EARTH GND WIRING:Minimum 14AWG solid
copper wire.
INPUT WIRING:maximum distance of 300m (1000ft)
from the Controller when using 22 AWG
AUX WIRING:Min 22AWG Max 16AWG. (Depends on
length and Current consumption). For wire/cable size,
a maximum of 5% voltage drop at the terminals of
the powered device has to be observed.
ETHERNET WIRING:CAT5e / CAT6 max 100m (330 ft)
MODULE NETWORK WIRING:Recommended Belden
9842 or equivalent. (24AWG twisted pair with
characteristic impedance of 120ohm or CAT5e / CAT6
are also supported for Data Transmission when using
ground in the same cable.
Do not use extra wires to
power devices.)max 900m (3000ft).
Configuration
ConnectReader 1 D0 to L1then power cycle the
Controller to forceitto use 192.168.111.222 as
it's IP address.
ConnectReader 2 D0 to L1then power cycle the
Controller to reset it to factory defaults. Note:
this will not reset the Ethernet settings.
Reader 2 Reader 1
If not used for Reader functions the Reader
outputs (L1& BZ) can be used as general
purposeouputs. They are Open Collector Outputs
& switch to 0V. The outputs can be used to
activate relays, sounders and lights.
1K5 OHM
Z4 V- Z3 Z2 V- Z1 V- V+
LED
Programmable Outputs (L1 & BZ)
LED Description
Power Green Power is applied
Off Low or no power is applied
Status Flashing green Normal operation
Fault Red A fault has occurred
Off Normal operation
Ethernet
Green Ethernet connection present
Off No Ethernet connection detected
Active Ethernet data
Modem Green Themodemhas control of thetelephone line
Off Modemnot active
R1 /R2 Data received but format is incorrect
Correctly formatted data received
Relay1/2 Red Relayis closed
Off Relayis open
Bell
Green Bell is turned on
Off Bell is connected and turned off
Bell is turned on, and the circuitis in
over-current protection
Bell is turned off, and the circuitis cut,
damaged or tampered
Zone1-8
Off The Input is not programmed
Red Input is in the OPEN state
Green Input is in the CLOSED state
Flashing red Input is in the TAMPERED state
Flashing green Input is in the SHORTED state
2green flashes
1green flash
Long red flash
Short red flash
Fast green flash
+AUX- Z1 COM COMZ2 Z3 Z4
N.C Input Contact
N. C
Tamper Value 2 Value 1
Typical Input Circuits
Value 1 Value 2 Monitored Status
No Resistor No Resistor Open, Closed
1k 1k Open, Closed, Tamper, Short
2k2 6k8 Open, Closed, Tamper, Short
10k 10k Open, Closed, Tamper, Short
2k2 2k2 Open, Closed, Tamper, Short
4k7 2k2 Open, Closed, Tamper, Short
4k7 4k7 Open, Closed, Tamper, Short
CAUTION:
INCORRECT
WIRING MAY RESULT IN
DAMAGE TO THE UNIT
Input Options
The onboard reader ports use inputs 1 – 8 as
door contact, REX, bond sense and REN inputs
respectively. Any of these inputs that are not
configured for use with the Onboard Reader
may be used as general purpose inputs. Refer to
the Controller Installation Manual for instructions
on programming the onboard reader.
BZ L1 NB NA Z8 V- Z7 Z6 V- Z5 V- V+ BZ L1 NB NA Z4 V- Z3 Z2 V- Z1 V- V+
READER 2 READER 1
ZONE INPUT 5-8 ZONE INPUT 1-412VDC OUT 12VDC OUT
D1/ D0/ D1/ D0/
Controller
For UL applications,must be powered by aUL
Listed (UL 603 or UL 294) power limited power
supply capableof supplying at least 4 hours of
standby power. For ULC application, must be
powered by a ULC Listed (CAN/ULCS318) or
(CAN/ULC-S319 power limited power supply
capable of supplying at least 24 hours.
External Power Supply
Optional UL
Listed Reader
EOL Resistor Input Configuration
N.C Input Contact
Door Contact 1K 1K
REX 1K 1K
N . O Input Co nt act
N.C Input Contact
Bond Sense 1K 1K
REN 1K 1K
N . O Input Co nt act
Optional UL
Listed Reader
N.C Input Contact
1K 1K Door Contact
1K 1K REX
N . O Input Cont act
N.C Input Contact
1K 1K Bond Sense
1K 1K REN
N . O Input Co nt act
Input
LON
Interface