperature
When C9=1 and the control sensor is normal, press the SET button to display the
temperature of the control sensor.
MEC-18x User Manual |Code M01C230116| Jan. 16th,2023 Ver2.13 2/4
How to check the temperature of the evaporation probe
Press the
key, the evaporation probe temperature will be displayed, and the
normal display will be restored after 1 second.
Note: Only when the evaporation probe is enabled (d1=1) and the evaporation probe is
normal (no E2 fault) can you view the evaporation probe temperature, otherwise there will
be no response when you press the key.
How to manually start or stop the defrost
Press and hold the key for 3 seconds to manually start or stop the defrost.
How to set the recorder clock
In the parameter setting interface,Pressing SET button for 3s to display "Yea",
and to switch between year, month, day, hour, minute and second.
And press the SET key again to switch between parameter items and parameter
values; After pressing the SET key, if the clock has changed, modify the recorder clock
and exit the setting mode; Otherwise, the clock will not be changed.
If there is no key operation within 30 seconds, it will automatically exit the setting
interface without setting the clock.
Note:Every time you reset the recording clock and parameters, the previously recorded data
will be cleared. Please pay attention to data storage before operation.
Quickly clear and re record data
After Pressing + button for 5s to display the "cFg", and the current data of
the recorder will be cleared. At the same time, the recorder will be reconfigured
according to the current parameters, and new data recording will be started again.
Tips for USB flash disk exporting data
Insert the USB stick into the recorder and start exporting data.
During the export process, the controller displays the current progress (0~100%)
every 3 seconds, the recorder gives a short sound every 2.5 seconds, and the blue
indicator flashes.
After the data export is completed, the controller displays "OK", the recorder buzzer
sounds for a long time, and the blue indicator is always on. At this time, you can
remove the USB flash disk.
Note(1): During data export, please ensure that the main power supply is stable, and do not
pull out the U disk in advance;
Note(2): It is prohibited to export data from the USB flash disk when the main power is off.
Power failure prompt
Display: When the mains power is cut off, the controller will display and prompt once
every 6 seconds. The display temperature accuracy is adjusted to 1.
Alarm: When A13=0, the controller prohibits noise reduction;
When A13=1, press any key to silence.
4.Parameter table
Menu Functions Setting range Default Unit
St Temperature set value Upper limit~Lower limit 4 ℃/℉
Po Administrator menu Password 00~99 00 /
C1 Hysteresis value
0.5℃~9.0℃
4.0 ℃/℉
1℉~20℉
C2 Compressor start Min interval 0~60 5 min
C3 Compressor initial start Min interval 0~90 5 min
C4 Cabinet sensor calibration
-10.0℃~10.0℃
0.0 ℃/℉
-20℉~20℉
C5 Temperature set lower limit
-50℃~temperature set value
-2 ℃/℉
-58℉~temperature set value
C6 Temperature set upper limit
temperature set value~85℃
22 ℃/℉
temperature set value~185℉
Menu
Functions Setting range Default Unit
C7
Max.standby time after
finishing compressor start
Min. interval (note①)
0~90
0:Max.standby time calculation is
forbidden
0
Min
C8
Refrigeration Min. running
time
0~90
0: Refrigeration Min.running time
calculation is forbidden
0 min
C9 Condenser sensor selection 0: Disabled 1: Enabled 1 /
C10
Condenser sensor
calibration
-10.0℃~10.0℃
0.0 ℃/℉
-20℉~20℉
C11 Reserve 0~99 0 /
d1 Evaporator sensor selection 0: Disabled 1: Enabled 0 /
d2 Evaporator sensor calibration
-10.0℃~10.0℃
0.0 ℃/℉
-20℉~20℉
d3 Defrost cycle calculation
0: accumulated refrigeration time
1: natural time
1 /
d4 Defrost cycle
0~90
0: Defrost forbidden
6 hour
d5 Defrost status display
0:Display cabinet temperature
1:Display dEF during defrost and
defrost time delay, display cabinet
temperature after finishing defrost
time delay.
2:Always display dEF during defrost
and defrost dripping
3:Always display start-defrost
cabinet temperature during defrost
and defrost dripping
2 /
d6 The maximum time of defrost 1~90 25 min
d7
Defrost termination
temperature
0℃~50℃
12 ℃/℉
32℉~122℉
d8 Dripping time after defrost
0~60
0: Defrost dripping time forbidden
2 min
d9
Cabinet temperature display
time delay after defrost
0~90 10 min
d10 Time delay after defrost start
0~60
0:Defrost start time delay is
canceled
0 min
d11 Defrost type
0:Electric heating defrost
1:Hot gas defrost
0 /
F1 Fan running mode
0:Fan and compressor run or stop
synchronically
1:Fan runs continuously, stops
during defrost
2: Fan runs continuously, stops
during defrost and defrost dripping
5 /
MEC-18x User Manual |Code M01C230116| Jan. 16th,2023 Ver2.13 3/4
Menu
Functions Setting range Default Unit
F1 Fan running mode
4:Controlled by defrost sensor, fan
stops during defrost.
5:Fan runs continuously
5 /
F2
Fan initial start time delay
after electrified
0~60 4 min
F3
Fan start time delay after
defrost
0~60
0: Fan time delay canceled
2 min
F4 Fan working lowest temp.
-50℃~Fan working highest temp.
-12 ℃/℉
-58℉~Fan working highest temp.
F5 Fan working highest temp.
Fan working lowest temp.~85℃
-5 ℃/℉
Fan working lowest temp.~185℉
A1
Compressor run and stop in a
proportional time after
cabinet sensor failure
0: Cancel the mode of “Run/stop in
a proportional time”
1: Start the mode of “Run/stop in a
proportional time”
1 /
A2
Compressor stop time in
the mode of “Run/stop in a
proportional time”
1~60 5 min
A3
Compressor running time
in the mode of “Run/stop
in a proportional time”
1~60 30 min
A4 Buzzer alarm output switch
0: Buzzer output disabled
1: Buzzer output enabled
1 /
A5 Cabinet temperature lower
limit alarm value
-50℃~Cabinet temperature
upper limit alarm value
-10℃ ℃/℉
-58℉~Cabinet temperature
upper limit alarm value
A6
Cabinet temperature upper
limit alarm value
Cabinet temperature lower limit
alarm value~85℃
24℃ ℃/℉
Cabinet temperature lower limit
alarm value~185℉
A7
Cabinet over tempera
-ture alarm time delay
0~60 20 3min
A8
The initial cabinet over
temperature alarm time
delay after electrified
0~60 40 3min
A9
Over temperature ala
-rm upper deviation
1℃~30℃
10℃ ℃/℉
1℉~60℉
A10
Over temperature alarm
lower deviation
1℃~30℃
5℃ ℃/℉
1℉~60℉
A11
Over temperature alarm
mode
0: Absolute temperature point
1:set value+ over temperature
alarm deviation
0 /
A12 Power outage mute mode 0: Disabled 1: Enabled 0 /
do1 Control output of door switch
0:Door switch is canceled
1:Close fan during door open
Menu
Functions Setting range Default Unit
do1 Control output of door switch
2: Turn on the light when door
open, turn off the light when door
closed
3:Close fan and turn on the light
when door open, Turn off the light
when door closed
4: When door is open, it is the
synchronous signal input of defrost,
defrost will start.
1 /
do2
Buzzer response when door
open
0:NO
1:YES
1 /
do3
Buzzer response delay time
when opening the door
0~99 2 min
do4 Repeat alarm delay 0~99 30 min
cd1 Condenser sensor selection 0:Disabled 1:Enabled 0 /
cd2
Condenser high temperature
alarm start value
30℃~90℃
30℃ ℃/℉
86℉~194℉
cd3
Lower hysteresis of condenser
high temperature alarm
1℃~15℃
5℃ ℃/℉
2℉~30℉
adr controller address 00~127 01 /
un1 The controller area address 00~127 01 /
*u1
Celsius /Fahrenheit
selection (note②)
00:Fahrenheit 01:Celsius 01 /
*r1 Recorder selection 0: Disabled 1: Enabled 00 /
*r2
Select Chinese and English
for export file
0:Chinese
1:English
00 /
r3 Select the latest data to export
0:Export All
1-9:Export records in recent r3
months
0 /
*r4 Recording interval 1~999 2 5S
*r1n
Recorder overtemperature
alarm selection
0: Disabled 1: Enabled 1 /
*r1u
Upper limit of recorder
control temperature alarm
r1p ~ 85℃
30 ℃/℉
r1p ~ 185℉
*r1p
Lower limit of recorder
control temperature alarm
-50℃~r1u
-30 ℃/℉
-58℉~r1u
*r2n
Recorder cabinet
temperature alarm
0: Disabled 1: Enabled 1 /
*r2u
Upper limit of recorder
cabinet temperature alarm
r2p ~ 85℃
30 ℃/℉
r2p ~ 185℉
*r2p
Lower limit of recorder
cabinet temperature alarm
-50℃~r2u
-30 ℃/℉
-58℉~r2u
Note1:Please reconfirm the temperature related parameters after the temperature mode conversion!
Note2:The controller shall prevail if the parameters are subject to change without notice.
Note3:Note the parameters marked with "*". When changing these parameters, the recorder
data will be cleared. Please backup the data in advance!
MEC-18x User Manual |Code M01C230116| Jan. 16th,2023 Ver2.13 4/4
5.Err Code
Code
Description
E1 Control cabinet temperature sensor fault
E4 Cabinet temperature sensor fault
EE Recorder communication failure
FF The recording function is turned on, but the recording is not turned on
rH Cabinet temperature high temperature alarm
rL Cabinet temperature low temperature alarm
Er Copy card programming failed
EP The data format of the copy card does not match
cFg Clear the recorder data, reconfigure the recorder parameters, and start a new record
6.Technical data sheet
Material of shell: PC : light window -PC
Back shell -ABS ( Flammability rating: UL94-V0)
Water proof cover (option)-ABS (UL94-V0)
Dimensions and Panel mounting:
please check the No.1 chapter
Sizer of the connector insert:
Power supply and outputs: Screw terminal
Connector type for probe and door switch: PH-2A connector
UPS interface: XH-2A connector
Recorder interface: PH-2*2A connector
Power supply: 220VAC±10%,50/60Hz
or 110VAC±10%,50/60Hz
power consume: 5.0VA max
Display : Three-digit digital tube and symbol light
(red/white/blue optional),
Resolution: 0.1℃ or 1℉
Temperature measurement range and accuracy:
-50℃~90℃,-40℃~50℃@±1℃, others ±2℃
Input : 2 NTC probes and 1 single input ( switch door)
Outputs: Refer to the wiring diagram
Working temperature: 0℃~55℃
Storage temperature: -25℃~75℃
Relative humidity: 20%~85% (no frost)

Popular Temperature Controllers manuals by other brands

KIOUR TOUCH RSD3 quick start guide

KIOUR

KIOUR TOUCH RSD3 quick start guide

dixell XW460L Installing and operating instructions

dixell

dixell XW460L Installing and operating instructions

Sorel TDC 4 Installation and operating instructions

Sorel

Sorel TDC 4 Installation and operating instructions

Auber WS-1500EBPM operation instruction

Auber

Auber WS-1500EBPM operation instruction

Siemens Polygyr-Compact Technical instructions

Siemens

Siemens Polygyr-Compact Technical instructions

PCS VC-M-1 Installation, operation & maintenance manual

PCS

PCS VC-M-1 Installation, operation & maintenance manual

Sorel TDC 1 Installation and operating instructions

Sorel

Sorel TDC 1 Installation and operating instructions

Omron E5GN user manual

Omron

Omron E5GN user manual

Full Gauge Controls TC-960Ri LOG quick start guide

Full Gauge Controls

Full Gauge Controls TC-960Ri LOG quick start guide

Minco TI408 operating instructions

Minco

Minco TI408 operating instructions

Gira System 3000 operating instructions

Gira

Gira System 3000 operating instructions

Velux KRX 100 quick start guide

Velux

Velux KRX 100 quick start guide

Evinox ViewSmart user guide

Evinox

Evinox ViewSmart user guide

Danfoss ECL Comfort 296 installation guide

Danfoss

Danfoss ECL Comfort 296 installation guide

Diymore W1209 quick start guide

Diymore

Diymore W1209 quick start guide

Dynisco 1440 Installation and operation manual

Dynisco

Dynisco 1440 Installation and operation manual

Delta Controls RTS-20 Series Installation & Application Guide

Delta Controls

Delta Controls RTS-20 Series Installation & Application Guide

La Crosse Technology LTV-TH2 manual

La Crosse Technology

La Crosse Technology LTV-TH2 manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.