manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. Intermatic
  6. •
  7. Accessories
  8. •
  9. Intermatic IOS-CMP-LV Quick guide

Intermatic IOS-CMP-LV Quick guide

Low Voltage Occupancy Sensor
Input: +24VDC
Model#:
For Indoor Use Only
IOS-CMP-LV
DESCRIPTION:
The IOS-CMP-LV 360° Passive Infrared (PIR) Low Voltage Occupancy Sensors control lighting systems
based on occupancy and ambient light levels. When movement is detected, the sensor turns the lights
ON. If no movement is detected for a user-specified or Autoset time of 15 seconds to 30 minutes, the
lights are turned OFF. The occupancy sensor provides a 360° coverage pattern, up to 1200 square feet.
MOUNTING THE SENSOR
NOTE: A junction box and Phillips screwdriver are needed to complete this procedure.
1. Make sure power is turned off at the main disconnect.
2. Remove the screws on the occupancy sensor cover and remove the cover from the sensor.
3. Observe these guidelines when mounting the sensor:
• TheoccupancycoverageareamaybemoreorlessthanthesensingdistancesshowninFigure1
due to potential coverage area obstacles, such as furniture or partitions.
• Placethesensor4to6feetawayfromairsupplyductstopreventfalseactivations.
• Ifyoumountthesensoroutsideof8to11feetfromtheoor,itaffectsthecoveragepattern.
• Decreasingthemountingheightdecreasesthesensorrangeandincreasesthesensitivityto
 smallermotions.Mountingthesensoratheightsmorethan12to14feetreducessensitivity
• Eachoccupantshouldbeabletoclearlyviewthesensortoguaranteenoobstructioninthearea
• Avoidplacingthesensordirectlyinlinewithanopendoorthroughwhichithasaclearviewout.
This may cause the sensor to detect people walking by the door.
• Toobtaincompletecoverageinlargeareas,installmultiplesensorstocreateanoverlapwitheach
adjacent sensor’s coverage area.
4.PunchknockoutonthejunctionboxandinserttheIOS-PP24powerpacknippleintotheknockout.
5. Pull the low voltage wires from the power pack into the junction box, through the conduit knockout.
6. Connect the low voltage wires from the power pack to the appropriate terminals on the occupancy
sensor. See table below for wire designations. Refer to FIgure 2.
Wire from power pack To Terminal on Occupancy Sensor
Redwire(+24VDC) +24 VDC terminal
Black wire (Common) Common terminal
Blue wire Control Out terminal
IOS-CMP-LV INSTALLATION
1. If you want to connect multiple single loads for the sensor to control, connect the blue wire from the
power pack to the Control Out terminals on the sensor.
2. If you want to add a manual switch to the above application, connect a wire from one side of the
switch to the common terminal on sensor and connect another wire from the other side of the switch
to the Manual ON terminal on sensor.
3. Loosen the mounting screws attached to the junction box.
4.Alignthesensorinthejunctionboxsothatthemountingscrewsintheboxmatchthekeyholeson
the sensor’s rear housing.
5. Push the sensor into the junction box and align the mounting screws on the junction box with the
keyhole slots on the sensor so that the screws are seated in the keyhole slots. Tighten mounting
screws.
ADJUST THE LIGHT LEVEL
The Light Level feature enables the user to adjust the level of light needed to be detected before
the sensor turns lighting ON. Remove the cover from the sensor and adjust the lighting from
the light level dial on the sensor (see Figure 5). You can set the dial anywhere between + or – to
obtain the optimal brightness configuration for the room (see Figure 3).
SENSOR ADJUSTMENT
Follow this procedure to verify the sensor coverage and customize the settings.
1. Remove the screws on the front cover and remove the cover.
2. Make sure all the furniture in the sensing area is installed, the lighting circuits are turned on and the
HVAC systems are in the Override position.
3. IfthereisaVAVsystem,setittothehighestairow.
360˚ Passive Infrared
Low Voltage Occupancy Sensor
With Light Level Feature
MODEL: IOS-CMP-LV
Specifications:
Voltage-24VDC
Current Consumption - 9mA
PowerSupply-IOS-PP24PowerPacks
Adjustable Light Level - 10FC-150FC
AdjustableTimeDelay-15sec.-30min(DIPswitch)
Walk-Through Mode - 3 minutes if no activity after 30 sec.
TestMode-15sec.uponinitialpower-uporDIPswitchreset
PIR Coverage:
SensitivityAdjustment-AutomaticorLow(DIPswitch)
Coverage - Up to 1200 ft2
Figure 3
Figure 2
Figure 4
Figure 5
IOS-CMP-LV
terminals
Wiring
Common
+24VDC
Manual ON
Low Voltage Occupancy Sensor
Input: +24VDC
Model#:
For Indoor Use Only
IOS-CMP-LV
Control Out
Common
+24VDC
Manual ON
Control Out
- +
Light
- +
Light
- +
Light
- +
Light
- +
Light
- +
Light
Risk of Fire, Electrical Shock or Personal Injury
• TurnOFFpoweratcircuitbreakerorfuseandtestthatthepowerisOFFbeforewiring.
 • Tobeinstalledand/orusedinaccordancewithappropriateelectricalcodesandregulations.
 • Ifyouarenotsureaboutanypartoftheseinstructions,consultaqualiedelectrician.
 • Usethisdeviceonlywithcopperorcoppercladwire.
 • INDOORUSEONLY
WARNING
44 ft
13.4m
8 ft
tf22tf22 tf31tf31 7 ft 7 ft3 ft 0 3 ft
Typical
desk-top
level
Figure 1
J-Box Mount
Front Cover
Rear Housing
Wire
Screws
4" Octagonal
box 2-1/2"
Deep mounting
Drop
Ceiling
PIR lens
PIR Activity LED(Red)
Light level Adjustment
Double gang mudring
mounting holes
DIP switches
Keyhole slots
Keyhole slots(for mounting to
4" octagonal box)
Load LED(Green)
Buzzer
(for mounting to 4" octagonal box)
INSTALLATION AND CONFIGURATION INSTRUCTIONS
ADJUSTING DIP SWITCH SETTINGS
Theoccupancysensorfeatures9DIPswitches.Eachsettingcanbesettoanuppositionordownpositionthat
congurestheDIPSwitchsettingtoaspeciedrequirement.FollowthisproceduretoadjusttheDIPswitchsettings.
1. AdjustthesensitivitylevelDIPSwitch(1).TheUppositionsetsthesensitivityto100%,whilethedownposition
 adjuststhesensitivitylevelto50%.
DIP SWITCH 1 - SENSITIVITY LEVEL SETTINGS
 50% Downposition
 100% UpPositions
2. AdjustthetimedelayDIPswitches(2-4).Refertothetableforalistofthetimedelayoptions.
NOTE: After the sensor detects no motion in the coverage area, it will delay a user-configured amount of time before turning lights off. See the table before turning
lights off. See the table below to determine how to set the desired time delay for the sensor.
TIME DELAY SETTINGS
 TimeDelay 2SwitchSetting 3SwitchSetting 4SwitchSetting
 15Sec/Autoset DownPosition DownPosition DownPosition
 30Seconds DownPosition DownPosition UpPosition
 5Minutes DownPosition UpPosition DownPosition
 10Minutes DownPosition UpPosition UpPosition
 15Minutes UpPosition DownPosition DownPosition
 20Minutes UpPosition DownPosition UpPosition
 25Minutes UpPosition UpPosition DownPosition
30 Minutes Up Position Up Position Up Position
3. AdjustDipswitchsettings5through9.Seetable2belowforadescriptionofeachsetting.
 NOTE:ForDIPswitchsettings5through9,theuppositionenablesthesetting,whilethedownpositiondisablesthesetting.
 DIP
 SWITCH  EnabletheSetting.Set DisabletheSetting.Set
 NUMBER DESCRIPTION DIPSwitchTo DIPSwitchTo
5 Walk Through -Turnsthelightsoffforthreeminutesaftertheareaisinitiallyoccupied. UpPosition DownPosition
If no motion is detected.
6 Vacancy-TurnthisDIPswitchtoONifyouhaveamomentaryswitch.Thisenablesoverrides. UpPosition DownPosition
7 Audible Alert-Analarm(soundslikeatick)thatindicatesthatthetimedelayhasexpired. UpPosition DownPosition
 8 Visible Alert-Analarm(loadLEDashesonce)toindicatethetimedelayhasexpired. UpPosition DownPosition
9 Hold ON-SetthistoONtooverrideallsensorfunctions UpPosition DownPosition
4. Installthefrontonthesensorandsecurewiththescrews.
TESTING THE OCCUPANCY SENSORS
1. EnsurethePIRActivityisenabledRedLEDashes,HoldONmodeisOFF(DIP9switchOFF)andPIRSensitivityissettoMAX(DIPswitch1ON).
2. MakesureDIPSwitches2,3,and4aresettothedown(disable)positionsotheTimeDelayissetforTESTMODEwiththe15seconds/AUTOSETsetting.
3. Ensure the Light Level is the default (maximum).
4. Donotmovesothesensordoesn’tdetectthemovement.ThegreenLEDandLoadareONandthelightsshouldturnoffafter15seconds.
5. Move about the coverage area. The lights will illuminate.
6. Whentestingandadjustmentiscomplete,resetDIPSwitchesandLightLeveltothedesiredsettingsandreplacethecoveronthesensor.
NOTE:IfyouneedtoinvoketheTestModeandtheDIPswitchesarealreadysetfor15seconds/Autoset,toggleDIPswitch#3ONthebacktotheOFFposition.This 
 providesa5-minutetestperiod.Duringthetestperiod,theTimeDelayisonly15seconds.
TROUBLESHOOTING
ThePIRactivityLEDdoesnotashproperly, The warm-up period has not been completed
Make sure the circuit breaker is on
    SetthePIRsensitivitytoMax/Autoset(DIPswitch1ON)
Check all sensor and power pack connections
    Checkfor24Vinputtothesensor.If24Vispresent,replacethesensor.If24Visnotpresent,checkifthehigh
voltage is present to power pack. If it is, replace the power pack.
ThereisimproperPIRactivity,LEDashes MakesurethelightleveladjustmentissetproperlybycoveringthePIRlensandPIRactivityLEDtoverifyiflights
turn on. If lights still turn on, adjust the light level.
Check all sensor and power pack wire connections.
    Whilethesensorisactivated,checkfor24VDCatthebluewireconnectionatthesensor.Ifthereisnovoltage,
replace the sensor. If voltage is present, replace the power pack.
Lights do not turn on automatically Make sure the sensor is not experiencing activations from outside the controlled area
Check all sensor and power pack wire connections
    Disconnectthebluewire.Iflightsdonotturnoff,replacepowerpack.Iflightsturnoff,checkthesensor.
Turn the sensitivity and time delay to minimum and allow the sensor to time out.
 Thesensorisactivatingwithoutdetectingmovement SettheDIPswitch1toOFF
Relocate the sensor.
158--01282
1234567
8
9
ON
12346
79
5
Sensitivity
Time
Delay
Walk-Through
Vacancy
Audible Alert
Visible Alert
HOLD ON
8
Up Position
Down Position
DIP SWITCH
DIP Switch
Settings
Settings Chart
LIMITED TWO YEAR WARRANTY
If within the warranty period specified, this product fails due to a defect in material or workmanship, Intermatic Incorporated will repair or replace it, at its sole option, free of charge. This warranty is extended to the original
purchaser only and is not transferable. This warranty does not apply to: (a) damage to units caused by accident, dropping or abuse in handling, acts of God or any negligent use; (b) units which have been subject to
unauthorized repair, opened, taken apart or otherwise modified; (c) units not used in accordance with instructions; (d) damages exceeding the cost of the product; (e) sealed lamps and/or lamp bulbs, LED’s and
batteries; (f) the finish on any portion of the product, such as surface and/or weathering, as this is considered normal wear and tear; (g) transit damage, initial installation costs, removal costs, or reinstallation costs.
INTERMATIC INCORPORATED WILL NOT BE LIABLE FOR INCIDENTAL OR CONSEQUENTIAL DAMAGES. SOME STATES DO NOT ALLOW THE EXCLUSION OR LIMITATION OF INCIDENTAL OR
CONSEQUENTIAL DAMAGES, SO THE ABOVE LIMITATION OR EXCLUSION MAY NOT APPLY TO YOU. THIS WARRANTY IS IN LIEU OF ALL OTHER EXPRESS OR IMPLIED WARRANTIES. ALL IMPLIED
WARRANTIES, INCLUDING THE WARRANTY OF MERCHANTABILITY AND THE WARRANTY OF FITNESS FOR A PARTICULAR PURPOSE, ARE HEREBY MODIFIED TO EXIST ONLY AS CONTAINED IN THIS
LIMITED WARRANTY, AND SHALL BE OF THE SAME DURATION AS THE WARRANTY PERIOD STATED ABOVE. SOME STATES DO NOT ALLOW LIMITATIONS ON THE DURATION OF AN IMPLIED
WARRANTY, SO THE ABOVE LIMITATION MAY NOT APPLY TO YOU.
This warranty service is available by either (a) returning the product to the dealer from whom the unit was purchased, or (b) completing a warranty claim on line at www.intermatic.com. This warranty is made by:
Intermatic Incorporated, Customer Service 7777 Winn Rd. Spring Grove, Illinois 60081-9698. For warranty service go to: http://www.intermatic.com or call 815-675-7000.

Other Intermatic Accessories manuals

Intermatic HA04 Manual

Intermatic

Intermatic HA04 Manual

Intermatic AG2403C User manual

Intermatic

Intermatic AG2403C User manual

Intermatic HA03 Manual

Intermatic

Intermatic HA03 Manual

Intermatic AG2401 User manual

Intermatic

Intermatic AG2401 User manual

Intermatic IG250LA User manual

Intermatic

Intermatic IG250LA User manual

Intermatic HB61R Manual

Intermatic

Intermatic HB61R Manual

Intermatic AG4801 User manual

Intermatic

Intermatic AG4801 User manual

Intermatic HA05 Manual

Intermatic

Intermatic HA05 Manual

Intermatic inTouch CA3500 User manual

Intermatic

Intermatic inTouch CA3500 User manual

Intermatic AL1150 User manual

Intermatic

Intermatic AL1150 User manual

Intermatic IOS-CMP-U Quick guide

Intermatic

Intermatic IOS-CMP-U Quick guide

Intermatic HA02 Manual

Intermatic

Intermatic HA02 Manual

Intermatic AG6503C User manual

Intermatic

Intermatic AG6503C User manual

Intermatic AG2083C User manual

Intermatic

Intermatic AG2083C User manual

Intermatic K4000 series Instruction Manual

Intermatic

Intermatic K4000 series Instruction Manual

Intermatic AG4803C User manual

Intermatic

Intermatic AG4803C User manual

Intermatic InTouch CA9000 User manual

Intermatic

Intermatic InTouch CA9000 User manual

Intermatic EM14PS User manual

Intermatic

Intermatic EM14PS User manual

Intermatic IOS-CMP-DT-U Quick guide

Intermatic

Intermatic IOS-CMP-DT-U Quick guide

Intermatic IOS-CMP-U Quick guide

Intermatic

Intermatic IOS-CMP-U Quick guide

Intermatic FL300MSW User manual

Intermatic

Intermatic FL300MSW User manual

Popular Accessories manuals by other brands

Grandview CB-MRC instruction manual

Grandview

Grandview CB-MRC instruction manual

Aromateca bloom user manual

Aromateca

Aromateca bloom user manual

Daikin EKRSCA1 installation manual

Daikin

Daikin EKRSCA1 installation manual

dtp Winco PSS60/A Installation and operation manual

dtp

dtp Winco PSS60/A Installation and operation manual

Alula Home Disaster RE119 quick start guide

Alula

Alula Home Disaster RE119 quick start guide

texet PowerPack Series manual

texet

texet PowerPack Series manual

Okoia OB200 instruction manual

Okoia

Okoia OB200 instruction manual

PASCO PAS Port PS-2186 instruction manual

PASCO

PASCO PAS Port PS-2186 instruction manual

Toshiba TWBM001C-NB user manual

Toshiba

Toshiba TWBM001C-NB user manual

Kellfri 13-VT275 operating instructions

Kellfri

Kellfri 13-VT275 operating instructions

PCB Piezotronics IMI SENSORS TO640B32 Installation and operating manual

PCB Piezotronics

PCB Piezotronics IMI SENSORS TO640B32 Installation and operating manual

Leuze IGSU 14E instruction manual

Leuze

Leuze IGSU 14E instruction manual

Banner MINI-BEAM MINI-BEAM Expert brochure

Banner

Banner MINI-BEAM MINI-BEAM Expert brochure

Hobo RXW-THC Series manual

Hobo

Hobo RXW-THC Series manual

MIXX CHARGE FLX Charge quick start guide

MIXX CHARGE

MIXX CHARGE FLX Charge quick start guide

Anker EUFY T8910 user manual

Anker

Anker EUFY T8910 user manual

eufy Security T8210 quick start guide

eufy Security

eufy Security T8210 quick start guide

Velleman MP1800 quick start guide

Velleman

Velleman MP1800 quick start guide

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.