INSTALLATION, OPERATION &
MAINTENANCE DATA SHEET
Series “GZ” and “GZ…-M” Operators
P/N KIL00921506 FORM NO. K1506 R08/19ECO-3-041-19 Page 1of 4
APPLICATION
IMPORTANT NOTE
Series GZ and GZ…-M include pilot lights, pushbutton switches, illuminated pushbutton
switches, selector switches and (operator/actuator with contact block) combinations.
They are used in control stations, panels and enclosures used in areas made hazardous
due to the presence of flammable vapors, gases or combustible dusts.
Please read these instructions carefully before installing or maintaining this equipment.
When Series GZ and GZ…-M devices are to be installed in OEM equip
ment, refer to
Installation Instruction Sheet that came with the OEM
equipment for proper installation.
Sound electrical practices should be followed at all times and this data should be used
as a guide only.
UL/CSA application details:
IECEx, ATEX and INMETRO application details:
Identification:
Class I, Division 1 , Groups B, C, D
Class II, Division 1, Groups E, F, G
Identification:
II 2G Ex db IIC Gb
II 2D Ex tb IIIC Db
Class III
Certificates:
Sira 19 ATEX 1171U
Certificate:
E12379
IECEx CSA 19.0030U
Ambient temperature range:
-50°C to +60°C
Ambient temperature range:
-50°C to +60°C
Thread:
M22x1,5 (Series GZ with -M Suffix)
3/4" x 14 NPSM (Series GZ)
Thread:
M22x1,5 (GZ*-M)
3/4" x 14 NPSM (GZ*)
Required threads (Class I)
Six (6) full threads engaged (GZ*-M)
Seven (7) full threads engaged (GZ*)
Required threads (EN 60079-1)
8 mm threads engaged (GZ*-M)
Five (5) threads engaged (GZ*)
Required threads (Class II and III):
Three (3) full threads engaged
(GZ*-M and GZ*)
Required threads (EN 60079-31)
3 mm (GZ*-M)
3.7 mm (GZ*)
Ingress protection:
Type 4X
Ingress Protection:
IP66W (salt spray)
Storage temperature in original packaging
-20°C to +50°C
Storage temperature in original packaging
-20°C to +50°C
APPLICABLE STANDARDS
TECHNICAL DATA
•UL 1203 Standard for Explosion-Proof and Dust-Ignition-Proof Electrical
Equipment for use in Hazardous (Classified) Locations
•UL 50 Enclosures for Electrical Equipment
•UL 508 Standard for Industrial Control Equipment
•CSA C22.2 No. 25-1966 Enclosures for use in Class II, Groups E, F, G
Hazardous Locations
•CSA C22.2 No. 30-M1986 Explosionproof Enclosures for use in Class I
Hazardous Locations
•CSA C22.2 No. 94-M91 Special Purpose Enclosures Industrial Products
•CSA C22.2 No. 14-13 Industrial Control Equipment
•EN 60079-0:2012/A11 | IEC 60079-0:2011 6ª Ed. | NBR IEC 60079-
0:2013
•EN 60079-1:2014 | IEC 60079-1:2014 7ª Ed. | NBR IEC 60079-1:2016
•EN 60079-31:2014 | IEC 60079-31:2013 2ª Ed. | NBR IEC 60079-31:2014
The product is not intended to be used alone and the electrical apparatus or systems to
which it was incorporated require certification as a whole, when intended for use in
explosive atmospheres. The 3/4" NPSM or M22x1,5 thread joint of this product, and the
thread of the equipment to which it is being incorporated, must have a female 3/4"
NPSM or M22x1,5 thread meeting the requirements for threaded joints.
“GZ” operators are available in three bushing thread lengths; 25mm (0.94”),
40mm (1.57”) and 57mm (2.24”). Panel thicknesses beyond 2” require a spot face
to insure locknut can be installed from the inside of the enclosure.
CAUTION:Before installing, make sure you are compliant with area classifications, as
failure to do so may result in bodily injury, death and property damage. Do not attempt
installation until you are familiar with the following procedures. All installation must
comply with the applicable Electrical Code(s).
Make sure that the circuit is de-energized before starting installation or maintenance.
Verify that the installation is grounded. Failure to ground will create electrical shock
hazards, which can cause serious injury and or death.
ELECTRICAL SPECIFICATIONS
PUSHBUTTONS:
ROTARY SWITCHES:
Rated voltage
Ui 500 V
BREAKING CAPACITY
FOR AC
RATED
CURRENT 20 A
BREAKING CAPACITY
FOR DC
RATED
CURRENT 20 A
Rated current
Ith 10A
AC-3
220-240 V
3.0 kW
24 V
48 V
60 V
110 V
Breaking capacity for
AC15
Voltage
Current
380-440 V
5.5 kW
Resistive
loads
T<1ms
20 A 12 A 4.5 A 1 A
220 V
10 A
AC-15
220-240 V
5 A
380 V
7.5 A
380-440 V
4 A
500 V
5 A
AC-22A
220-240 V
20 A
Inductive
loads
T=50ms 12 A 2 A 1 A 0.4 A
Breaking capacity for
DC13
Voltage
Current
380-440 V
20 A
24 V
2.75 A
AC-23A
220-240 V
3.7 kW
60 V
1.10 A
380-440 V
7.5 kW
110 V
0.55 A
220 V
0.27 A
RATED VOLTAGE
690 V
RATED CURRENT
20 A
PILOT LIGHTS:
MAX. N° CONTACT
CHAMBERS
6
LED SOCKET
ILLUMINATED PUSHBUTTONS:
CONTACT BLOCK INFORMATION
12 V / 24 V / 120 V
240 VAC
480 VAC
Rated voltage
Ui500 V
Rated voltage: 250VAC/VDC
Rated voltage: 240VAC
Rated Voltage: 480 VAC
Rated current
Ith 6 A
Maximum power: 2.6 W
Maximum power: 2.6 W
Maximum power: 2.6 W
Contacts for AC 15
Voltage
Current
NOTE 1: To reach Pilot Light voltages, the socket and LED voltage combinations must be
according to Note 2.
250 V
6 A
Contacts for DC 13
Voltage
Current
NOTE 2:
24 VDC
3 A
LED SOCKET
Maximum Power 2.6 W
Maximum Voltage 250 V
L001
LC240
LC480
PILOT LIGHT VOLTAGE
SOCKET
LED VOLTAGE
12 VAC/VDC
L001
12 V
24 VAC/VDC
L001
24 V
120 VAC/VDC
L001
120 V
240 VAC
LC240
120 V
480 VAC
LC480
120 V
HUBBELL ELECTRICAL PRODUCTS
A Division of HUBBELL INC. (Delaware)
2112 Fenton Logistics Park Blvd
Fenton, Missouri 63026 USA
INSTALLATION, OPERATION &
MAINTENANCE DATA SHEET
Series “GZ” and “GZ…-M” Operators
P/N KIL00921506 FORM NO. K1506 R08/19ECO-3-041-19 Page 2of 4
MOUNTING INSTRUCTIONS
To install the product correctly, follow the steps below:
PUSHBUTTONS:
ROTARY SWITCHES
1.
Disconnect the contact block from the assembly by sliding the cage locking tab
clockwise.
1.
Disconnect the rotary switch from the switch assembly by sliding the cage
locking tab clockwise.
2.
Remove the nut and protective sleeve from the threaded body.
2.
Remove the nut and protective sleeve from the threaded body.
3.
Place the legend plate when used under the knob, or attach to the enclosure, if
applicable.
3.
Place the legend plate when used under the rotary knob, or attach to the
enclosure if applicable.
4.
Make sure the operator threads and surface being attached to are clean and free
of debris. Screw the pushbutton assembly into the enclosures 3/4” NPSM (GZ*)
or M22x1,5 (GZ*-M) threaded entry and torque 3 N-m to 6 N-m (27 in.-lbs. to 53
in.-lbs.). Ensure legend plate is held in place to prevent rotation, if applicable.
4.
Make sure the operator threads and surface being attached to are clean and free
of debris. Screw the pushbutton assembly into the enclosures 3/4” NPSM (GZ*)
or M22x1,5 (GZ*-M) threaded entry and torque 3 N-m to 6 N-m (27 in.-lbs. to 53
in.-lbs.).
5.
Align the rotary knob pointer to the legend plate.
5.
Install the nut onto the assembly threaded body and torque to 2 N-m (18 in.-lbs.)
with an appropriate tool.
6.
Install the nut onto the switch assembly threaded body, but do not tighten yet.
7.
Installing the rotary switch to the switch assembly:
6.
Installing the contact block to the assembly:
a.
With the cage locking tab held in the clockwise position, align the
a.
With the cage locking tab held in the clockwise position, align the assembly
channel with the locking cage ID tabs on the contact block and slide the
assembly channel with the locking cage ID tabs on the rotary switch and
slide onto the assembly.
block onto the assembly.
b.
Apply pressure to the rotary switch while rotating the knob handle until the
b.
Move the cage tab counterclockwise to lock switch in place.
splined shaft aligns and drops into place.
c.
Verify orientation of block is such that control wires and certification tag
won't be directed into flame path of cover/body.
c.
Move the cage tab counter/clockwise to lock switch in place.
d.
If the knob pointer is misaligned from the legend plate markings, the
switch assembly may need to be rotated by threading the assembly in or
out while maintaining the 27 in.-lbs. to 53 in.-lbs. (3 N-m to 6 N-m) torque
requirement.
e.
Torque nut to 18 in.-lbs. (2 N-m) with an appropriate tool.
NOTE: During the cables/wires installation, make sure that no mechanical tension is
applied to the rotary switch to avoid any damage.
After performing the connections described above, the product can be safely used,
and the ingress of protection is assured.
PILOT LIGHTS AND ILLUMINATED PUSHBUTTONS:
1.
Disconnect the contact/terminal block from the assembly by sliding the cage
locking tab clockwise.
2.
Install LED into terminal block.
3.
Remove the nut and protective sleeve from the threaded body.
4.
Place the legend plate under the knob, or attach to the enclosure.
5.
Make sure the operator threads and surface being attached to are clean and free
of debris. Apply STL thread lubricant and screw the pushbutton assembly into the
enclosures 3/4” NPSM (GZ*) or M22x1,5 (GZ*-M) threaded entry and torque to 3
N-m to 6 N-m (27 in.-lbs. to 53 in.-lbs.).
6.
Install the nut onto the assembly threaded body and torque to 2 N-m (18 in.-lbs.)
with an appropriate tool.
After performing the connections described above, the product can be safely used, and
the ingress of protection is assured.
7.
Installing the contact block to the assembly:
a.
With the cage locking tab oriented in the bottom, ensure it is slid to the left
position.
TYPICAL CONTACT POSITIONS
b.
Align the assembly channel with the locking cage ID tabs on the contact
block and slide the block onto the assembly.
c.
Move the cage tab counterclockwise to lock switch in place.
d.
Verify orientation of block is such that control wires and certification tag
won't be directed into flame path of cover/body.
After performing the connections described above, the product can be safely used,
and the ingress of protection is assured.
PILOT LIGHT
MODULE
CAGE
LED LAMP
NUT
PILOT LIGHT
CONTACT BLOCK
& LAMP HOLDER
CAGE
LED LAMP
NUT
PILOT LIGHT
PUSH BUTTON
CONTACT
BLOCK
CAGE
NUT
KNOB
ROTARY
SWITCH
CAGE
NUT
KNOB
LEGEND
LOCKED
UNLOCKED
2 POS. SELECTOR SWITCH
ONE POLE DOUBLE THROW
GZ25-2A3, GZ5-2A3,
GZL52A3
LEFT POS. RIGHT POS.
2 POS. SELECTOR SWITCH
TWO POLE DOUBLE THROW
GZ25-2A6, GZ5-2A6,
GZL52A6
LEFT POS. RIGHT POS.
3 POS. SELECTOR SWITCH
ONE POLE DOUBLE THROW w/ OFF
GZ25-3C3, GZ5-3C3, GZL53C3
LEFT POS. CNTR POS. RIGHT POS.
3 POS. SELECTOR SWITCH
TWO POLE DOUBLE THROW w/ OFF
GZ25-3C8, GZ5-3C8, GZL53C8
LEFT POS. CNTR POS. RIGHT POS.
3 POS. SELECTOR SWITCH
ONE POLE DOUBLE THROW w/o OFF
GZ25-3G3, GZ5-3G3, GZL53G3
LEFT POS. CNTR POS. RIGHT POS.
HUBBELL ELECTRICAL PRODUCTS
A Division of HUBBELL INC. (Delaware)
2112 Fenton Logistics Park Blvd
Fenton, Missouri 63026 USA
INSTALLATION, OPERATION &
MAINTENANCE DATA SHEET
Series “GZ” and “GZ…-M” Operators
P/N KIL00921506 FORM NO. K1506 R08/19ECO-3-041-19 Page 3of 4
WIRE SIZE CHART
The chart below shows the wire size for each type of devices.
IECEx and ATEX
UL
Device type
Hard wire (up to 2
wires)
Flexible cable (up to 2
wires)
Hard wire (up to 2
wires)
Flexible cable (up
to 2 wires)
Torque
Pushbuttons and lights 2.5mm21.5mm218 - 13 AWG 20 - 15 AWG
9 in.-lbs.
(1 N-m)
Selector switches 2.5mm22.5mm212 AWG 14 AWG
9 in.-lbs.
(1 N-m)
IECEx AND ATEX SPECIAL CONDITIONS FOR SAFE USE
UL/CSA CONDITIONS OF ACCEPTABILITY
•For flameproof applications, the actuators and signaling elements shall
only be installed in Ex d enclosures with maximum internal volume of
35 liters and approved for at least Group IIC according to EN60079-
1/IEC 60079-1.
•For flameproof applications, the actuators and signaling elements shall
only be installed in Ex d enclosures with maximum internal explosion
pressure of 20 bar for Group IIC according to EN60079-1/IEC 60079-1.
•The actuators and signaling elements shall only be used for a service
temperature range of -50°C to +60°C.
•For flameproof applications, the actuators and signaling elements shall
only be threaded in enclosure walls having a minimum length of 8.0
mm for M22x1,5 thread, and at least five (5) threads engaged for 3/4"
NPSM thread, according to table 4, from EN 60079-1/IEC 60079-1. The
maximum thickness of the enclosure wall is limited by size (length) of
the actuating and signal elements.
•For dustproof applications, the actuators and signaling elements shall
only be threaded in enclosure wall having a minimum length of 3,0 mm
for M22x1,5 or 3,7 mm for 3/4"NPSM thread, and at least threads
engaged according to EN 60079-31/IEC 60079-31. The maximum
thickness of the enclosures wall is limited by size (length) of the
actuating and signal elements. The elements have to be fixed in the
electrical equipment in such a way that rotation and accidental
loosening will be prevented.
•For the pilot light and illuminated buttons, the maximum load for LED is
2 W.
•The outer molding of the elements has to be tightened according
manufacturer's instructions.
•For flameproof applications, the actuators and signalling elements shall
only be installed in Ex d enclosures with maximum internal volume of
160 litres and approved for at most Group IIB+H2, according to
EN60079-1/IEC 60079-1.
•For flameproof applications, the actuators and signaling elements shall
only be installed in Ex d enclosures with maximum internal volume of
35 liters and approved for at least Group IIC, according to EN60079-
1/IEC 60079-1
•
The flameproof joints are not intended to be repaired.
•Open type devices should be mounted through covers / walls of
enclosures having adequate strength and thickness in the
intended manner. The manufacturer’s instructions must be
followed.
•
The devices have been assessed for use in a service
temperature range of -50°C to +60°C.
•With regards to Unclassified Location
assessment, gasket
temperatures must not exceed 70°C.
•All dead-metal parts shall be grounded or shall contact grounded
metal parts in the final assembly.
•
The threaded joint located between the auxiliary device body
and the end equipment enclosure shall consist of at least six (6)
full threads of engagement for M22x1,5 and at least seven (7)
full threads of engagement for 3/4"NPSM for Class I Group B
locations, 5 full threads for Class I, Groups C&D,
and 3 full
threads of engagement for Class II and III locations.
•
These devices were only evaluated relevant to their installation
through covers / walls of enclosures with a free volume up to 160
dm3with a maximum internal
explosion pressure of 20 bar (290 psi), all requirements from the
relevant standards must be considered in the end application.
•
The devices were evaluated for ingress protection when installed
in an enclosure
wall/cover, and it is known to be Type 4X. When
installed on enclosure walls/covers, and the enclosure is also
rated Type 4X, it is known to maintain the
enclosure ingress
protection.
•
Metric threads shall have a tolerance Class of 6g/6H or better
according to
Standard for General Purpose Metric Screw
Threads - Tolerances - Part 1, ISO 965-1 and the Standard for
General Purpose Metric Screw Threads - Tolerances - Part 3,
ISO 965-3.
•The maximum load for LED is 2 W.
STORAGE
IMPORTANT:
Upon receiving the product, the parts must stored in a covered, clean and
dry place so that there is no contact between threads of the products.
Technical information, advice and recommendations contained in these
documents is based upon information that Killark believes to be reliable.
All the information and advice contained in these documents is intended for
use only by persons having been trained and possessing the requisite skill
and know-how and to be used by such persons only at their own discretion
and risk.
The nature of these instructions is informative only and does not cover all of
the details, variations or combinations in which this equipment may be used,
its storage, delivery, installation, check out, safe operation and maintenance.
Since conditions of use of the product are outside of the care, custody and
control of Killark, the purchaser should determine the suitability of the
product for his intended use and assumes all risk and liability whatsoever in
connection therewith.
INSPECTION AND MAINTENANCE
Inspection and maintenance must be performed in accordance with the
applicable codes of practice by an appropriately trained person.
REPAIR
A properly trained person shall perform the repair of equipment in
accordance with the manufacturer's instructions and applicable codes of
practice. Repair/modification must be performed only with manufacturer
original parts and should be limited to the replacement of the following
parts:
•Gasket
•Contact blocks
•Power supply module for pilot light
•Color calotte for signaling
HUBBELL ELECTRICAL PRODUCTS
A Division of HUBBELL INC. (Delaware)
2112 Fenton Logistics Park Blvd
Fenton, Missouri 63026 USA
INSTALLATION, OPERATION &
MAINTENANCE DATA SHEET
Series “GZ” and “GZ…-M” Operators
P/N KIL00921506 FORM NO. K1506 R08/19ECO-3-041-19 Page 4of 4
ATTESTATION OF CONFORMITY
Manufacturer : Killark Electric , Div of Hubbell Inc.(Delaware),
2112 Fenton Logistics Park Blvd , Fenton, MO 63026, USA
Tel : (314) 531-0460 | Email: killarkinfo@hubbell.com
Declares in its sole responsibility that the product mentioned below
Product Designation : Series GZ Actuators, Actuator Assemblies,Pilot Lights,
and Potentiometers;
Series EXH Circuit Breaker Operators
Type Designation : Flameproof and Dust Ignition-proof Actuators and
Signal Elements
is in conformity with the essential protection requirements of the following Directive(s),Certification
Scheme(s) and Standard(s).
Directive(s) / Scheme(s) Standard(s)
2014/34/EU ATEX Directive
EN 60079-0:2012+A11:2013
EN 60079-1:2014
EN 60079-31:2014
IEC Certification Scheme For Explosive
Atmospheres
IEC 60079-0:2011, Ed. 6.0
IEC 60079-1:2014-06, Ed. 7.0
IEC 60079-31:2013, Ed. 2.0
Others EN 60529:1991+A1:2000+A2:2013
Type Examination Certificate
ATEX
IECEx
SIRA 19ATEX1171U Issue No. 0 IECEx CSA 19.0030U Issue No. 0
Certification Body
ATEX
IECEx
Sira Certification Service (Reg No.: 0518)
Unit 6 Hawarden Industrial Park
Hawarden, CH5 3US, United Kingdom
Sira Certification Service
Unit 6 Hawarden Industrial Park
Hawarden, CH5 3US, United Kingdom
Marking: (Note 1)
ATEX
IECEx
II 2G Ex db IIC Gb (up to 35 Liters) Ex db IIC Gb (up to 35 Liters)
0518 II 2G Ex db IIB+H2 Gb (up to 160 Liters) Ex db IIB+H2 Gb (up to 160 Liters)
II 2D Ex tb IIIC Db IP66 (Salt Spray) Ex tb IIIC Db IP66 (Salt Spray)
Tservice= -500C to +600C Tservice = -500C to +600C
Note 1: Rating data,characteristics and for incorporation into equipment refer Installation & operating manual.
PQAN compliance has been approved by Notified Body Sira Certification Services Limited (A CSA Group
company), Unit 6, Hawarden Industrial Park, Hawarden, Deeside, CH5 3US England (Notified Body 0518).
To verify the status and authencity of IECEx Certificate of Conformity, please visit Official IECEx Website
Signature :
Place and Date : Fenton, 2019-08-05
Name :
Tom Michalski
Designation :
Certifications Manager

This manual suits for next models

1

Other Hubbel Lighting Equipment manuals

Hubbel DUAL LITE Spectron User manual

Hubbel

Hubbel DUAL LITE Spectron User manual

Hubbel KIM LIGHTING LIGHTVAULT LTV50 Series User manual

Hubbel

Hubbel KIM LIGHTING LIGHTVAULT LTV50 Series User manual

Popular Lighting Equipment manuals by other brands

Feniex WIDE LUX A-4600 instruction manual

Feniex

Feniex WIDE LUX A-4600 instruction manual

Hatco NLX Series Installation and operating manual

Hatco

Hatco NLX Series Installation and operating manual

fomex HD150 user manual

fomex

fomex HD150 user manual

Daisy Below Ground Pool Cover Box installation instructions

Daisy

Daisy Below Ground Pool Cover Box installation instructions

Sengled element Z01-hub user manual

Sengled

Sengled element Z01-hub user manual

NENKO 42200952 manual

NENKO

NENKO 42200952 manual

Francis A6172 User instruction & installation manual

Francis

Francis A6172 User instruction & installation manual

Vision & Control LDLF60x540-B470/UDC Instructions for use

Vision & Control

Vision & Control LDLF60x540-B470/UDC Instructions for use

XanLite SO300B instructions

XanLite

XanLite SO300B instructions

Vision & Control LDLF60x480-G525/24V Instructions for use

Vision & Control

Vision & Control LDLF60x480-G525/24V Instructions for use

Alkalite Tracpod 30 installation guide

Alkalite

Alkalite Tracpod 30 installation guide

Kichler Lighting 16022 instructions

Kichler Lighting

Kichler Lighting 16022 instructions

Gama Sonic GS-80 instruction manual

Gama Sonic

Gama Sonic GS-80 instruction manual

Slot.it SP44 manual

Slot.it

Slot.it SP44 manual

Ledj Libretto Mini WW Profile user manual

Ledj

Ledj Libretto Mini WW Profile user manual

Cooper HALO HC8R installation instructions

Cooper

Cooper HALO HC8R installation instructions

Sumitomo TYPE-Q102-CA + Quick reference guide

Sumitomo

Sumitomo TYPE-Q102-CA + Quick reference guide

SGM Hazer 400 quick start guide

SGM

SGM Hazer 400 quick start guide

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.