Intelligent Building Solutions CAP 2020 DR H User manual

Installation Manual
CAP 2020 DR H
ACCESS CONTROL UNIT
(for hotel anage ent syste s)
●Proxi ity card based
●DIN-rail ounting
CIB-tech

I n t r o d u c t i o n
The CAP 2020 DR H is a proximity card based access control device, with hotel room economizer unction,
part o the CIB-tech automation system.
The unit can control the entry in a hotel room. It accepts up to 1024 users and provides entry via the use o
proximity cards. It can control the power supplied to the room, based on the state o the room's proximity
card holder.
Additional Equip ent Required
1. Functional CIB-tech syste
A minimal number o essential CIB-tech components to make a unctional CIB-tech system1.
2. Proxi ity card and/or PIN code reader with bell button, for entry request
A proximity card reader with a 26-bit Wiegand-type output, urther re erred to as “Reader A”2.
NOTE: The proximity card reader must supply the bell button event in Wiegand data ormat.
3. Proxi ity card holder
Proximity card holder with built in proximity card reader (ex IBS product RFE 10 F), or any simple,
contact based card holder with voltage ree contacts2, urther re erred to as “Smart card holder” or
“Simple card holder”.
4. Open door sensor (optional)
Normally open or normally closed type with voltage ree contacts2.
5. Electric door lock
Fail sa e (power to lock) or ail secure (power to open) strike lock/door bolt/magnetic lock2.
6. Power supply for electric door lock
Re er to the electric door lock's characteristics to choose a suitable power supply. A power supply
with battery backup is recommended.
7. Circuit breaker
Miniature circuit breaker (MCB) or DIN-Rail mountable use must be used or over-current protection.
T e c h n i c a l S p e c i f i c a t i o n s
Electrical characteristics
●Power Supply
The CAP 2020 DR H unctions as a node in a CIB-tech system, being powered rom the CIB-tech
system's power supply via the CIB-tech connectors.
○Operating voltage range: 20 to 28V DC (nominal 24V DC)
○Supply current
■Standby current (without reader/card holder): 22mA
■Maximum current (without reader/card holder): 50mA
■Typical standby current (with reader and card holder): 110mA
■Absolute maximum current (with reader and card holder): 300mA
●Power output
The CAP 2020 DR H can provide power to the proximity card reader and card holder.
○Output voltage: 12V DC
1 See “CIB-tech installation manual” for details.
2 See “Recommended equipment to be used with CIB-tech” for details
CAP 2020 DR H ©2009 - Intelligent Building Solutions 1

○Maximum output current: 2 x 170mA
●Relay output (for electric door lock)
I an electric door lock with a DC power supply is used, an external suppressor diode must be used3.
○Rated voltage: 24V AC/DC
○Rated current: 2A
●Relay output (for roo power)
○Rated AC voltage: 250V AC
○Rated current: 16A
●Signal Input
○Wiegand data input:
■supported input voltage levels: 0 - 5V
■input impedance: 1KOhm
○Open door sensor: N.O. or N.C. with voltage ree contacts
○Contact based card holder: N.O. with voltage ree contacts
●Signal Output
○External LED control:
■output voltage levels: 0 - 5V
■output current: 15mA
Mechanical characteristics
The CAP 2020 DR H has a standard 3-module wide enclosure or M36 type DIN-Rail
●Dimensions: 96mm W x 52mm L x 60mm D
●Weight: 130g
Environ ental characteristics
●Operating temperature: 0ºC to 65ºC
●Storage temperature: -10ºC to 70ºC
K e y F e a t u r e s
●Programmable via the CIB-tech system with dedicated so tware
●Controls unidirectional access through one door
●Provides access or up to 1024 users
●Users may be members o one o up to 30 groups with di erent access rights, based on a weekly
schedule. Groups have individual access right expiration dates
●Controls the power supply or one hotel room.
●Room power is automatically enabled when a valid entry request is detected.
●Programmable “keep room power on” time, a ter card is removed rom the card holder.
●Support or Simple card holder (any card may be placed in the holder and the room will be powered
on) and Smart card holder (the room will be powered on only i a valid proximity card is placed in the
RFE 10 F).
●Support or an open-door sensor input or detecting actual door openings.
●Internal battery powered real-time clock. Clock keeps running in case o power ailure
●Internally stored 1024-entry access log with time stamps
●Internally stored 1024-entry open door event log with time stamps
IBS product PS 121 D is a dedicated power supply for door locks: 12V AC and DC output, internal suppressor
diode. Note that battery backup for door lock is not possible with it.
Please verify whether it is suitable for your door lock!
CAP 2020 DR H ©2009 - Intelligent Building Solutions 2

●Con igurable relay output; normal-open or normal-closed (in power-o state relay contacts are
always open)
●Two unctional modes: open door momentarily or toggle door state
●Con igurable keep-door-open time or the momentary-open mode
●Relay outputs are remotely controllable via the CIB-tech system
●Internal bi-color LED indicating the state o the door lock (green: closed / red: open)
●Support or two external LEDs ( or reader A and and card holder) indicating a valid proximity card;
I n s t a l l a t i o n
The CAP 2020 DR H is meant to be installed on a standard M36 type DIN-Rail.
Part description
●Bus connectors:
○4P4C modular jack connectors or CIB-tech connection1
●Sys button:
○pushbutton or CIB-tech system con iguration
●EOL ju per:
○CIB-tech system's End O Line jumper1
●LED:
○indicator LED or door lock state (green : closed / red : open)
●DIN-rail release:
○lever or removing the device rom the M36 DIN-Rail
●Low ter inal block: terminals or connecting external devices
1. Smart card holder – LED control
2. Smart card holder – Wiegand data 1
3. Smart card holder – Wiegand data 0 / Simple card holder N.O. contact
4. Smart card holder – DC power supply +12V
5. Smart card holder – DC power supply ground / Simple card holder common contact
6. Reader A – LED control;
7. Reader A – Wiegand data 1
8. Reader A – Wiegand data 0
9. Reader A – DC power supply +12V
10. Reader A – DC power supply ground
11. Open-door sensor input
12. Relay contact 1 or electronic door lock
13. Relay contact 2 or electronic door lock
●High ter inal block: terminals or connecting external door bell
H5. Relay contact 1 or room power
H6. Relay contact 2 or room power
1 See “CIB-tech installation manual” for details.
CAP 2020 DR H ©2009 - Intelligent Building Solutions 3

Wiring diagra s
Connection to CIB-tech syste :
Use the CAP 2020 DR H device's two 4P4C modular jack connectors to connect it to the CIB-tech systems
(chain like) bus. Do not orget to remove the EOL jumper i the device is not the last element o the chain1
1 See “CIB-tech installation manual” for details.
CAP 2020 DR H ©2009 - Intelligent Building Solutions 4
0v DC
24v DC
BUS-L
BUS-H
0v DC
24v DC
BUS-L
BUS-H
Sys button
EOL jumper
Bus connectors
CAP 2020 DR H
LED
Bus connectors
EOL jumper
Low terminal block
Din-rail release lever
1 1312111098765432
Sys button
H6H3 H4H2H1 H5 H7 H8 H9
High terminal block
1 1312111098765432
Low terminal block
High terminal block
H6H3 H4H2H1 H5 H7 H8 H9

Connecting the input devices
Connection example or proximity card reader and Smart card holder:
Connection example or proximity card reader and Simple card holder:
CAP 2020 DR H ©2009 - Intelligent Building Solutions 5
CAP 2020 DR H
LED
D1
D0
+12V
GND
Reader A
LED
D1
D0
+12V
GND
Smart
card
holder
Open door sensor
(optional)
CAP 2020 DR H
LED
D1
D0
+12V
GND
Reader A
Open door sensor
(optional)
Simple
card
holder
Common N.O.

NOTE: Some proximity card readers don't have a LED control input. For these readers the LED control
output o the CAP 2020 DR H is not connected.
Some proximity card readers have auxiliary inputs and outputs (ex. tamper, auxiliary led). These auxiliary
inputs and outputs can not be connected to the CAP 2020 DR H.
Connecting the electronic door lock
Connection example or AC-type electronic door lock:
Connection example or DC-type electronic door lock:
NOTE: An external suppressor diode (ex. 1N4001) is required.
CAP 2020 DR H ©2009 - Intelligent Building Solutions 6
CAP 2020 DR H
Electronic door lock
( ail sa e or ail secure)
type 12/24V AC
Line
transfor er
12/24V AC 230V AC
CAP 2020 DR H
Electronic door lock
( ail sa e or ail secure)
type 12/24V DC
DC power
supply
12/24V DC 230V AC
+
-
Suppressor diode
-
+

Connection example or DC-type electronic door lock and PS1213D, dedicated power supply :
CAP 2020 DR H ©2009 - Intelligent Building Solutions 7
CAP 2020 DR H
Electronic door lock
( ail sa e or ail secure)
type 12V DC
230V AC
PS 1213 D
1 765432
8 14131211109
- +

Connecting the roo power control
NOTE: A max. 16A Miniature Circuit Breaker (MCB) or max. 16A use must be connected in series with the
CAP 2020 DR H's room power relay.
Document Version 1.0
Technical Support:
http://www.ibs-smarthouse.com/
All trademarks used in this document are properties o their respective owners.
The manu acturer reserves the right to change the technical eatures o this product without prior notice.
CAP 2020 DR H ©2009 - Intelligent Building Solutions 8
CAP 2020 DR H
230V AC
MCB
16A
230V~
N L
N L
Room equipment
and connectors
Table of contents
Other Intelligent Building Solutions IP Access Controllers manuals
Popular IP Access Controllers manuals by other brands

Dahua
Dahua ASR2101H-D user manual

Pongee Industries
Pongee Industries Pegasus PC-1074 user manual

Rosslare
Rosslare AC-425 Hardware installation and user's guide

Competition Electronics
Competition Electronics DH16A-12DT instruction manual

Sebury
Sebury sTouch2 instruction manual

fadini
fadini ZERO.SAPE manual

Roger
Roger OSR88M-IO operating manual

Alcad
Alcad Linea 201 Technical manual

FRIEDHELM LOH
FRIEDHELM LOH Rittal CMC III DK 7030.202 Installation and Short User Guide

Soyal
Soyal AR-721H manual

Roger
Roger MCT86M-IO-HR-CH operating manual

Gianni Industries
Gianni Industries GEM Easiprox+ Series installation guide