Isimet DLA Series Installation manual

Application:
The DLA Series Style 3 Controller is a multiple circuit controller used to operate remotely located 12-vdc latching
solenoids for domestic water services to restrooms in multiple Patient Rooms within a Patient Care Facility.
This unit is provided with ISIMET latching circuit boards that permit a 24-vac signal to latch the solenoids ON and OFF,
controlling the water supply to the restroom facility.
ISIMET DLA Controller
Patient Care Facility
Multiple Room Configuration
Style 3 W/ Ver 4.41 pcb & Pulse Relay pcb(s)
Installation, Operations, Start-up and
Maintenance Instructions
Table of Contents:
Page
Warranty………………………………………………….. 2
General Product Information……………………………… 3
Enclosure Specifications and Dimensions………………… 4
Model Number……………………………………………. 4
Illustration and Parts List………………………………….. 5
Mounting Instructions (Flush)….…………………………. 6
Mounting Instructions (Surface Mount)..…………………. 6
Installing the Electrical Conduit…………………………... 7
Wiring the Unit……………………………………………. 7
Mounting the Door Panel..………………………………… 8
Connecting the Door Cable………………………………… 8
Circuit Output Configurations………………………….…. 9
Monitoring Configurations………………………….…….. 10
Wiring Configurations.. …………………………………… 10
Operation of Unit………………………………………….. 11
Equipment Maintenance…………………………………… 11
March 2014
DOC# 18015

2
ISIMET DLA Series Utility Controller
Installation, Maintenance, Operations, and Startup Instructions
Copyright © 2014 ISIMET, LLC.
All rights reserved.
Patent 6,757,589 B1
6,990,393 B2
This document is copyrighted. This document may not, in whole or part, be copied, duplicated, reproduced,
translated, electronically stored, or reduced to machine readable form without prior written consent from ISIMET,
LLC.
Although the material contained herein has been carefully reviewed, ISIMET, LLC does not warrant it to be free of
errors or omissions. ISIMET reserves the right to make corrections, updates, revisions, or changes to the
information contained herein.
Warranty:
ISIMET will repair or replace any defective parts or workmanship of this product for a period of one year
from date of installation. The P.C. Board has a two year limited warranty. Damage caused by incorrect
installation or improper usage is not warranted. Failure to follow recommended installation, operation,
and/or maintenance procedures listed in this manual may void product warranty. Recovery rights shall be
limited to the total sum of the amounts paid for the product by the purchaser.
EXTENDED WARRANTY:
ISIMET will extend the warranty of this product to a period of two years from date of installation when
installation complies with all start up and routine maintenance procedures and Start up has been performed
by an authorized factory representative. Refer to Extended Warranty Policy.
Limits of Liability:
ISIMET's liability shall be limited to costs of repair or replacement parts. The DLA Controller is not
intended for usage other than those expressly described in this manual. ISIMET shall not be liable for
damage or injury caused by the improper use of the product.
ISIMET does not warrant against or assume liability for failure of operation or lack of notification to
secondary integrated monitoring systems. The system should be thoroughly tested and adjustments made at
time of initial operation. Periodic testing should be conducted by the user to assure that all components
function and operate according to specifications.
Care should be taken in the installation of this product. ISIMET shall not be liable for damage or injury
caused from the improper installation of the product.
Warranty is Subject to Compliance with Specific Installation Requirements.
DISCLAIMER OF IMPLIED WARRANTY:
THERE ARE NO WARRANTIES THAT EXTEND BEYOND THE DESCRIPTION HEREIN. SELLER
DISCLAIMS ANY IMPLIED WARRANTY OF MERCHANTABILITY OF THE GOODS OR OF THE
FITNESS OF THE GOODS FOR ANY PURPOSE, AND BUYER AGREES THAT THE GOODS ARE
SOLD “AS IS.”
NOTE: Only qualified craftsmen licensed within the governing jurisdiction to perform the work associated
with this installation should install and/or service this equipment.

3
General Product Information
Construction
All electrical components are pre-assembled, wired, and mounted. The Electronic Controller is assembled within the Utility
Controller compartment.
Caution: Do not drop the assembly or expose it to the environment.
Assembly, Compliance and Registration Information
All DLA Controllers are assembled to permit limited field configurations of the operating system. Options requiring
additional instructions and/or assembly parts are shipped within the component package. Refer to Equipment Specifications
to verify that ALL components conform to these requirements.
The output circuits of the DLA Controller provide 12 VDC pulse control signals to solenoids for domestic water utilities.
ISIMET provides a full line of Companion Enclosures and fittings. It is recommended that these items be included in the
system design, but when the installer elects to provide these fitting from other sources compliance with Product
Specifications should be confirmed prior to installation.
Enclosed with this Manual is a separate registration form. The front of the form is for equipment warranty registration.
The back is a copy of the equipment start-up checklist. To ensure proper warranty of the product, it is important that you
complete both sides of the form and either mail or fax to ISIMET within 30 days of installation.
Pre-Installation Information
The DLA Controller is not provided with a protective cover for the enclosure opening if the door is to be removed for
protection during construction phases of the facility so that no debris enters the enclosure. Protection should in these cases
be field provided. A wrap protects each PCB. Care should be taken to assure that PCB covers are not removed until final
assembly and testing.
Locating and Positioning the DLA Controller
Prior to installation, verify ADA (Americans with Disabilities Act) dimensions and compliance requirements.
For best results: Mount the vertical center of the service switches on the Wall Panel to the ADA-required maximum height.
Trim Kit (Flush Mount only)
A Trim Kit is provided with flush mounted units, and is provided with separate installation instructions. Verify installation
requirements prior to installation of the unit. Store the Trim Kit in a protected location, out of the weather, until installation.
Upon Receipt of Product
Each DLA Controller is assembled specifically for an individual application.
All primary components have the same serial number.
Check components for damage. Notify ISIMET immediately of any damaged components.
Check package and product name plates to determine if all components were shipped correctly.
Store uninstalled components in a protected environment, out of the weather.

4
Warranty is Subject to Compliance with Specific Installation Requirements.
Enclosure Specifications and Dimensions:
The DLA Series Style 3 Enclosure thru 4 circuits is 16 X 14 X 6 plus 0.625” door flange, for units with 6 to 8 circuits the enclosure
is an 18 X18 X 6. Custom fabrications are available to provide greater than 8 circuits within a 24 X 24 X 6 enclosure. Flush Trim
adds 3.5 inches to both height and width Wall Surface dimensions. The NEMA 1 enclosures may be either surface or flush mounted.
Labeling on the DLA Controller door panel is customized to the specific purpose.
Styles
# LA
PCB
# Pulse
PCB
# Output
Circuits
MAX.
Switch
Fuse
Output
Rating
Transformer
Relay Rating
DLA -3
2
2
4 @ 24 vac
15 amp
4 amp @ 24 vac
4 amp @ 25
4 X 2 amp @ 24 vac
DLA -3
3
6
6 @ 24 vac
15 amp
6 amp @ 24 vac
2- 3 amp
6 X 2 amp @ 24 vac
DLA -3
4
8
8 @ 24 vac
20 amp
8 amp @ 24 vac
2-4 amp @ 25
8 X 2 amp @ 24 vac
Output fuse on PCB, FUSE 1 is Slow Blow. PCB circuit fuse, FUSE 3 is 500 mA Fast Acting

5
DLA Controller Illustrations and Parts Lists
DLA Controller Primary Components:
1 -
Electronic Controller PCB
2 - 24 VAC Transformer
3 -
Wiring Junction Cover
4 - Control Switch
5 - Upper hinge pin assembly
6 - Lower hinge pin assembly
7 - Recess Mounting Flanges (4) (See Figure 4)
8 - Surface Mounting Flanges (2) (See Figure 5)
9 - 8-32 Self-Starting Screws (See Figure 4)
10- Output Terminals
Fuse Specifications @ each pcb
Fuse 1 5 X 20m 2 Amp Slow Blow
PC Board (typical)
Fuse 3 2 AG .177” X .57” 500 mA PC Board
Figure 2 - DLA Controller
Figure 3 - Typical Door Panel
Switch layout depends upon the required number
of output circuits.
Four (4) shown W/ two (2) cables
Door Panel Primary Components:
11 - Service Switch ( 4 )
12 - Keyed Switch
13 - Panic Button
14 - Door Panel Keyed Lock
15 - Door Panel Plug See Fig. 9
16 - LEDs (8)
3
4
5
2
1
6
10
11
16
13
12
14
15

6
Installing the DLA Controller
CAUTION: Provided mounting hardware must be used.
There are two options for mounting the DLA Controller: Flush
Mounted and Surface Mounted. Note: Mounting instructions
for custom assemblies including circuits in excess of 12
outputs are provided with the unit separately.
Flush Mounted (Figure 4)
Prior to installation:
The Controller easily mounts between two wall studs
within a minimum 6” wall cavity for flush mounting. If
stud spacing is greater than that required for the mounting
of the controller, add studs to insure a secured mounting.
The studs should be facing to facilitate securing the
controller.
Predetermine wall finish so that the face lip of the
enclosure aligns flush with the finished wall surface.
To install:
1. Using the self-starting screws (13), mount the flanges at
each side and at the top and bottom of the enclosure.
2. Attach the enclosure to the wall studs with field-provided
sheet metal screws. (See Figure 4)
3. Level the Controller.
Notes:
The Door Panel, when mounted onto the Controller,
should protrude beyond the wall surface about ¼”. Care
should be taken at installation time to ensure that this
occurs.
A Flush Mounting Trim Flange is provided with each
flush mounted unit. Separate installation instructions and
hardware are included with this kit. Flush trim adds 3.5
inches to both Height and Width Wall Surface
dimensions.
It is the responsibility of the installer to verify finish wall
dimensions.
Surface Mounted
(Figure 5)
Prior to installation:
Wall finishes must be complete.
The wall cavity must have sufficient backing or support to
ensure a firm mounting of the controller to the wall surface.
To install:
1. Secure the surface mount flanges to the back of the
enclosure with the self-starting screws (13).
2. Use the field-provided screws to attach the enclosure by the
flanges to the wall surface.
3. Level the Controller.
Figure 4 - Flush Mounted
*For best Flush Mounting results, recess
face of enclosure’s lip ½” behind wall
finish
Clearance around Enclosure:
Care should be taken to allow ½” clearance
from wall framing and sheet-rock or other
wall surface material around the outer surface
of the unit to permit the trim to be properly
installed.
Figure 5 - Surface Mounted

7
Installing the Electrical Conduit at the DLA Controller
Several knock-out holes for connecting the conduits are located at the top and at each side of the DLA Controller.
Connect rigid conduit for the required 120 VAC electrical service at the top left or side opening as indicated in
Figure 6.
Connect conduit for integrated services such as “EMS” (Energy Management System) and building alarm at the
top of the enclosure.
Connect conduit for the controlled utility services to the upper right top or right side of the enclosure.
Important!
All local codes must be followed when connecting the conduit to the service panel.
Do not install wiring or cable for integrated systems, remote panic assemblies or other interface wiring within conduit for
either 24-vac control or 120-vac line voltage. Each wiring system should be housed in independent conduit and not
bundled with wiring for other systems.
Figure 6 –DLA Controller Knock-out Holes
NOTE: This Unit is provided with
an Output Terminal per pcb as shown
in Figure 2.
Panel holes for output circuits,
remote panic assemblies and other
integrations must be field provided.
Figure 7 - Junction Box
Wiring the DLA Controller
Important!
Verify that the electrical supply is disconnected prior to
connecting wiring to the Controller.
To wire the DLA Controller:
1. Remove the junction box cover from the panel
surface.
2. Make final connections to the 120 VAC electrical
service to wiring within the junction box. Verify that
line wiring (Black), neutral (White), and ground wire
(Green) are correctly connected. Minimum
recommended wire size is 14 AWG.
3. Replace the junction box cover before activating or
testing the unit.
Connect Conduit for
Electrical Service to
Top Knock-out Hole

8
Removing and Reinstalling the Door Panel
If the Door Panel is to be removed from the unit, refer to step by step instructions below.
In reverse order, perform steps 1 through 4 to remove the Door Panel. If the Panel is to be removed during the
construction phase, a field provided protective cover should be securely placed over the enclosure opening.
Installing Flush Door Trim
If the DLA Controller is Flush Mounted, a Trim Kit is provided separately. Refer to installation directions provided with
that component.
To install the Door Panel
Figure 8
To install the Door Panel on the Enclosure:
1. Position the door at 90° – 100° of enclosure.
2. Slide top hinge pin onto fixed hinge post at top of
door.
3. Slide lower hinge pin toward lower spring hinge
mechanism with hinge pin lever in retract position.
4. With lower hinge pin in position, turn hinge pin lever
outward and down, then turn inward to the extend lock
position.
Connecting the Door Cable to the PCB:
Units are provided with 9 pin sockets for connection of door
panel switches to the individual pcb. Units have wiring
harnesses from switches to individual PC boards labeled
accordingly.
Figure 9

9
Output Circuit Terminal
All DLA Controller should utilize ISIMET S-200 or S-220 Series General Service Brass Valves with 12 vdc coils.
These coils are polarized and must be connected correctly to the Output Terminal in order to function as intended.
Connect Supply Solenoids to the ‘ON’ w/Latch Terminals.
Make connections to ‘BLK’ and ‘WHT’ pins to match instructions provided with the solenoids that are similarly color coded.
Piping and wiring for solenoids should follow details provided with the solenoids.
Do not connect more that 2 ISIMET provided latching solenoids to the output Terminal.
NOTE: This image shows the
wiring for each LA PCB
arrangement. The quantity of
these boards will differ for
each unit.
Figure 10

10
•Connect rigid conduit for the required 120-vac electrical service.
•Connect conduit for the operating power to the upper left top of the enclosure at the junction box.
•Connect conduit for the operating power for the output to the upper right top of the enclosure.
Optional Input Control circuit
Alarm Input: 24-vac/vdc active OFF. Refer to jumper configuration chart above. Make connection of this optional
wiring at CON 4.
Optional Remote Panic Input Connection
An optional input from an ISIMET Remote Panic Assembly can be connected to the PCB at CON 4-a.
Optional Panic Output Terminal
A configurable Panic output is activated at CON 5. See configuration chart and location of this connector on Figure 11.
Important!
All local electrical codes must be followed when installing the unit and connecting the conduit to the service
panel and making wiring connections. Do not install wiring or cable for integrated systems, remote panic
assemblies or other interface wiring within conduit for either 24-vac control or 120-vac line voltage. Each wiring
system including outputs should be housed in independent conduit and not bundled with wiring for other
systems. Failure to comply with these wiring specifics may create transient voltage at the pc board and cause
system malfunction and/or failure.
CAUTION! Do not install the panel until all wall finishes are complete. Verify that the plug is configured
correctly. Incorrect insertion will prevent operation of unit.
WARNING!! Other pcb Jumper placements
Jumpers at JP 1, JP 4 and JP 5 are factory placed in order to configure the circuit board to specific functions for the
Controller. Removal and/or re-placement may cause the unit to malfunction.
Monitoring Circuit- JP3
Output Configuration Jumpers
@ Panic Output
1 jumper across center two posts
= dry-contact.
2 jumpers across each pair of posts
= 24-vac output
Figure 11

11
CAUTION:
ISIMET DOES NOT recommend that service to emergency and/or safety devices, such as emergency
showers and eyewashes, be controlled by the DLA Controller System or Solenoids. Such devices are
intended to operate independent of restrictive authority operation, as is the case with the design of this unit.
ISIMET makes available components for the monitoring of such safety devices. Please contact ISIMET
regarding any questions regarding this type of application.
Equipment Maintenance
The DLA Series Controller should have semi-annual inspections.
ISIMET recommends that you periodically conduct a brief test of the system to verify that the output
circuit performs as intended.
If examination of the unit indicates tampering, ISIMET recommends that you first review the
installation and wiring portions of this manual prior to placing the unit in service.
ISIMET recommends that piping systems be thoroughly flushed and cleaned and tested for leaks prior to
placing the system into use. Periodic testing of these solenoids will assure that the piping system
continues to function properly.
If you have any questions regarding the operation and maintenance of the DLA Controller, please contact
ISIMET or your local Service Representative.
The enclosure has a NEMA 1 rating. It is not intended for use in wet areas. Exercise caution to prevent
exposure of the interior compartment of the enclosure to moisture. If moisture is present within the
enclosure, ISIMET recommends that the control switch be turned OFF, power be disconnected from the unit
until the source of the moisture is determined, and all moisture is removed from the compartment.
The electronic controller (PCB) is sensitive to dust and other air-borne particles. Do not expose the interior
compartment of the enclosure to dust. During the semi-annual inspection, if dust or other material is present,
ISIMET recommends that you remove all foreign matter before operating the unit.
If the Unit fails to operate, ISIMET recommends that you check the power supply to the unit. With the
control switch in the ON position, LED 1 on each LA PCB should illuminate. If not, check the service
breaker and PCB fuses.
If the fuse is not damaged and the unit still does not function, contact ISIMET or your local Service
Representative.
Operation of the Unit
With the panel service switch ON, engage the Key-switch. The circuit will activate and the panel Green LED
will illuminate to indicate that the water services to the patient restroom are active. After turning a switch
OFF, it will be necessary to re-engage the Key-switch in order to reactivate the services. The Red LED will
illuminate when the circuit is OFF.
Pressing the panic button will deactivate the services. All Panel lights should illuminate with Panic.
Once in the Panic Mode the Key-switch must be engaged in order to reactivate service. The Alarm Signal
must be withdrawn prior to reactivation.
This unit utilizes latching solenoids that pulse ON with circuit active to open the water supply and pulse OFF
with circuit inactive to close it.

12
Innovative Systems
Integrating
Mechanical and Electrical
Technology
ISIMET believes that sole and local authority means that the primary operator should have
the sole authority to start and stop the utility services within the immediate area of use during
normal usage. This should distinguish this type of operating environment from that where a
single emergency shut-down device is located remotely from the areas of use.
PO Box 129 (Mailing)
103 W. CJ Wise Pkwy
Naples, Texas 75568-0129
Phone (866) 897-0737
Fax (903) 897-0740
www.ISIMET.com
This manual suits for next models
1
Table of contents
Other Isimet Controllers manuals
Popular Controllers manuals by other brands

Sunricher
Sunricher SR-2201DMX manual

Emerson
Emerson Bettis G01 Series Installation, operation and maintenance manual

Yudian
Yudian AI-7048 operation instruction

thomann
thomann BOTEX Rainbow Rider DMX user manual

IBM
IBM SAN Volume Controller 2145-CG8 Hardware installation guide

thomann
thomann the t.racks DSP 4x4 Amp 4.250 user manual