
2107137-20 -EN FR26 GLO 305 Printed in Germany
SPECIFICATIONS
Input
Nominal voltage 24 Vdc (-10 %, +10 %)
Nominal consumption dc: 1,5 W
Output
Contacts 4 NO, 1 NC (plus 1 NC for External Device Monitoring loop)
Contact type Safety relay, positive-guided
Response time Max. 15 ms (delay on de-energisation)
Delay on energisation Typ. 25 ms
Switching Capability Power factor = 1 with resistive load
Current Range (min. to max.) 10 mA to 5 A
Voltage Range (min. to max.) 0,1 to 250 Vac
Switching capability per
EN 60947-5-1
AC15: NO contact: 3 A/230 Vac, NC contact: 2 A/250 Vac
DC13: NO contact, NC contact: 8 A / 24 Vdc
Power factor = 1 at 230 Vac (see figure 1, note 1)
current operations current operations
0,5 A 5 500 000 2 A 1 000 000
Typical Electrical Life Expectancy
1 A 2 000 000 5 A 250 000
Limitation Factor F (see figure 2, note 2)
cos ϕF cos
ϕ
F
0,3 0,45 0,7 0,85
Typical Power Factor (cos ϕ)
0,5 0,7 1 1
Operating frequency 1200 operating cycles/h
Fuse rating 6 A time delayed (max.)
Mechanical life 20 000 000 operating cycles
General
Temperature range -15 °C to + 55 °C (5 °F to 131 °F) at 90 % humidity (max.)
Sealing Housing IP 40; Terminals IP 20
Housing material Thermoplastic
Vibration resistance
(IEC/EN 60 068-2-6)
Amplitude 0,35 mm; Frequency 10 to 55 Hz
Wire connection Solid wire: 1 x 4 mm2[12 AWG] or 2 x 2,5 mm2[14 AWG]
Stranded wire with sleeve: 1 x 2,5 mm2[14 AWG] or 2 x 1,5 mm2[16 AWG]
Wire/conductor attachment M3.5 screw terminals
Mounting Quick install rail mounting IEC/EN 60715 (width: 35 mm (1.38 in))
Weight 205 g (0.45 lb)
NOTE 1: Install arc suppressors
across load to avoid module contact
arcing and ensure specified contact life
expectancy.
NOTE 2: Total operations = operations
(power factor 1) x limitation factor F.
Example:
U = 230 Vac, I = 1 A,
power factor cos ϕ= 0,5
Switching power P = U x I = 230 VA
Contact life (cos ϕ= 1, P = 230 VA) =
2 000 000 operations (see Figure 1)
Limitation factor F (cos ϕ= 0,5) = 0,7
(see Figure 2)
Contact life (cos ϕ= 0,5, P = 230 VA) =
F x contact life (cos ϕ= , P= 230 VA) =
2 000 000 x 0,7 = 1 400 000 operations.
FIGURE 1. TYPICAL CONTACT
LIFE FOR 100 % RESISTIVE LOAD
(power factor cos ϕ= 1, note 1)
10
7
5
3
2
7
70,5 1,0 1,5 2,0
5
Operations
Switching power [kVA]
3
2
7
10
6
10
5
FIGURE 2. LIMITATION FACTOR FOR
INDUCTIVE LOADS
(power factor cos ϕ< 1, note 2)
Limitation factor F
Power factor