INIM IRIS ID200 User manual

Iris
onventional fire detectors
ID100 - optical smoke detector
ID200 - temperature detector
ID300 - multicriteria detector
TTENTION!
For information regarding device placement, coverage and method of installation, refer to
the established standard regulations and codes relating to automatic fire-detection systems.
Iris series detectors are compliant with EN54-7: Smoke detectors – Point detectors using the
scattered light principle, light transmission or ionization (ID100 and ID300 models only)
and EN54-5: Heat detectors – point detectors (for ID200 and ID300 models only).
Product description
Iris series detectors offer wide-spectrum detection of smoke particles generated by the majority of fires. They
are suitable for most applications and provide first-rate early warning.
The EITK-DRV driver, supplied by INIM Electronics, allows you to change the operating parameters to suit specific
environment conditions. This device permits easy programming and verification of contamination and
performance. For further details, refer to “Using the EITK-DRV driver” section.
During standby status, these detectors have low current draw, 80A. However, in the event of alarm the current
draw increases to a maximum of 40mA thus signalling the condition to the control panel.
INIM Electronics offers three Iris series conventional fire-detectors, which can be identified by the technical
specifications/serial number on the back of the detector.
ID100
Optical detector equipped with a reference chamber based on the scattered light
principle (Tyndall effect). This detector must be installed in draught and obstacle
free place which guarantees appropriate air-flow into the reference chamber.
The detector will trigger an alarm when the level of smoke inside the reference
chamber reaches the following values:
• 0.08 dB/m (mode set via the EITK-DRV)
• 0.10 dB/m (mode set via the EITK-DRV)
• 0.12 dB/m (pre-set mode)
• 0.15 dB/m (mode set via the EITK-DRV)
ID200
Heat detector with heat-sensitive element capable of sensing the temperature
within the protected environment.
The operating modes, programmable via the EITK-DRV are:
• “A1R” (pre-set); the detector signals alarm status when the temperature within the protected
environment exceeds 58 °C or when the temperature undergoes anomalous changes.
• “B”; the detector signals alarm status when the temperature within the protected
environment exceeds 72°C.
• “A2S”; the detector signals alarm status when the temperature within in the protected
environment exceeds 58°C.
• “BR”; the detector signals alarm status when the temperature within the protected
environment exceeds 72° or when it senses a rapid temperature rise.
TTENTION!
The operating modes of the “A2S” and “BR” are not certified.
ID300
Optical-heat detector with heat sensitive element and optical smoke chamber. The
combination of values provides (in accordance with the operating mode selected
via the EITK-DRV driver) high immunity to nuisance alarms and an exceptionally
sensitive detector which is capable of swift response to fires characterized by low
smoke emission.
The operating modes, programmable via the EITK-DRV driver are:
• “PLUS” (pre-set); the detector signals alarm status when smoke in the protected
environment exceeds the programmed threshold (programmed as described for the
ID100 model) or when the temperature within the protected environment exceeds the
N54-7:2000+A1+A2
ID100 NNNNNNNN ID100 NNNNNNNN
ID100
0832
0832-CPR-F1152
MAD IN ITALY
991c/01
NNNNNNNN
*NNNNNNNN*
YYYY/MM
FW: FF.WW
CONV NTIONAL
OPTICAL SMOK D T CTOR
N54-5:2000+A1
ID200 NNNNNNNN ID200 NNNNNNNN
ID200
0832
0832-CPR-F1243
MAD IN ITALY
991e/01
NNNNNNNN
*NNNNNNNN*
YYYY/MM
FW: FF.WW
CONV NTIONAL
CLASS P H AT D T CTOR
N54-5:2000+A1
N54-7:2000+A1+A2
ID300 NNNNNNNN ID300 NNNNNNNN
ID300
0832
0832-CPR-F1153
MAD IN ITALY
991a/01
NNNNNNNN
*NNNNNNNN*
YYYY/MM
FW: FF.WW
CONV NTIONAL
MULTI OPTICAL SMOK AND CLASS P H AT D T CTOR
0832
0832-CPR-F1152
0832-CPR-F1243
0832-CPR-F1153
991c/01
991e/01
991a/01

6
Iris
programmed threshold (programmed as described for the model ID200). Furthermore, in the event of a rise in
temperature within the protected environment, the sensibility of the smoke chamber will be increased. This operating
mode, characterized by high sensitivity, allows detection of fires which produce a large amount of flames but low smoke
emission (e.g. combustion of alcohol or similar highly-inflammable products).
• “OR”; the detector signals alarm status when smoke in the protected environment exceeds the programmed threshold
(programmed as described for the ID100 model) or when the temperature within the protected environment exceeds the
programmed threshold (programmed as described for the ID200 model). This operating mode, characterized by a medium-
high sensitivity, allows detection of fires which generate a substantial amount of smoke (slow burning fires) and also fires
which generate high temperatures with low smoke emission (chemical products).
• “AND”; the detector signals alarm status when the smoke and temperature in the protected environment exceed the
programmed thresholds simultaneously (programmed as described for the ID100 model and ID200 respectively). This
operating mode, characterized by a low sensitivity, lowers the false alarm rate and is useful in applications where either the
smoke or heat values in the protected environment may increase without the risk of fire.
TTENTION!
Given the limited response, consider the conditions in the protected environment
carefully before selecting this operating mode.
• “SMOKE”; the detector assumes the characteristics of the ID100 model
• “HEAT”; the detector assumes the characteristics of the ID200 model
Installation
TTENTION!
The detectors are supplied with protective covers which help to protect them against
minor damage and dust contamination which may occur during the installation phase.
The covers should not be removed until the system is ready to start up.
Iris series detectors should be used with one of the following compatible mounting bases:
•
EB0010
; standard base
An example of installation using standard bases is shown opposite.
TTENTION!
The value of the EOL resistance depends on the type of control panel in use.
•
EB0020
; relay base
Appropriate when the detector is to be connected to an intrusion control panel or to a control panel using 4 wires. For the
respective wiring instructions, refer to the leaflet supplied with the EB0020.
TTENTION!
The two removable serial-number stickers should be taken off and one should be
attached to the mounting base and the other to the installation layout.
Once the base is located properly in its placement, place the detector unit onto the base and, with minimum
force, turn it clockwise until notch [A] aligns with notch [B] (in order to attach the detector to the base); turn it
still further until notch [A] aligns with notch [C] (in order to allow the base to engage with the detector contacts).
Testing and maintenance
After installation and during periodic maintenance inspections, you must carry out the following operations on
each detector:
•
heck the LED
; if the LED blinks at 5 second intervals, the detector is in fault status. This may be due to dust
contamination. If after cleaning, this condition persists, remove the faulty detector and replace it with a new one. The
EITK-DRV driver will assist you in finding the cause of faults.
•
Optical smoke detector test
; smoke detectors should be tested immediately after installation and periodically during
maintenance inspections in accordance with the established standard regulations and codes in force. To test smoke
detectors, use an approved test aerosol strictly in accordance with the accompanying instructions.
Ensure that the smoke inlet ports to the smoke detection chamber are not blocked. Check the contamination level of the
smoke detection chamber via the EITK-DRV. If the contamination level is high, detach the detector from its mounting base
Technical specifications ID100 ID200 ID300
Power supply 10-30V
Average current draw in standby 90A 70A 90A
Average current draw in alarm Max 40mA
Current draw by the “R” output
(internally limited) Max 14mA
Operating temperature -5°C / +40°C
Humidity (without condensation) 95% RH
Height (standard base included) 46mm 54mm
Diameter (standard base included) 110mm
Weight (standard base included) 160g
Weight (without base) 91g
A
B

onventional fire detectors
7
A
Detector
H
Cover removing hooks
B
Base
I
Optical chambre removing
hooks
Red/green LED
L
“+” terminal
D
Optical chamber
M
“-” terminals
E
Thermal probe
N
“R” terminal
F
Identifier sticker
O
Short-circuit reed
G
Technical specifications/
serial-number sticker
P
Screw locations
A
E
F
I
L
M
N
O
B
D
A
H
H
D
E
P
P
G
I

8
Iris
and open the chamber then, using a small, soft-bristle brush or hand-held vacuum cleaner remove all dust particles from
inside and around the smoke detection chamber and free the protection mesh from all contaminants.
•
Heat detector test
; using a suitable device (e.g. hairdryer), create heat in the vicinity of the detector, then work through
the steps described in the device instruction sheet. During each periodic maintenance inspection, ensure that the heat
element is intact and that is not obstructed by dust or paint. If it is, using a small, soft-bristle brush or hand-held vacuum
cleaner remove all contaminants.
Operating mode
The bicolour LED (360° viewing) indicates the detector status.
• Green blinking at 30-second intervals: detector in standby status (i.e. operating properly).
• Green blinking at 5-second intervals: detector in fault status. Further details regarding the cause of the fault (high
contamination level in the smoke chamber, detector component fault, etc.) can be obtained through the EITK-DRV driver.
• Red LED On solid: detector in alarm status.
The detectors have an output (terminal “R”), for the connection of an alarm repeater LED. This LED will activate
when the detector it refers to triggers an alarm.
Using the EITK-DRV driver
The EITK-DRV driver allows you to change the operating parameters of the detectors, check the contamination
level of the smoke chambers and also obtain accurate diagnostic data. It can operate through the USB port of a
computer furnished with the relative software programme, or can function autonomously by way of the battery
housed inside.
Each detector is capable of retaining memory (smoke and/or temperature depending on the model) of the 5
minutes prior to an alarm. Therefore, if an alarm occurs, it will be possible to obtain information regarding the
onset of the fire by simply connecting the EITK-DRV driver to the detection line.
For further information and details regarding use of the EITK-DRV driver, refer to the respective handbook.
Warnings and limitations
Iris series detectors must be used exclusively with fully compliant, compatible control panels. Detectors may not
provide timely warning of fire if coverage is limited by large obstructions (pillars, large machinery, etc.). When
installing or working on a fire detection system, always refer to and comply with the established standard
regulations and codes. Appropriate fire-risk assessment should be undertaken to determine the type of detectors
required and their placements.
E marking and certifications
DoP, EC DoC and certificates related to these products can be downloaded from the following link:
www.inim.biz/certifications
832
INIM Electronics s.r.l.
Via Fosso Antico snc - Fraz. Centobuchi
63 76 Monteprandone (AP) - Italy
15
832-CPR-F1152
EN 54-7:2 + A1:2 2 + A2:2 6
ID1
Conventional optical smoke detector for fire detection and fire
alarm systems installed in buildings
Essential characteristics
Performance
Nominal activation condition/sensitivity,
response delay (response time) and
performance under fire conditions PASS
Operational reliability PASS
Tolerance to supply voltage PASS
Durability of
operational
reliability
Temperature resistance PASS
Vibration resistance PASS
Humidity resistance PASS
Corrosion resistance PASS
Electrical stability PASS
832
INIM Electronics s.r.l.
Via Fosso Antico snc - Fraz. Centobuchi
63 76 Monteprandone (AP) - Italy
15
832-CPR-F1243
EN 54-5:2 + A1:2 2
ID2
Conventional class P heat detector for fire detection and fire
alarm systems installed in buildings
Essential characteristics
Performance
Nominal activation condition/sensitivity,
response delay (response time) and
performance under fire conditions PASS
Operational reliability PASS
Tolerance to supply voltage PASS
Durability of
operational
reliability
Temperature resistance PASS
Vibration resistance PASS
Humidity resistance PASS
Corrosion resistance PASS
Electrical stability PASS
Detector class (EN54-5): A1R or B
832
INIM Electronics s.r.l.
Via Fosso Antico snc - Fraz. Centobuchi
63 76 Monteprandone (AP) - Italy
15
832-CPR-F1153
EN 54-5:2 + A1:2 2
EN 54-7:2 + A1:2 2 + A2:2 6
ID3
Conventional multicriteria optical smoke and class P heat
detector for fire detection and fire alarm systems installed in
buildings
Essential characteristics
Performance
Nominal activation condition/sensitivity,
response delay (response time) and
performance under fire conditions PASS
Operational reliability PASS
Tolerance to supply voltage PASS
Durability of
operational
reliability
Temperature resistance PASS
Vibration resistance PASS
Humidity resistance PASS
Corrosion resistance PASS
Electrical stability PASS
Detector class (EN54-5): A1R or B
INIM Electronics reserves the right to change
the technical specifications of this product
without prior notice.
INIM Electronics s.r.l.
via Fosso Antico, entobuchi
63076, Monteprandone, (AP) Italy
Tel. +39 0735 70 50 07
Fax + 39 0735 70 49 12
www.inim.biz [email protected]
This manual suits for next models
2
Table of contents
Popular Fire Alarm manuals by other brands

Plumis
Plumis Automist User handbook manual

HST
HST HS201 Installation and maintenance instruction

Vigilant
Vigilant FP0539 Operating & installation instructions

Panasonic
Panasonic Firetracker FT1020G3 CIE Technical and Programming Manual

Fire-Lite Alarms
Fire-Lite Alarms MS-4412B manual

Simplex
Simplex 4100ESi installation guide