manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. Pepperl+Fuchs
  6. •
  7. Control Unit
  8. •
  9. Pepperl+Fuchs KFD2-DWB-Ex1.D User manual

Pepperl+Fuchs KFD2-DWB-Ex1.D User manual

This manual suits for next models

1

Other Pepperl+Fuchs Control Unit manuals

Pepperl+Fuchs WCS-PNG110 User manual

Pepperl+Fuchs

Pepperl+Fuchs WCS-PNG110 User manual

Pepperl+Fuchs VAA-2E-KE1-S User manual

Pepperl+Fuchs

Pepperl+Fuchs VAA-2E-KE1-S User manual

Pepperl+Fuchs IUT-F190-R4-V1 Series User manual

Pepperl+Fuchs

Pepperl+Fuchs IUT-F190-R4-V1 Series User manual

Pepperl+Fuchs ICE11-8IOL-G60L-V1D User manual

Pepperl+Fuchs

Pepperl+Fuchs ICE11-8IOL-G60L-V1D User manual

Pepperl+Fuchs VAA-2E1A-CB10-SJ/E2J-FL User manual

Pepperl+Fuchs

Pepperl+Fuchs VAA-2E1A-CB10-SJ/E2J-FL User manual

Pepperl+Fuchs ICE11-8IOL-G60L-V1D User manual

Pepperl+Fuchs

Pepperl+Fuchs ICE11-8IOL-G60L-V1D User manual

Pepperl+Fuchs IC-KP2-1HB6-2V15B User manual

Pepperl+Fuchs

Pepperl+Fuchs IC-KP2-1HB6-2V15B User manual

Pepperl+Fuchs ICA-8DIO4M1-G20-IO User manual

Pepperl+Fuchs

Pepperl+Fuchs ICA-8DIO4M1-G20-IO User manual

Pepperl+Fuchs IC-KP2-1HB6-V15B User manual

Pepperl+Fuchs

Pepperl+Fuchs IC-KP2-1HB6-V15B User manual

Pepperl+Fuchs VBA-4E-KE5-IL User manual

Pepperl+Fuchs

Pepperl+Fuchs VBA-4E-KE5-IL User manual

Pepperl+Fuchs VBA-4E2A1A-KE3-ZEL/E2L/SEL User manual

Pepperl+Fuchs

Pepperl+Fuchs VBA-4E2A1A-KE3-ZEL/E2L/SEL User manual

Pepperl+Fuchs WCS-PNG410 User manual

Pepperl+Fuchs

Pepperl+Fuchs WCS-PNG410 User manual

Pepperl+Fuchs WCS-EIG410 User manual

Pepperl+Fuchs

Pepperl+Fuchs WCS-EIG410 User manual

Pepperl+Fuchs VBA-4E-G11-I-F User manual

Pepperl+Fuchs

Pepperl+Fuchs VBA-4E-G11-I-F User manual

Pepperl+Fuchs IC-KP2-2HB6-V15B User manual

Pepperl+Fuchs

Pepperl+Fuchs IC-KP2-2HB6-V15B User manual

Pepperl+Fuchs VBA-2E-KE5-IJL User manual

Pepperl+Fuchs

Pepperl+Fuchs VBA-2E-KE5-IJL User manual

Pepperl+Fuchs EtherCAT WCS-ECG110 User manual

Pepperl+Fuchs

Pepperl+Fuchs EtherCAT WCS-ECG110 User manual

Pepperl+Fuchs VBA-4E4A-G20-ZEJ/M48L-P12 User manual

Pepperl+Fuchs

Pepperl+Fuchs VBA-4E4A-G20-ZEJ/M48L-P12 User manual

Pepperl+Fuchs IDENT-M System V MVI-F57-2HB12 User manual

Pepperl+Fuchs

Pepperl+Fuchs IDENT-M System V MVI-F57-2HB12 User manual

Pepperl+Fuchs VAA-4E4A-G20-ZEJ/M2L-P7-GEB User manual

Pepperl+Fuchs

Pepperl+Fuchs VAA-4E4A-G20-ZEJ/M2L-P7-GEB User manual

Pepperl+Fuchs PXV Series User manual

Pepperl+Fuchs

Pepperl+Fuchs PXV Series User manual

Pepperl+Fuchs WCS-ECG410 User manual

Pepperl+Fuchs

Pepperl+Fuchs WCS-ECG410 User manual

Pepperl+Fuchs VBA-2A-KE5-IL/UL User manual

Pepperl+Fuchs

Pepperl+Fuchs VBA-2A-KE5-IL/UL User manual

Pepperl+Fuchs VAA-2E2A-KE1-S/E2 User manual

Pepperl+Fuchs

Pepperl+Fuchs VAA-2E2A-KE1-S/E2 User manual

Popular Control Unit manuals by other brands

Seitz 14A80 user manual

Seitz

Seitz 14A80 user manual

Wilo RS485 Installation and operating instructions

Wilo

Wilo RS485 Installation and operating instructions

Becker CentralControl CC41 Commissioning Instruction

Becker

Becker CentralControl CC41 Commissioning Instruction

SICK CDB650 operating instructions

SICK

SICK CDB650 operating instructions

Panduit NetKey NKP5E88M Series installation instructions

Panduit

Panduit NetKey NKP5E88M Series installation instructions

MX Options Concentric Petite Fitting instructions

MX

MX Options Concentric Petite Fitting instructions

Clean Water Systems Fleck 2510 Installation & start?up guide

Clean Water Systems

Clean Water Systems Fleck 2510 Installation & start?up guide

Fairchild FSB44104A user guide

Fairchild

Fairchild FSB44104A user guide

LEGRAND Wattstopper LMIN-104 installation instructions

LEGRAND

LEGRAND Wattstopper LMIN-104 installation instructions

PMK ATT10BNCS instruction manual

PMK

PMK ATT10BNCS instruction manual

Tektronix TDS3FFT user manual

Tektronix

Tektronix TDS3FFT user manual

Woodward easYgen Technical manual

Woodward

Woodward easYgen Technical manual

Balluff BNI EIP-502-105-R015 user guide

Balluff

Balluff BNI EIP-502-105-R015 user guide

NXP Semiconductors TWR-LS1021A Getting started

NXP Semiconductors

NXP Semiconductors TWR-LS1021A Getting started

Advantech PCM-3117 Startup manual

Advantech

Advantech PCM-3117 Startup manual

Danfoss MCO 101 manual

Danfoss

Danfoss MCO 101 manual

Moons' Lin Engineering R701P user manual

Moons'

Moons' Lin Engineering R701P user manual

Aventics RV1 operating instructions

Aventics

Aventics RV1 operating instructions

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.

Instruction Manual
1. Marking
Rotation Speed Monitor
KFD2-DWB-Ex1.D
Switch Amplifier, Timer Relay
KFD2-DU-Ex1.D
ATEX certificate: TÜV 99 ATEX 1408
ATEX marking:
1 II (1)G [Ex ia Ga] IIC
1 II (1)D [Ex ia Da] IIIC
1 I (M1) [Ex ia Ma] I
ATEX certificate: TÜV 02 ATEX 1885 X
ATEX marking: 1 II 3G Ex nA nC IIC T4 Gc
IECEx certificate:
IECEx TUN 03.0000
IECEx TSA 18.0007X
IECEx marking:
[Ex ia Ga] IIC, [Ex ia Da] IIIC, [Ex ia Ma] I
Ex ec nC IIC T4 Gc
North America Certifcates: FM22CA0016X / Project ID: 3009603 (FM)
Class I, Division 2, Groups A-D, T4
Class I, Zone 2, AEx nC, Group IIC, T4
Class I, Zone 2, Ex nA nC, Group IIC, T4
Associated apparatus with intrinsically safe circuits for:
Class I, Division 1, Groups A-D; Class II, Division 1, Groups E-G;
Class III
Class I, Zone 0, [AEx ia] IIC, Class I, Zone 0, [Ex ia] IIC
North America Certifcates: E223772 (UL)
Pepperl+Fuchs Group
Lilienthalstraße 200, 68307 Mannheim, Germany
Internet: www.pepperl-fuchs.com
2. Target Group, Personnel
Responsibility for planning, assembly, commissioning, operation,
maintenance, and dismounting lies with the plant operator.
The personnel must be appropriately trained and qualified in order to carry
out mounting, installation, commissioning, operation, maintenance, and
dismounting of the device. The trained and qualified personnel must have
read and understood the instruction manual.
Prior to using the product make yourself familiar with it. Read the
instruction manual carefully.
3. Reference to Further Documentation
Observe laws, standards, and directives applicable to the intended use
and the operating location.
For mining applications, observe laws, standards, and directives
applicable to the operating location.
The corresponding datasheets, manuals, declarations of conformity, EU-
type examination certificates, certificates, and control drawings if
applicable supplement this document. You can find this information under
www.pepperl-fuchs.com.
For specific device information such as the year of construction,
scan the QR code on the device. As an alternative, enter the serial number
in the serial number search at www.pepperl-fuchs.com.
If you use the device in safety-related applications, observe the
requirements for functional safety. You can find these requirements in the
functional safety documentation under www.pepperl-fuchs.com.
4. Intended Use
The device is only approved for appropriate and intended use. Ignoring
these instructions will void any warranty and absolve the manufacturer
from any liability.
The device is used in control and instrumentation technology
(C&I technology) for the galvanic isolation of signals such as 20 mA and
10 V standard signals or alternatively for adapting or standardizing signals.
The device has intrinsically safe circuits that are used for operating
intrinsically safe field devices in hazardous areas.
Use the device only within the specified ambient and operating conditions.
Only use the device stationary.
The device is an associated apparatus according to IEC/EN 60079-11.
The device is an electrical apparatus for hazardous areas of Zone 2.
The device may be installed in the non-hazardous area.
If you use the device in safety-related applications, observe the
information for safety function and safe state.
Rotation Speed Monitor
The device monitors for an overspeed or underspeed condition of a digital
signal (NAMUR sensor/ mechanical contact) from a explosion-hazardous
area by comparing the input frequency to the user programmed reference
frequency.
Switch Amplifier, Timer Relay
The device is a highly configurable timer that accepts a digital signal
(NAMUR sensor/mechanical contact) from a explosion-hazardous area
and is commonly used in applications requiring on-delay, off-delay, one-
shot, or pulse lengthening.
5. Improper Use
Protection of the personnel and the plant is not ensured if the device is not
used according to its intended use.
If circuits with type of protection Ex i are operated with non-intrinsically
safe circuits, they must no longer be used as circuits with type of
protection Ex i.
6. Mounting and Installation
Do not mount a damaged or polluted device.
The device is designed for mounting on a 35 mm DIN mounting rail
according to EN 60715.
Mount the device in a way that the device is protected against mechanical
hazard. Mount the device in a surrounding enclosure for example.
Ensure that the surrounding enclosure can only be opened with a tool.
The device fulfills a degree of protection IP20 according to IEC/EN 60529.
The device must be installed and operated only in a controlled
environment that ensures a pollution degree 2 (or better) according to
IEC/EN 60664-1.
If used in areas with higher pollution degree, the device needs to be
protected accordingly.
Do not mount the device in the dust hazardous area.
The device must be installed and operated only in an environment of
overvoltage category II (or better) according to IEC/EN 60664-1.
Supply the device with a power supply that meets the requirements for
safety extra-low voltage (SELV) or protective extra-low voltage (PELV).
If you are using the Power Rail, supply the Power Rail only via the
corresponding power feed modules or power supplies. Do not supply the
Power Rail via isolators.
Observe the installation instructions according to IEC/EN 60079-14.
If you install the device in safety-related applications, observe the
requirements for functional safety.
Requirements for Cables and Connection Lines
Observe the permissible core cross section of the conductor.
When using stranded conductors, crimp wire end ferrules on the
conductor ends.
Use only copper conductors.
Use only one conductor per terminal.
When installing the conductors the insulation must reach up to the
terminal.
Observe the tightening torque of the terminal screws.
If the voltage is greater than 50 V AC or 120 V DC, switch off the voltage
before connecting or disconnecting the device.
Only use cables and connection lines with a temperature range
appropriate to the application.
Requirements for Usage as Associated Apparatus
If circuits with type of protection Ex i are operated with non-intrinsically
safe circuits, they must no longer be used as circuits with type of
protection Ex i.
Observe the respective peak values of the field device and the associated
apparatus with regard to explosion protection when connecting intrinsically
safe field devices with intrinsically safe circuits of associated apparatus
(verification of intrinsic safety). Also observe IEC/EN 60079-14 and
IEC/EN 60079-25.
Intrinsically safe circuits of associated apparatus can be led into
hazardous areas. Observe the compliance of the separation distances to
all non-intrinsically safe circuits according to IEC/EN 60079-14.
Observe the compliance of the separation distances between two
adjacent intrinsically safe circuits according to IEC/EN 60079-14.
Requirements for Equipment Protection Level Gc
The device must be installed and operated only in surrounding enclosures
that
lcomply with the requirements for surrounding enclosures according to
IEC/EN 60079-0,
lare rated with the degree of protection IP54 according to
IEC/EN 60529.
Connection or disconnection of energized non-intrinsically safe circuits is
only permitted in the absence of a potentially explosive atmosphere.
Provide a transient protection. Ensure that the peak value of the transient
protection does not exceed 140 % of the rated voltage.
DOCT-8419 / 2022-09 1 / 2
7. Operation, Maintenance, Repair
If you operate the device in safety-related applications, observe the
requirements for functional safety. In case of operating in low demand
mode, plan appropriate intervals for the proof test.
If the voltage is greater than 50 V AC or 120 V DC, switch off the voltage
before connecting or disconnecting the device.
Do not use a damaged or polluted device.
Do not repair, modify, or manipulate the device.
If there is a defect, always replace the device with an original device.
Requirements for Equipment Protection Level Gc
Connection or disconnection of energized non-intrinsically safe circuits is
only permitted in the absence of a potentially explosive atmosphere.
Only use operating elements in the absence of a potentially explosive
atmosphere.
8. Delivery, Transport, Disposal
Check the packaging and contents for damage.
Check if you have received every item and if the items received are the
ones you ordered.
Always store and transport the device in the original packaging.
Store the device in a clean and dry environment. The permitted ambient
conditions must be considered, see datasheet.
The device, built-in components, packaging, and any batteries contained
within must be disposed in compliance with the applicable laws and
guidelines of the respective country.
DOCT-8419 / 2022-09 2 / 2