Innotech GENII CSAH REM User manual

© MASS ELECTRONICS Pty Ltd 2006
Models:
GENII CSAH REM: Control Station Aer Hours Module
DS 15.09
August 2013
GENII CSAH REM
Control Station Aer Hours Module
Applications
Expands GENESIS Controller capabilities by providing a numeric output
display, numerical value input, a single momentary digital input switch
and single LED display output for distributed control via RS485. The
GENII CSAH REM Module provides a visual display of a control value and
a means to set a parameter.
Application Notes
A GENESIS Controller must have version 4.0 firmware installed to
support REM Modules. Version 4.1 or higher Config Soware must be
used to configure a GENESIS Controller that has a CSAH REM Module
connected to it.
One GENESIS Controller can have up to 9 GENII CSAH REM Modules*
connected to it via the REM comms bus. For detailed connection
information to the pre-version 5 GENESIS Digital Controller Family,
please refer to DS 99.03
Overview
The Innotech GENII CSAH REM Momentary Digital Input Control
Station Module is an expansion device for the GENESIS range of
Digital Controllers.
The module is powered by 24VAC and provides a limited User
Interface to the GENESIS Controller. There are no physical
connections between field equipment and the GENII CSAH REM,
all input/output values are edited and viewed on the wall unit.
The GENII CSAH REM may be located remotely from the GENESIS
Controller providing a distributed User Interface for the system.
The GENII CSAH REM is configured via the wallplate and
programmed via the GEN2Config Soware.
The GENII CSAH REM communicates with the Genesis Controller
via the REM Comms port. The remote link uses RS-485 at a baud
rate of 38400. For pre-version 5 controllers, a Gen II RMI Remote
Module Interface is required. Please refer to DS 15.01 for further
information.
Features
• One single decimal place numerical value input
• One single decimal place numerical output
• One momentary digital input and one LED digital display
output
• Housed in a switchplate that mounts in standard electrical
wall plates
• RS485 interconnection between REM Modules
• 24VAC operation
• Wiring Diagrams for modules generated by GEN2Config
Soware
• Adjustable user input range
• Configurable power on settings
Approvals
The GENII CSAH REM conforms to:
• EN 55011 Class B Group 1 & AS/NZS 2064:1997 for RCM
Labelling
• FCC Title 47 CFR, Part 15 Class A for FCC Marking
• UL listed to UL916, File Number E242628
© MASS ELECTRONICS Pty Ltd 2006
Page 2
DS 15.09 - GENII CSAH REM - Control Station Aer Hours Module
August 2013
Specifications
Power Supply
• Voltage: 24VAC ±10% @ 50/60Hz
• Power Consumption: 3VA max
The operating voltage must meet the requirements of Safety Extra Low
Voltage (SELV) to EN60730. The transformer used must be a Class 2 safety
transformer that has the energy and voltage limiting characteristics as
described in the National Electrical Code, ANSI/NFPA70. It must also be sized
and fused in compliance with local safety regulations.
Inputs
• Push buttons for adjusting control values
• Momentary push button for input of “digital function”
Outputs
• No physical outputs
• Display of Temperature and Setpoint
Terminal Identification
1 24VAC Supply
2 0VAC Supply
3 Earth
TERMINAL 3 is for the protection of the Comms circuitry and must
be connected to a good electrical bonded Earth.
COMMS Connection
SHLD 1 Shield from incoming Comms Cable.
+ RS 485 (+) signal.
- RS 485 (-) signal.
SHLD 2 Shield from outgoing Comms Cable.
Temperature Ratings
• Storage 0 to 50°C non-condensing
• Operating 0 to 40°C non-condensing
Enclosure
The GENII CSAH REM Modules are housed in switchplate that mounts
in standard electrical wall plates.
Colour: White
Mounting: Wall mounted
Installation
• The Cable run between the GENII CSAH REM and the GENII RMI
should not exceed 500 metres. The Comms wiring requires cable
especially suited for RS485. Other shielded cable is not suitable
and will cause spasmodic Comms failures.
• Strictly follow the guidelines when installing the Comms wiring as
outlined in the Genesis II Installation Manual.
• Mount the GENII CSAH REM in a dry and clean location free of
excess vibration.
The REM address must be set by programming Parameter 0.
Please refer to the Program Functions section of this data sheet
for more specific information regarding this.
Wiring
• The cable used for RS485 Comms must be shielded single twisted
pair, 120 ohms character impedence, 36 to 45pF per metre
capacitance between conductors.
• The Comms cable must be organised as a bus topology. That is,
starting at one end, devices are connected to it until the other
end of the cable is reached. No “stubs” are allowed. To connect a
device to the cable, as cut is made in the cable at the point where
the device is to be situated along it. Then, the two new ends of
the cable are wired into the device. The shields from the two new
ends are then terminated into the terminals marked SHLD1 and
SHLD2.
Refer to the Genesis Network Installation Instructions for more
information.
FCC Class A Notice
This device complies with Part 15 of the FCC Rules. Operation is
subject to the following two conditions:
• This device may not cause harmful interference.
• This device must accept any interference received, including
interference that may cause undesired operation.
Note – This equipment has been tested and found to comply with the limits for a Class A
digital device, pursuant to Part 15 of the FCC Rules. These limits are designed to provide
reasonable protection against harmful interference when the equipment is operated
in a commercial environment. This equipment generates, uses and can radiate radio
frequency energy and, if not installed and used in accordance with the instruction
manual, may cause harmful interference to radio communications. Operation of this
equipment in a residential area is likely to cause harmful interference in which case the
user will be required to correct the interference at his own expense. Modifications to this
device, may void the authority granted to the user by the FCC to operate this equipment.
© MASS ELECTRONICS Pty Ltd 2006
Page 3
DS 15.09 - GENII CSAH REM - Control Station After Hours Module
August 2013
Program Functions On The GENII CSAH REM
Start Programming Mode
To enter Programming Mode depress and hold the and
ON
OFF buttons for 5 seconds. The display will become blank
indicating that you are in the Programming Mode. Release both
keys and the display will show parameter 0.
Whilst in the programming mode the following buttons are
active:
ON
OFF Change to the next parameter.
Increase the current parameters value.
Decrease the current parameters value.
Parameter 0: Rem Address
The display will show current REM Address of the device.
• The range of address is 0 to 15
• The default address is 0
Parameter 1: Maximum Input Value
The display will show the Maximum Input Value to which the
module’s input can be set.
• The range of Maximum Input Value is 0.0 to 99.9
• The factory default setting is 30.0
Parameter 2: Minimum Input Value
The display will show the Minimum Input Value to which the
module’s input can be set.
• The range of Minimum Input Value is 0.0 to 99.9
• The factory default setting is 15
Exit Programming Mode
To exit the Programming Mode depress the ON
OFF and
buttons and the new setting will be saved.
Start Up Default Settings
The GENII CSAH REM Module can be set to start with a default
setpoint.
1. To set the start up default setpoint, adjust the GENII CSAH
REM Module to the desired setpoint and then press and
hold the ON
OFF and buttons for 5 seconds.
2. The display will become blank indicating that the new
setpoint has been saved.
Operating Functions On The GENII CSAH REM
Numerical Output
The GENII CSAH REM Module will display a 3 digit, single decimal place
analogue output value during normal operation.
Numerical Input
The GENII CSAH REM Module will provide a 3 digit, single decimal
place analogue input value to the GENESIS Controller during normal
operation.
This value can be modified by pressing the button to increment by
0.1 or the button to decrement by 0.1.
Momentary Digital Input Value
The ON
OFF button on the GENII CSAH REM Module provides a digital input
value to the GENESIS Controller during normal operation.
This operates as a standard momentary switch, i.e. Press the ON
OFF
button produces a momentary digital input to the GENESIS controller.
Digital Output Led
The GENII CSAH REM displays a digital state via the system LED during
normal operation.
© MASS ELECTRONICS Pty Ltd 2006
Page 4
DS 15.09 - GENII CSAH REM - Control Station Aer Hours Module
August 2013
RS485(-)
RS485(+)
RS485(-)
RS485(+)
RS485(-)
RS485(+)
YOUR DISTRIBUTOR
Australian Owned, Designed & Manufactured
by Mass Electronics Brisbane
Phone: +61 7 3421 9100 Fax: +61 7 3421 9101
Email:
[email protected] www.innotech.com.au
The INNOTECH device and the word INNOTECH are registered or unregistered trademarks of Mass Electronics Pty Ltd in Australia, USA and other countries

Other Innotech Control Unit manuals

Innotech GENII MZSAH REM User manual

Innotech

Innotech GENII MZSAH REM User manual

Innotech GENII CS REM User manual

Innotech

Innotech GENII CS REM User manual

Innotech IRM5004 User manual

Innotech

Innotech IRM5004 User manual

Innotech ICS01 User manual

Innotech

Innotech ICS01 User manual

Innotech GENII MZS REM User manual

Innotech

Innotech GENII MZS REM User manual

Popular Control Unit manuals by other brands

Telcoma T201 Instructions for installing

Telcoma

Telcoma T201 Instructions for installing

ActionTec 802R8822 Product specification

ActionTec

ActionTec 802R8822 Product specification

Pacbrake PH5 Powerhalt Programming manual

Pacbrake

Pacbrake PH5 Powerhalt Programming manual

Aaeon AQ7-BT manual

Aaeon

Aaeon AQ7-BT manual

tams elektronik mc2 40-03007 manual

tams elektronik

tams elektronik mc2 40-03007 manual

Lawler 61 Series Installation & maintenance manual

Lawler

Lawler 61 Series Installation & maintenance manual

Symmons Maxline 7-225 Series Operation & maintenance manual

Symmons

Symmons Maxline 7-225 Series Operation & maintenance manual

Systems With Intelligence IM500 installation guide

Systems With Intelligence

Systems With Intelligence IM500 installation guide

Spirax Sarco ADV Series Installation and maintenance instructions

Spirax Sarco

Spirax Sarco ADV Series Installation and maintenance instructions

Aventics HF03 operating instructions

Aventics

Aventics HF03 operating instructions

IDEC LONWORKS user manual

IDEC

IDEC LONWORKS user manual

Allen-Bradley POINT I/O series installation instructions

Allen-Bradley

Allen-Bradley POINT I/O series installation instructions

DEFA Home Relay DIN User and installation manual

DEFA

DEFA Home Relay DIN User and installation manual

ABB i-bus EIB product manual

ABB

ABB i-bus EIB product manual

Siemens SINAMICS PM230 Getting started guide

Siemens

Siemens SINAMICS PM230 Getting started guide

Spectracom SecureSync 1200 User reference guide

Spectracom

Spectracom SecureSync 1200 User reference guide

SSS Siedle BSG 650-02 manual

SSS Siedle

SSS Siedle BSG 650-02 manual

Fibocom L810-MiniPCIe Hardware user manual

Fibocom

Fibocom L810-MiniPCIe Hardware user manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.