
3-4 startup / opEratIon
P/N 3018126_E U.S. & Canada 1-800-922-1919 • Mexico 1-800-890-2900 • www.hussmann.com
P/N 3018126_E 3-5
HUSSMANN CORPORATION • BRIDGETON, MO 63044-2483 U.S.A. SMG8B & SSG8B
Controller Parameters
XR 75 Parameter XR 75 Function
SEt Temperature Setpoint LS to US -5 17 19
(0.1 to 25.5°C / 1 to 255°F)Intervention differential for setpoint. Compressor
Cut IN is setpoint + differential (Hy).Compressor Cut OUT is when the
temperature reaches the setpoint.
LS Minimum setpoint (-100°C to SEt/-148°F to SEt)Sets the minimum value for the setpoint. -50 10 12
US Maximum setpoint (SEt to 110°C/ SEt to 230°F)Set the maximum value for the setpoint. 110 33 26
ot Thermostat probe calibration
(-12.0 to 12.0°C; -120 to 120°F)Allows to adjust possible offset of the
thermostat probe.
P2P Evaporator probe presence
n = not present: the defrost stops by time y = present: the defrost stops
by temperature
oE Evaporator probe calibration
(-12.0 to 12.0°C; -120 to 120°F)Allows to adjust possible offset of the
evaporator probe.
P3P Third probe presence (P3)
n = not present; the terminals 18-20 operate as digital input y = present;
the terminals 18-20 operate as third probe
o3 Third probe calibration (P3)
(-12.0 to 12.0°C; -120 to 120°F) Allows to adjust possible offset of the third
probe.
P4P Fourth probe presence (n = not present; y = present) n n n
o4 Fourth probe calibration (-12.0 to 12.0°C) Allows to adjust possible offset of the fourth probe. 0 0 0
Ods Outputs activation delay at startup
(0 to 255 min) This function is enabled at the initial start up of the device
and inhibits any output acti-vation for the period of time set in the
Ac Anti-short cycle delay
(0 to 50 min) Minimum interval between the compressor stop and the
following restart.
Percentage of the second andfirst
probe for regulation (0 to100; 100
Allows to set the regulation according to the percentage of the first and
second probe,as for the following formula (rtr(P1-P2)/100 + P2).
Compressor ON time during
(0.0 to 24.0 hr; res. 10 min)Allows to set the length of the continuous cycle:
compressor stays ON without interruption for the CCt time. Can be used, for
instance, when the room is filled with new products.
CCS Setpoint for continuous cycle (-100 to 150°C)Sets the setpoint used during the continuous cycle. -5 17 19
Compressor ON time with faulty
probe
(0 to 255 min)Time during which the compressor is active in case of faulty
thermostat probe. WithCon = 0, compressor is always OFF.
Compressor OFF time with faulty
probe
(0 to 255 min)Time during which the compressor is OFF in case of faulty
thermostat probe. When CoF= 0, compressor is always active.
CF Temperature measurement unit
°C = Celsius, °F = Fahrenheit, (CAUTION! When the measurement unit is
changed, the setpoint and the values of the parameters Hy, LS, US, ot, ALU
and ALL have to be checked and modified if necessary).
rES Resolution (for °C) (in = 1°C; dE = 0.1°C) Allows decimal point display. dE dE dE
(P1; P2, P3, P4, SEt, dtr) Selects which probe is displayed by the device: P1 =
Thermostat probe P2 = Evaporator probe; P3 = Third probe (only for models
with this option enabled), P4 = Fourth probe, SEt= setpoint, dtr =
percentage of visualization
Red X- REP display (optional)
(P1; P2, P3, P4, SEt, dtr) Selects which probe is displayed by the device: P1 =
Thermostat probe P2 = Evaporator probe; P3 = Third probe (only for models
with this option enabled), P4 = Fourth probe, SEt= setpoint, dtr =
percentage of visualization
(0 to 20.0 min; resul. 10 seconds) When the temperature increases, the
display is updated of 1°C/1°F after this time.
Percentage of the second and first
probe for visualization when Lod =
dtr (0 to 100; 100 = P1, 0 = P2 )
If Lod = dtr, it allows to set the visualization according to the percentage of
the first and second probe, as for the following formula (dtr(P1-P2)/100 + P2).
Defrost mode (only for controller
rtC = Real Time Clock mode. Defrost time follows Ld1 to Ld6 parameters on
workdays and Sd1 to Sd6 on holidays. in = interval mode. The defrost starts
when the time Idf is expired.
tdF Defrost type EL = electrical heater in = hot gas EL EL EL
Probe selection for defrost
termination
nP = no probe P1 = thermostat probe P2 = evaporator probe P3 =
configurable probe P4 = probe on Hot Key plug
dtE Defrost termination temperature
(-50 to 50°C/ -58 to 122°F) (Enabled only when EdF = Pb) Sets the temperature
measured by the evaporator probe, which causes the end of defrost.
IdF Interval between defrost cycles
(0 to 120 hr) Determines the time interval between the beginning of two
defrost cycles.
MdF (Maximum) length for defrost
(0 to 255 min) When P2P = n, (not evaporator probe: timed defrost) it sets
the defrost duration, when P2P = y (defrost end based on temperature) it sets
the maximum length for defrost.
(0 to 99 min) This is useful when different defrost start times are necessary
to avoid overloading the plant.
Temperature displayed during
defrost
(rt = real temperature; it = temperature at defrost start; SEt = setpoint; dEF =
dEF la-bel)
dAd MAX display delay after de-frost
(0 to 255 min)Sets the maximum time between the end of defrost and the
restarting of the real roomtemperature display.
(0 to 120 min)Time interval between reaching defrost termination
temperature and the restoring of thecontrollers normal operation. This time
allows the evaporator to eliminate water drops that might have formed due
dPo First defrost after start-up (y = immediately; n = after the IdF time) n y y
dAF Defrost delay after continuouscycle
(0 to 23.5 hr)Time interval between the end of the fast freezing cycle and the
following defrost relatedto it.
C-n = runs with the compressor, OFF during defrost O-n = continuous mode,
OFF during defrost C-y = runs with the compressor, ON during defrost
O-y = continuous mode, ON during defrost
Fnd Fans delay after defrost (0 to 255 min) Interval between end of defrost and evaporator fans start 10 0 0
Temperature differential avoiding
(0 to 59°C; FCt = 0 function disabled) If the difference in temperature
between the evaporator and the room probes is morethan the value of the
FCt parameter, the fans are switched ON.
FSt Fans stop temperature
(-50 to 50°C/ 122°F) Setting of temperature, detected by the evaporator
probe, above which fans are always OFF.
(0 to 15 min) With Fnc=C_n or C_y, (fan activated in parallel with
compressor). Sets the evaporator fan ON cycling time when the compressor is
OFF. When Fon=0 and FoF not equal to 0, the fans are always OFF, with
Fon=0 and FoF=0, the fans are always OFF.
(0 to 15 min)With Fnc=C_n or C_y, (fan activated in parallel with compressor).
Sets the evaporator fan OFF cycling time when the compressor is OFF. When
Fon=0 and FoF not equal to 0, the fans are always OFF, when Fon=0 and
FoF=0, the fans are always OFF.
Probe selection for fan
management
nP = no probe P1 = thermostat probe P2 = evaporator probe P3 =
configurable probe P4 = probe on Hot Key plug
Kind of regulation for auxiliary
relay
Ht = heating CL = cooling CL CL CL
SAA Setpoint for auxiliary relay
(-100 to 150.0°C; -148 to 302°F) Defines the room temperature setpoint to
switch auxiliary relay.
SHy Differential for auxiliary output
(0.1 to 25.5°C/ 1 to 255°F)Intervention differential for auxiliary output
setpoint. When ACH = CL, AUX Cut in is SAA + SHy; AUX Cut out is SAA
When ACH = Ht , AUX Cut in is SAA - SHy; AUX Cut out is SAA
ArP Probe selection for auxiliary
nP = no probe, the auxiliary relay is switched only by the digital input P1 =
Probe 1 (thermostat probe) P2 = Probe 2 (evaporator probe) P3 =
Probe 3 (display probe) P4 = Probe 4
Sdd Auxiliary relay OFF during defrost
n = the auxiliary relay operates during defrost y = the auxiliary relay is
switched OFF during defrost
ALP Probe selection for alarm
nP = no probe, the temperature alarms are disabled P1 = Probe 1
(thermostat probe) P2 = Probe 2 (evaporator probe) P3 = Probe 3 (display
probe) P4 = Fourth probe
ALC Temperature alarms configuration
(Ab; rE) Ab = absolute temperature: alarm temperature is given by the ALL or
ALU values. rE= temperature alarms are referred to the setpoint.
Temperature alarm is enabled whenthe temperature exceeds the SEt + ALU or
SEt - ALL values.
ALU Maximum temperature alarm
(SEt to 150°C; SEt to 302°F)When this temperature is reached, the alarm is
enabled, after the ALd delay time.
ALL Minimum temperature alarm
(-100 to SEt; -148°C to 230°F)When this temperature is reached, the alarm is
enabled, after the ALd delay time.
Differential for temperature alarm
(0.1 to 25.5°C; 1 to 45°F) Intervention differential for recovery of
temperature alarm. It is also used for the restartof the fan when the FSt
ALd Temperature alarm delay
(0 to 255 min) Time interval between the detection of an alarm condition
and alarm signaling.
Exclusion of temperature alarmat
(from 0.0 min to 23.5 hr)Time interval between the detection of the
temperature alarm condition after devicepower ON and alarm signaling.
Probe selection for temperature
alarm of condenser
nP = no probe P1 = thermostat probe P2 = evaporator probe P3 =
configurable probe P4 = probe on Hot Key plug
Low temperature alarm of
condenser
(-100 to 150°C) When this temperature is reached, the LA2 alarm is signaled,
possibly after the Ad2 delay.
High temperature alarm of
condenser
(-100 to 150°C)When this temperature is reached, the HA2 alarm is signaled,
possibly after the Ad2 delay.
Differential for temperature
condenser alarm recovery
(0.1 to 25.5°C; 1 to 45°F) 552 52
Condenser temperature alarm
delay
(0 to 255 min)Time interval between the detection of the condenser alarm
condition and alarm signaling.
Condenser temperature alarm
exclusion at start up
(from 0.0 min to 23.5 hr, res. 10 min) 1.3 1.3 1.3
temperature alarm of condenser
n = no: compressor keeps on working Y = yes, compressor is switched OFF
until the alarm is present, in any case regulation restarts after Ac time at
Compressor OFF with high
temperature alarm of condenser
n = no: compressor keeps on working Y = yes, compressor is switched OFF
until the alarm is present, in any case regulation restarts after Ac time at
Alarm relay silencing (with
n= silencing disabled: alarm relay stays ON until alarm condition lasts y
=silencing enabled: alarm relay is switched OFF by pressing a key during an
oA3 Fourth relay configuration (1-4)
dEF, FAn: do not select it! ALr: alarm; Lig: light; AUS: Auxiliary relay; onF:
alwaysON with device ON; db= neutral zone; cP2 = do not select it!; dEF2: do
not select it!; HES: night blind
Set if the alarm relay is open or closed when an alarm happens. CL=
terminals 1-4 closed during an alarm oP = terminals 1-4 open during an
i1P Digital input polarity (18-20)
oP = the digital input is activated by opening the contact CL = the digital
input is activated by closing the contact
i1F Digital input configuration (18-20) dor = door switch functiondEF = activation of a defrost cycle dor dor dor
i2P 2nd digital input polarity (18-19)
oP = the digital input is activated by opening the contact CL = the digital
input is activated by closing the contact
2nd digital input configuration(18-
EAL= external alarm: "EA" message is displayed bAL= serious alarm "CA"
message is displayed PAL= pressure switch alarm, "CA"
dor = door switch function dEF= activation of a defrost cycle ES = energy
saving AUS = auxiliary relay activation with oA3 = AUS Htr = kind of action
inversion (cooling - heating) FAn = fan HdF = Holiday defrost (enable only
with RTC) onF = to switch the controller OFF
(0 to 255 min) with i2F= EAL or i2F
= bAL digital input alarm delay (18-
Delay between the detection of the external alarm condition and its signaling.
When i2F= PAL: time for pressure switch function: time interval to calculate
the number of the pressure switch activation.
doA Door open signaling delay (0 to 255 min) 15 15 15
nPS Pressure switch number
(0 to 15) Number of activation of the pressure switch, during the did interval,
before signaling the alarm event (i2F = PAL). If the nPS activation in the did
time is reached, switch OFF and ON the device to restart normal regulation.
Odc
Compressor status when open
door
no = normal Fan = fan OFF CPr = compressor OFF F_C = compressor and
fan OFF
rrd Outputs restart after doA alarm
no = outputs not affected by the doA alarm yES = outputs restart with the
doA alarm
Temperature increase during the
Energy Saving cycle
(-30.0°C to 30.0°C) Sets the increasing value of the setpoint during the Energy
Saving cycle.
Adr Serial address (1 to 244)
Identifies the device address when connected to a MODBUS compatible
monitoring system.
Allows to set the kind of probe used by the device: Pt1 = Pt1000 probe ntc
= NTC probe
onF ON/OFF key enabling not used = disabled oFF = enabled ES = not set it
dP1 Thermostat probe display
dP2 Evaporator probe display
dP3 Third probe display - optional
Shows the setpoint used during the energy saving cycle or during the
continuous cycle.
rEL Software release For internal use only
Ptb Parameter table code Read-only
CONDENSER TEMPERATURE ALARM
AUXILIARY THERMOSTAT CONFIGURATION (terms. 1-4) - oA3 = AUS