ICT PRT-CTRL-DIN-IP User manual

PRT-CTRL-DIN-IP / PRT-CTRL-DIN
Protege GX DIN Rail Integrated System
Controller
Installation Manual

The specifications and descriptions of products and services contained in this document were correct at the time
of printing. Integrated Control Technology Limited reserves the right to change specifications or withdraw
products without notice. No part of this document may be reproduced, photocopied, or transmitted in any form or
by any means (electronic or mechanical), for any purpose, without the express written permission of Integrated
Control Technology Limited. Designed and manufactured by Integrated Control Technology Limited, Protege® and
the Protege® Logo are registered trademarks of Integrated Control Technology Limited. All other brand or product
names are trademarks or registered trademarks of their respective holders.
Copyright © Integrated Control Technology Limited 2003-2022. All rights reserved.
Last Published: 04-Jul-22 11:34 AM
PRT-CTRL-DIN | Protege GX DIN Rail Integrated System Controller | Installation Manual 2

Contents
Introduction 6
About This Module 6
Controller Editions 6
Installation Requirements 7
Wiring 7
Grounding Requirements 8
Safety Grounding 8
Earth Ground Connection 8
Mounting 10
Removal 10
Wiring Diagram: PRT-CTRL-DIN 11
Wiring Diagram: PRT-CTRL-DIN-IP 12
Connections 13
Power Requirements 13
Auxiliary Outputs 15
Encrypted Module Network 15
Module Wiring 15
End of Line (EOL) Resistors 16
Telephone Dialer 17
Cellular Modem 17
Ethernet 10/100 Network Interface 18
Door Access Control 19
RS-485 Reader Locations 19
RS-485 Reader Connection (Entry Only) 20
RS-485 Reader Connection (Entry/Exit) 20
Wiegand Reader Connection 21
Multiple Wiegand Reader Connection 21
Magnetic Reader Connection 22
Door Contact Connection 22
Lock Output Connection 23
Programming the Onboard Reader 24
Inputs 26
EOL Resistor Value Options 27
Duplex Inputs 27
PRT-CTRL-DIN | Protege GX DIN Rail Integrated System Controller | Installation Manual 3

Trouble Inputs 28
Outputs 31
Bell/Siren Output 31
Relay Outputs 32
Reader Outputs 32
Hardware Configuration 33
Configuring a Controller via the Web Interface 33
Setting the IP Address from a Keypad 33
Temporarily Defaulting the IP Address 34
Defaulting a Controller 35
LED Indicators 37
Power Indicator 37
Status Indicator 37
Fault Indicator 37
Ethernet Link Indicator 37
Modem Indicator 38
Reader Data Indicators 38
Bell Indicator 38
Relay Indicators 38
Input Indicators 39
Mechanical Diagram: PRT-CTRL-DIN 40
Mechanical Diagram: PRT-CTRL-DIN-IP 41
Mechanical Layout 42
Technical Specifications 43
Current and Validation Example 45
New Zealand and Australia 46
Intruder Detection Maintenance Routine 46
Peripheral Devices 46
Testing Frequency 46
Recommended Routine Maintenance Procedures 47
European Standards 50
UK Conformity Assessment Mark 52
UK PD 6662:2017 and BS 8243 52
UL and ULC Installation Requirements 53
UL/ULC Installation Cabinet Options 53
Central Station Signal Receiver Compatibility List 53
PRT-CTRL-DIN | Protege GX DIN Rail Integrated System Controller | Installation Manual 4

UL Operation Mode 54
ULC Compliance Requirements 54
CAN/ULC-S304 54
CAN/ULC-S319 57
CAN/ULC-S559 57
UL Compliance Requirements 62
UL1610 62
UL294 64
FCC Compliance Statements 65
Industry Canada Statement 68
Disclaimer and Warranty 69
PRT-CTRL-DIN | Protege GX DIN Rail Integrated System Controller | Installation Manual 5

Introduction
This installation manual provides instructions and technical specifications for physical installation of the Protege
GX DIN Rail Integrated System Controller. For system communication and programming information, see the
Protege GX Integrated System Controller Configuration Guide, available from the ICT website.
About This Module
The Protege GX DIN Rail Integrated System Controller is the central processing unit responsible for the control of
security, access control and building automation in the Protege GX system. It communicates with all system
modules, stores all configuration and transaction information, processes all system communication, and reports
alarms and system activity to a monitoring station or remote computer.
Protege GX is an enterprise level integrated access control, intrusion detection and building automation solution
with a feature set that is easy to operate, simple to integrate and effortless to extend.
Flexible module network architecture allows large numbers of modules to be connected to the RS-485 module
network. Up to 250 modules can be connected to the Protege system in any combination to the network, over a
distance of up to 900M (3000ft). Further span can be achieved with the use of a network repeater module.
The current features of the controller include:
⦁Internal industry standard 10/100 ethernet
⦁32 Bit advanced RISC processor with 2Gb total memory
⦁Encrypted module network using RS-485 communication
⦁NIST Certified AES 128, 192 and 256 Bit Encryption
⦁Factory loaded HTTPScertificate
⦁OSDPconfigurable RS-485
⦁8 high security monitored inputs
⦁4 open collector outputs
⦁2 Form C Relay outputs
⦁Built-in offsite communications dialer (Contact ID or SIA) available with modem editions
⦁Industry standard DIN rail mounting
Controller Editions
There are two editions of the PRT-CTRL-DIN controller:
⦁The PRT-CTRL-DIN includes a built-in 2400bps modem dialer, which allows it to communicate alarms and
upload information to remote systems using Contact ID or SIA protocols. It can also communicate over IP, or
via connection to the PRT-4G-USB DINRail Cellular Modem.
⦁The PRT-CTRL-DIN-IP does not include a built-in modem. It can communicate alarms and upload information
to remote systems over IP,or via connection to the PRT-4G-USB DINRail Cellular Modem.
The features specific to the panel modem interface described in this manual are only relevant for the appropriate
controller edition.
PRT-CTRL-DIN | Protege GX DIN Rail Integrated System Controller | Installation Manual 6

Installation Requirements
This equipment is to be installed in accordance with:
⦁The product installation instructions
⦁UL 681 - Installation and Classification of Burglar and Holdup Systems
⦁UL 827 - Central-Station Alarm Services
⦁CAN/ULC-S301, Central and Monitoring Station Burglar Alarm Systems
⦁CAN/ULC-S302, Installation and Classification of Burglar Alarm Systems for Financial and Commercial
Premises, Safes and Vaults
⦁CAN/ULC-S561, Installation and Services for Fire Signal Receiving Centres and Systems
⦁The National Electrical Code, ANSI/NFPA 70
⦁The Canadian Electrical Code, Part I, CSA C22.1
⦁AS/NZS 2201.1 Intruder Alarm Systems
⦁The Local Authority Having Jurisdiction (AHJ)
Wiring
P
UL
ULC
For UL/ULCinstallations the following wiring specifications must be observed.
Earth Ground Wiring: Minimum 14AWG solid copper wire.
Input Wiring: Maximum distance of 300m (1000ft) from the connected module when using 22 AWG.
Aux Wiring: Minimum 22AWG, maximum 16AWG (depends on length and current consumption).
For wire/cable size, a maximum of 5% voltage drop at the terminals of the powered device has to be observed.
Ethernet Wiring: CAT5e / CAT6. Maximum length 100m (330 ft).
Module Network Wiring: Recommended Belden 9842 or equivalent.
⦁24AWG twisted pair with characteristic impedance of 120ohm. Maximum length 900m (3000ft).
⦁CAT5e / CAT6 also supported for data transmission when using ground in the same cable. Maximum length
100m (330 ft).
Do not use extra wires in the cable to power devices.
PRT-CTRL-DIN | Protege GX DIN Rail Integrated System Controller | Installation Manual 7

Grounding Requirements
An effectively grounded product is one that is intentionally connected to earth ground through a ground
connection or connections of sufficiently low impedance and having sufficient current-carrying capacity to
prevent elevated voltages which may result in undue hazard to connected equipment or to persons.
Grounding of the Protege system is done for three basic reasons:
1. Safety
2. Component protection
3. Noise reduction
Safety Grounding
The object of safety grounding is to ensure that all metalwork is at the same ground (or earth) potential.
Impedance between the Protege system and the building scheme ground must conform to the requirements of
national and local industrial safety regulations or electrical codes. These will vary based on country, type of
distribution system and other factors. The integrity of all ground connections should be checked periodically.
General safety dictates that all metal parts are connected to earth with separate copper wire or wires of the
appropriate gauge.
Earth Ground Connection
The DIN rail enclosure and the DIN rail modules must be grounded to a suitable single-point earth ground
connection in the installation. A minimum 14AWG solid copper wire (or thicker, in accordance with local
authorities) shall be used from the Protege system's earth connection points.
The DIN rail enclosure includes an earth ground single-point link connection via the metallic enclosure. This single-
point link is the Protege system's earth ground. All modules that have earth ground connections and that are
installed in the same enclosure shall be connected to this single point. A single-point earth ground connection
avoids the creation of ground loops in the system and provides a single reference point to earth ground.
Reader Expander
Input Expander
Output Expander
Controller
Dialer’s Earth
Ground Connection
Power Supply
V-
DIN Rail Ground Connections (one or more cabinets installed in the same room)
DIN Rail Enclosure Additional DIN Rail Enclosure(s)
Module Network
(RS-485 N+, N-, NA, NB)
AC Mains Wiring
Earth Ground
Link Connection
PRT-CTRL-DIN | Protege GX DIN Rail Integrated System Controller | Installation Manual 8

Sector or Building #2Sector or Building #1 Sector or Building #3
Input Expander
Input Expander
Input Expander
Reader Expander
Input Expander
Output Expander
Power Supply
Controller
Dialer’s Earth
Ground Connection
V-
Earth Ground
Link Connection
DIN Rail Enclosure DIN Rail Enclosure DIN Rail Enclosure
Module Network (RS-485 N+, N-, NA and NB)
DIN Rail Ground Connections (multiple cabinets in different rooms, sectors, or buildings)
The Dialer's Earth Ground Connection applies to modem model controllers only.
Note that the DIN rail enclosure earth terminal is connected to the power supply V- terminal.
There must be only one single earth grounding point per system.
PRT-CTRL-DIN | Protege GX DIN Rail Integrated System Controller | Installation Manual 9

Mounting
Protege DIN rail modules are designed to mount on standard DIN rail either in dedicated DIN cabinets or on
generic DIN rail mounting strip.
When installing a DIN rail module, ensure that there is adequate clearance around all sides of the device and that
air flow to the vents of the unit is not restricted. It is recommended that you install the module in a location that
will facilitate easy access for wiring. It is also recommended that the module is installed in an electrical room,
communication equipment room, secure cabinet, or in an accessible area of the ceiling.
1. Position the DIN rail module with the labeling in the correct orientation.
2. Hook the mounting tabs (opposite the tab clip) under the edge of the DIN rail.
3. Push the DIN rail module against the mount until the tab clips over the rail.
Removal
A Protege DIN rail module can be removed from the DIN rail mount using the following steps:
1. Insert a flat blade screwdriver into the hole in the module tab clip.
2. Lever the tab outwards and rotate the unit off the DIN rail mount.
PRT-CTRL-DIN | Protege GX DIN Rail Integrated System Controller | Installation Manual 10

Wiring Diagram: PRT-CTRL-DIN
CAUTION: Incorrect wiring may result in damage to the unit.
+
-
1N4007
Diode
1N4007
Diode
Electric Locking
Device
1.1A (Typical)
Electric
Locking
Device
1.1A Ohm
30W Siren
or 1.1A
(Typical)
N.C Input Contact
Shield
Red
Black
Green
White
Orange
Brown
Blue
Yellow
Shield
Red
Black
Green
White
Orange
Brown
Blue
Yellow
Violet
Violet
NAN+ N- NB
Next modules
on network
NAN+ N- NB
USB ETHERNET
MODEM
RELAY 2RELAY 1
BELL
RS485 NETWORK12VDC IN
N+ N- NA NB B+ B- NO COM NC NOCOM NC T1i R1i T1oR1o
READER 2 INPUT 5-8 12VDC OUT READER 1 INPUT 1-4 12VDC OUT
White
Blue
Black
Red
UL listed power
supply or module
supplying power to
networked devices
+
-
+
-
1K
+
-
Lock Power
Supply
+
-
1N4007
Diode
Electric Locking
Device
+
-
Lock Power
Supply
+
-
RJ31X
Grey
Brown
Red
Green
Cold water
earth pipe
Security System
User Interface
Controller
V+V-
Z1
V-
Z2Z3
V+
Z4NANBL1
BZV+V-Z5V-
Z6
Z7V-
Z8
NANB
L1
BZ
D1/ D0/ D1/ D0/
N.C Input Contact
Door Contact Door Contact 1K 1K
1K1K
1K1K
1K1K
1K1K
1K 1K
1K 1K
1K 1K
N.O Input Contact
N.C Input Contact
Bond Sense Bond Sense
N.O Input Contact
REN
REXREX
REN
Optional UL
Listed Reader
Optional UL
Listed Reader
N.C Input Contact
N.O Input Contact
N.O Input Contact
PRT-CTRL-DIN | Protege GX DIN Rail Integrated System Controller | Installation Manual 11

Wiring Diagram: PRT-CTRL-DIN-IP
CAUTION: Incorrect wiring may result in damage to the unit.
+
-
1N4007
Diode
1N4007
Diode
Electric Locking
Device
1.1A (Typical)
Electric
Locking
Device
1.1A Ohm
30W Siren
or 1.1A
(Typical)
N.C Input Contact
Shield
Red
Black
Green
White
Orange
Brown
Blue
Yellow
Shield
Red
Black
Green
White
Orange
Brown
Blue
Yellow
Violet
Violet
NAN+ N- NB
Next modules
on network
NAN+ N- NB
USB ETHERNET
RELAY 2RELAY 1
BELL
RS485 NETWORK12VDC IN
N+ N- NA NB B+ B- NO COM NC NOCOM NC
READER 2 INPUT 5-8 12VDC OUT READER 1 INPUT 1-4 12VDC OUT
White
Blue
Black
Red
UL listed power
supply or module
supplying power to
networked devices
+
-
+
-
1K
+
-
Lock Power
Supply
+
-
1N4007
Diode
Electric Locking
Device
+
-
Lock Power
Supply
+
-
Security System
User Interface
Controller
V+V-
Z1
V-
Z2Z3
V+
Z4NANBL1
BZV+V-Z5V-
Z6
Z7V-
Z8
NANB
L1
BZ
D1/ D0/ D1/ D0/
N.C Input Contact
Door Contact Door Contact 1K 1K
1K1K
1K1K
1K1K
1K1K
1K 1K
1K 1K
1K 1K
N.O Input Contact
N.C Input Contact
Bond Sense Bond Sense
N.O Input Contact
REN
REXREX
REN
Optional UL
Listed Reader
Optional UL
Listed Reader
N.C Input Contact
N.O Input Contact
N.O Input Contact
PRT-CTRL-DIN | Protege GX DIN Rail Integrated System Controller | Installation Manual 12

Connections
Power Requirements
Power is supplied to the controller by a 12V DC power supply connected to the N+ and N- terminals. The controller
does not contain internal regulation or isolation and any clean 12V DC supply is suitable for this purpose.
Termination of wiring to the module while power is applied or the battery is connected may cause serious
damage to the unit and will VOID ALL WARRANTIES OR GUARANTEES.
Power the unit only after all wiring, configuration and jumper settings are completed.
A battery backup must be connected to the module network to provide a monitored supply. The battery plays an
important role in power conditioning and provides a continuous source of power in the event of a power outage.
P
UL
ULC
For UL applications, must be powered by a UL Listed (UL 603 or UL 294) power limited power
supply capable of supplying at least 4 hours of standby power.
For ULC applications, must be powered by a ULC Listed (CAN/ULC S318 or CAN/ULC S319) power
limited power supply capable of supplying at least 24 hours of standby power.
Example 2A Power Supply Connection:
PRT-CTRL-DIN | Protege GX DIN Rail Integrated System Controller | Installation Manual 13

Example 4A Power Supply Connection:
In a small installation this same power supply can be used to supply the module network as well, so long as the
maximum load of the power supply is not exceeded. In larger installations, the power supply may need to be split
to allow for load sharing between several supplies.
To comply with EN 50131-1 only one battery can be connected and monitored per system. If more capacity is
required a single larger battery must be used.
Example Multiple PSU Connection:
When using multiple power supplies it is important to ensure that all ground connections (V-) are connected
between all power supplies and that no power connections (V+) are connected between any power supplies.
PRT-CTRL-DIN | Protege GX DIN Rail Integrated System Controller | Installation Manual 14

Auxiliary Outputs
The auxiliary outputs (V- V+) of the controller can be used to supply other equipment. Note that there is no
onboard regulation or isolation for these outputs; they are a fused feed-through from the N+ N- input terminals.
When using these outputs to supply other devices, be sure not to exceed the rating of the internal fuses as
outlined in the Technical Specifications.
Encrypted Module Network
The controller incorporates encrypted RS-485 communications technology. Connection of the communications
should be performed according to the following diagram.
PSU or
equivalent 12V DC
Shield is frame
grounded at
one point
Shields are
connected together
and Isolated
Shielded Cable
Controller Network Module Network Module
Shielded Cable
Shield not
connected
supply
NAN+ N- NB NAN+ N- NB
NAN+ N- NB
Always connect the controller's NA and NB terminals to the NA and NB terminals of the expansion devices and
keypads. The N+ and N- must connect to a 12V power supply source capable of supplying the peak current drawn
by all modules. If a shielded cable is used, the shield must be connected at only one end of the cable. DO NOT
connect a shield at both ends.
The 12V N+ and N- communication input must be supplied from only one point. Connections from more than
one 12V supply may cause failure or damage to the unit or the device supplying network power. Make sure that
the power supply can supply enough current for the peak load drawn by all modules connected to the 12V
supply, including the controller itself.
Module Wiring
The recommended module network wiring specifications are:
⦁Belden 9842 or equivalent
⦁24AWG twisted pair with characteristic impedance of 120 ohm
⦁Maximum total length of cable is 900m (3000ft)
⦁CAT5e / CAT6 are also supported for data transmission when using ground in the same cable (to a maximum
length of 100m (328ft))
Warning: Unused wires in the cable must not be used to carry power to other devices.
PRT-CTRL-DIN | Protege GX DIN Rail Integrated System Controller | Installation Manual 15

End of Line (EOL) Resistors
The 330 ohm EOL (End of Line) resistor provided in the accessory bag must be inserted between the NA and NB
terminals of the first and last modules on the RS-485 network. These are the modules physically located at the
ends of the RS-485 network cabling.
330R 330R
First Module on RS-485 Network Last Module on RS-485 Network
To
Next
Module
From
Previous
Module
NAN+ N- NB
NAN+ N- NB
PRT-CTRL-DIN | Protege GX DIN Rail Integrated System Controller | Installation Manual 16

Telephone Dialer
Modem model only.
The controller provides the ability to communicate alarms and upload information to remote systems using the
onboard 2400bps modem. The telephone line can be connected directly to the controller using the onboard
telephone connection terminals.
Telco line out
Telco line
tip and ring input
R1i T1o R1o
T1i
Cellular Modem
The controller provides the ability to communicate alarms and upload information to remote systems via the
Protege DINRail Cellular Modem (PRT-4G-USB).
The modem can be connected directly to the controller using the Type-A USB port.
Protege controllers which do not have a physical USBport are incompatible and cannot be retrofitted.
Controller
USB
ANT
SIM
12VDC IN
USB
N+ N-
Cellular
Modem
USB-A to USB-C cable
For more information, see the Protege DINRail Cellular Modem Installation Manual and Protege DINRail Cellular
Modem Configuration Guide.
PRT-CTRL-DIN | Protege GX DIN Rail Integrated System Controller | Installation Manual 17

Ethernet 10/100 Network Interface
The communication between the Protege system and the controller uses a 10/100 ethernet network operating the
TCP/IP protocol suite. The IP address of the controller can be configured using an LCD keypad terminal or via the
built-in web interface. The default IP address is set to a static address of 192.168.1.2 with a subnet mask of
255.255.255.0. These IP address settings are commonly used for internal networks.
Installing the module on an active network requires knowledge of the configuration and structure for the network.
Always consult the network or system administrator and ask them to provide you with a fixed IP address that can
be assigned to the module.
When installing an ethernet connection the module should be interfaced using a standard segment (<100m in
length) and should be connected to a suitable ethernet hub or switch:
Ethernet 10/100 Switch hub Connection:
Controller
Controller
Temporary direct connections can be used for onsite programming by using a standard ethernet cable.
Ethernet 10/100 Direct Connection:
Controller
P
UL
ULC
⦁All network equipment such as hubs/routers/gateways used with the controller must comply
with the UL and ULC standard requirements associated with a signal receiving center.
⦁The controller must be installed in the same room as the network equipment that provides it
the network connection.
PRT-CTRL-DIN | Protege GX DIN Rail Integrated System Controller | Installation Manual 18

Door Access Control
The controller provides access control functionality onboard without the requirement for additional hardware.
The controller allows the connection of 2 Wiegand devices to control 2 doors (entry or exit only) or 1 door (entry
and exit), or it can be configured in multiplex mode to allow 4 Wiegand devices controlling 2 doors with entry and
exit readers. Alternatively, the reader ports can be independently configured to connect RS485 readers.
The recommended cable types for RS-485 are:
⦁Belden 9842 or equivalent
⦁24 AWG twisted pair with characteristic impedance of 120ohm
The recommended cable types for Wiegand are:
⦁22 AWG alpha 5196, 5198, 18 AWG alpha 5386, 5388
Important:
⦁The card reader must be connected to the module port using a shielded cable.
⦁The shield must only be connected at one end of the cable in the metallic enclosure (frame grounded).
⦁Do not connect the cable shield to an AUX-, 0V or V- connection on the module.
⦁Do not connect the cable shield to any shield used for isolated communication.
⦁The reader and cable shield wires must be joined at the reader pigtail splice.
⦁Do not join the shield and black wires at the reading device.
⦁Do not terminate the reader shield wire inside the reader.
Note: The reader and cable shield wires must be joined at the reader pigtail splice for all MIFARE capable ICT card
readers. Older readers which are internally grounded and third-party readers do not require the shield wires to be
joined. For further information, contact ICT Technical Support.
Always refer to the card reader manufacturer for detailed installation guidelines.
P
UL
ULC
All UL listed ICT readers are shipped with single LED mode set as default and are fully compatible
with the Protege system.
RS-485 Reader Locations
As two RS-485 readers can be connected to the same RS-485 reader port, configuration of the green and orange
wires uniquely identifies the reader, and determines which is the entry reader and which is the exit reader.
Location Configuration
Entry Green and orange wires not connected.
Exit Green and orange wires connected together.
PRT-CTRL-DIN | Protege GX DIN Rail Integrated System Controller | Installation Manual 19

RS-485 Reader Connection (Entry Only)
The following diagram shows the connection of a single RS-485 reader connected in entry only mode.
V+
V-Z4 V- Z3 Z2 V- Z1BZ L1 D1/
NB
D0/
NA
Shield is frame
grounded at
one point
1 2
3 4
5 6
7 8
9 0
X
RED
BLACK
SHIELD
GREEN
WHITE
ORANGE
BROWN
BLUE
YELLOW
VIOLET
Reader shield is
not terminated
inside the reader
Shield wires
connected
at the splice
When the green and orange wires are not connected together, the reader defaults to an entry reader.
RS-485 Reader Connection (Entry/Exit)
The following diagram shows the connection of two RS-485 readers connected to provide an entry/exit
configuration.
V+
V-Z4 V- Z3 Z2 V- Z1BZ L1 D1/
NB
D0/
NA
Shield is frame
grounded at
one point
ENTRY
EXIT
1 2
3 4
5 6
7 8
9 0
X
RED
BLACK
SHIELD
GREEN
WHITE
ORANGE
BROWN
BLUE
YELLOW
VIOLET
Reader shield is
not terminated
inside the reader
Shield wires
connected
at the splice
RED
BLACK
SHIELD
GREEN
WHITE
ORANGE
BROWN
BLUE
YELLOW
VIOLET
Shielded Cable
Shielded Cable
The exit reader has the green and orange wires connected together.
A 330 ohm EOL (End of Line) resistor may be required to be inserted between the NA and NB terminals of the
reader port.
PRT-CTRL-DIN | Protege GX DIN Rail Integrated System Controller | Installation Manual 20
This manual suits for next models
1
Table of contents
Other ICT Controllers manuals

ICT
ICT PRT-CTRL-DIN-1D User manual

ICT
ICT Distribution 3 Series User manual

ICT
ICT PRT-CTRL-DIN-1D User manual

ICT
ICT PRT-WX-DIN User manual

ICT
ICT PRT-WX-DIN-1D User manual

ICT
ICT PRT-WX-DIN-1D User manual

ICT
ICT PRT-CTRL-DIN User manual

ICT
ICT Protege GX User manual

ICT
ICT Protege GX DIN Rail System Controller User manual

ICT
ICT Protege WX User manual