ISYGLT CC-03-USB User manual

Seebacher GmbH www.seebacher.de Phone: +49 (0) 80 41 / 77 77 6
Marktstrasse 57, 83646 Bad Tölz info@seebacher.de Fax: +49 (0) 80 41 / 77 77 2
1
Technical Data / Instruction Manual
CC-03-USB
Article no. 80016021
Compact Controller with USB interface

Seebacher GmbH www.seebacher.de Phone: +49 (0) 80 41 / 77 77 6
Marktstrasse 57, 83646 Bad Tölz info@seebacher.de Fax: +49 (0) 80 41 / 77 77 2
2
1. Notes on documentation
These instructions are intended for qualified personnel who are
familiar with the assembly, installation and operation of the ISYGLT
system. It is essential that you read these operating instructions
through before commissioning and keep them accessible for further
use.
SEEBACHER cannot accept any liability for damage or malfunctions
resulting from failure to observe these instructions.
1.1. Retention of documents
These instructions and all other applicable documents are part
of the product. They must be handed over to the device operator.
The operator will store the documents so that they can be made
available if necessary.
1.2. Symbols used
Observe the following safety and other instructions in the manual:
Handling instruction
The hand indicates that you should carry out an act.
Danger!
Immediate danger to life!
Attention!
General notes, useful information and special features
Directory of Content
1. Notes on documentation
1.1. Retention of documents
1.2. Symbols used
2. Safety instructions
2.1. Intended usage
2.2. Predictable mishandling
2.3. Safe handling
2.4. Qualification of staff
2.5. Changes to the product
2.6. Use of spare parts and additional equipment
2.7. Liability notes
3. Warranty
4. Declaration of Conformity
5. Service address
6. Maintenance / Care / Disposal
7. Storage
8. Assembly
9. Product description
10. Technical Data
10.1. Pin assignment
11. Wiring diagram

Seebacher GmbH www.seebacher.de Phone: +49 (0) 80 41 / 77 77 6
Marktstrasse 57, 83646 Bad Tölz info@seebacher.de Fax: +49 (0) 80 41 / 77 77 2
3
The module is designed for cabinet installation on a 35mm DIN
rail according to EN 60715 in corresponding standard housings.
Extreme environmental conditions impair the function of the pro-
duct.
• Protect module from shocks
• Use module indoors only
• Protect module from humidity
In addition to these safety instructions, you must also observe
the special safety instructions listed in the individual chapters for
the individual acts.
2.4. Qualification of staff
Assembly, commissioning, operation, maintenance, decommis-
sioning and disposal may only be carried out by qualified staff.
Work on electrical parts may only be carried out by a trained
electrician in accordance with the applicable regulations and
directives. Other activities in connection with the ISYGLT module,
such as assembly and installation of system components with
tested standard plug connections, as well as operation and con-
figuration of the ISYGLT module may only be carried out by trai-
ned staff.
2.5. Changes to the product
Unauthorized modifications to the ISYGLT module which are not
described in this or the other applicable instructions can lead to
malfunctions and are prohibited for safety reasons.
2.6. Use of spare parts and additional equipment
The module may be damaged if unsuitable spare parts and addi-
tional equipment are used. Only use original spare parts and
additional equipment from the manufacturer.
2.7. Liability notes
SEEBACHER accepts no liability or warranty whatsoever for
damage and consequential damage caused by non-compliance
with the technical regulations, instructions and recommendati-
ons. SEEBACHER shall not be liable for any costs or damage
incurred by the user or third parties as a result of the use of this
equipment, in particular improper use of the equipment, misuse
or malfunction of the connection, malfunction of the equipment
or connected devices.
SEEBACHER accepts no liability for printing errors.
2. Safety instructions
Observe the following general safety instructions when installing
and commissioning the device:
Assembly and installation of the ISYGLT module may only be carried
out by a qualified electrician. Other activities in connection with the
ISYGLT module, such as assembly and installation of system com-
ponents with tested standard plug connections, as well as operation
and configuration of the ISYGLT module may only be carried out by
trained staff.
Observe the electrical installation regulations of the country in which
the device is installed and operated as well as its national accident
prevention regulations. In addition, observe internal company regu-
lations (work, operating and safety regulations).
Before working on the ISYGLT module system, it must be
disconnected from the power supply and secured against
being switched on again. After completion of the assembly,
installation and maintenance work, an electrical check must
be carried out! Check all protective conductor connections
and the voltages at all connection plugs as well as at each
individual module slot.
2.1. Intended usage
The module is exclusively suitable for regulation (control) in con-
nection with ISYGLT system components. Any other use is not
intended. The limit values stated in the technical data must not be
exceeded under any circumstances. This applies in particular to
the permissible ambient temperature range and the permissible
IP protection type. For applications with a higher required IP pro-
tection type, the ISYGLT module must be installed in a housing
or a cabinet with a higher IP protection type.
2.2. Predictable mishandling
The module must not be used in the following cases in particular:
•explosive area
When operating in explosive areas, sparking can lead to defla-
gration, fire or explosions.
2.3. Safe handling
This module corresponds to the state of the art and the recog-
nised safety regulations. Each device is tested for function and
safety before delivery.
Only operate this module in perfect condition in accordance with
the operating instructions, the applicable regulations and directi-
ves of the country in which the device is installed and operated,
and the applicable safety and accident prevention regulations.

Seebacher GmbH www.seebacher.de Phone: +49 (0) 80 41 / 77 77 6
Marktstrasse 57, 83646 Bad Tölz info@seebacher.de Fax: +49 (0) 80 41 / 77 77 2
4
6. Maintenance / Care / Disposal
The product is maintenance-free. It is sufficient from time to time to
remove any dust deposits. This may only be done in a power-free
state.
Disposal (European Union)
Do not dispose of product in household waste! Products with this
symbol
7. Storage
The product must be stored in a dry place, protected from dirt and
mechanical stress. After damp or dirty storage, the product may only
be operated after a condition check by an authorised electrician.
8. Assembly
(Only by certified electrician!)
Mount the product only when it is in a power-free state!
Switch off the power supply, check that there is no voltage, secure
against being switched on again!
The device may only be operated at voltages according to the tech-
nical data and loaded with the currents defined therein. Only use
suitable equipment (system modules).
Check that there are no loose parts in the product. If this is the case
and the presence of such parts is not explicitly described, do not
install or commission the product.
Only use suitable cables and fixing screws.
Assembly site
• The product can be installed in any position in a casing to be deter-
mined by the electrician (distribution box, switch cabinet). Observe
maximum ambient temperature!
Assembly steps
(Read completely before assembly!)
• Mount the device in a suitable casing.
• Make the electrical connections according to the wiring diagram.
• Congure the DIP switches according to your requirements.
• Only after a complete connection and a visual test by a qualied
electrician, the system may be put under voltage.
Seebacher GmbH
Marktstrasse 57
83646 Bad Tölz
GERMANY
Phone: +49 (0) 80 41 / 77 77 6
Fax: +49 (0) 80 41 / 77 77 2
www.seebacher.de
info@seebacher.de
5. Service address
4. Declaration of Conformity
The valid declaration of conformity for the module can be requested
from us free of charge by stating type and article no. as follows:
By phone: +49(0)8041/77776
By fax: +49(0)8041/77772
By mail: info@seebacher.de
3. Warranty
We provide warranty within the framework of the statutory provisi-
ons. These are limited to the intended use of the module and refer
to the repair or replacement of the ISYGLT module. Please send the
device with an attached error description to our company address
given below.
must be disposed of according to the EU directive WEEE 2012/19/
EU on waste electrical and electronic equipment at the local collec-
tion points for waste electrical and electronic equipment!

Seebacher GmbH www.seebacher.de Phone: +49 (0) 80 41 / 77 77 6
Marktstrasse 57, 83646 Bad Tölz info@seebacher.de Fax: +49 (0) 80 41 / 77 77 2
5
Function displays
• 1 ashing yellow LED „BUS“ indicates trouble-free data transfer on the ISYGLT BUS
• 1 ashing green LED „Betrieb“ indicates the processor function:
Steady ashing means „system ok, but no DCF-77 time detected“.
2x short ashing followed by a pause means „system ok and valid DCF-77 time detected“
• 1 red LED „Power“ indicates the operating voltage
Design
• light grey plastic housing, can be put on 35mm DIN rail, 6 HP
Connections
• 1 analog output
• 1 relay output 230V 6.5A
• 1 connection for subnet (BUS A and B, RS-485)
• 1 connection for operating voltage (Ub, 0V)
• 2 P-COM connections (subnet and operating voltage)
• 8 outputs (NPN minus switching against common "+(A)")
• 8 inputs (on a common reference terminal "+(E)")
• 1 connection for programming > USB 2.0 Type-B socket
• 1 DMX512-IN
• 1 DMX512-OUT
Inputs / Outputs
• 1 relay output 230V 1500VA (max. 6.5A) hybrid technology with triac zero voltage switch
• 1 analog output 1-10V, sink current 20mA per channel, coupled with DMX-OUT channel 1 (but freely selectable dimming curve)
• 8 inputs 24V for buttons
• 8 feedback outputs
• 4 rotary potentiometers
• 1 DMX512-IN, 16 freely selectable channels
• 1 DMX512-OUT, 16 freely selectable channels
• 1 RS-485 interface for the subnet BUS
• 1 USB 2.0 Type-B socket for connection to PC / modem for programming
9. Product description
The CC-03-USB has been developed for the implementation of small control tasks. On the hardware side there is a 0(1)-10V interface, a relay
output in hybrid technology, 4 potentiometers, 8 low voltage button connections and 8 low voltage feedbacks, as well as 16 channels DMX-IN
and 16 channels DMX-OUT. With these prerequisites a multitude of small control systems can be implemented. The ISYGLT controller is freely
programmable and can be expanded with the available ISYGLT BUS components.
Application examples for this are:
• Small light controls with 1-4 xed values adjustable by potentiometer
• LED control via ISYGLT or DMX-512 with adjustment possibilities via potentiometer (brightness, colours RGB, warm white / cold white)
• Sequence controls

Seebacher GmbH www.seebacher.de Phone: +49 (0) 80 41 / 77 77 6
Marktstrasse 57, 83646 Bad Tölz info@seebacher.de Fax: +49 (0) 80 41 / 77 77 2
6
10. Technical data
10.1. Pin assignment
Type designation CC-03-USB
Article no. 80016021
Operating voltage 24V DC +/-20%
Current consumption 100mA at 24V + power for feedback outputs max. 150mA = sum max. 250mA
Inputs (buttons) 24V DC, input current per input 5mA at 24V (only own voltage by bridge can be used!); max. cable length: 50m
Outputs (feedbacks) 24V DC 0V switching, against internal + limited to 150mA; max. cable length: 50m
Relay output 230V 1500VA (max. 6.5A) with triac zero voltage switch
Analog output 1 analog channel 8 bit resolution 0-10V (1-10V); output current max. 20mA (sink or source)
Isolation voltage 1000V (ISYGLT BUS / analog outputs)
Interface 1 RS-485 subnet BUS max. 5.6V limited by Z-diodes
Interface 2 USB 2.0 Type-B socket for connection to PC / modem
Program memory Program memory for user program:
24 KByte (EEPROM) programmable
Scene memory:
8 KByte (EEPROM) for light scenes, non-volatile (not expandable)
Weight 200g
Connection Screw terminals 2.5mm² pluggable, spring-type terminals 1.5mm² pluggable
Operating temperature -10°C to +50°C
Storage temperature -25°C to +70°C
Dimensions WxHxD 106x90x59mm (6 HP)
Humidity 0 to 85% relative humidity, not condensing
Protection class IP 30
CE mark Yes
Terminal Down left
@Ub Operating voltage
0V 0V Operating voltage
A BUS A (subnet RS-485)
B BUS B (subnet RS-485)
Socket Top left (under the cover)
USB Type-B Programming interface
Terminal Top right
GND GND (0V) of 0(1)-10V analog output
AA1 0(1)-10V output sink or source (coupled with DMX output 1)
A8 Hybrid relay output 230V 6.5A (coupled with feedback output A8)
A8 Hybrid relay output 230V 6.5A (coupled with feedback output A8)

Seebacher GmbH www.seebacher.de Phone: +49 (0) 80 41 / 77 77 6
Marktstrasse 57, 83646 Bad Tölz info@seebacher.de Fax: +49 (0) 80 41 / 77 77 2
7
View
Terminal Down right (back row)
+(A) +24V current-limited for outputs
A1 Output 1
A2 Output 2
A3 Output 3
A4 Output 4
A5 Output 5
A6 Output 6
A7 Output 7
A8 Output 8
GND DMX512-OUT GND (is connected to XLR-Pin-1)
DMX- DMX512-OUT DATA - (is connected to XLR-Pin-2)
DMX+ DMX512-OUT DATA+ (is connected to XLR-Pin-3)
The GND of the DMX-IN and DMX-OUT connections are galvanically connected, but galvanically isolated from the rest of the controller!
Terminal Down right (front row)
+(E) +24V current-limited for inputs
E1 Input 1
E2 Input 2
E3 Input 3
E4 Input 4
E5 Input 5
E6 Input 6
E7 Input 7
E8 Input 8
GND DMX512-IN GND (is connected to XLR-Pin-1)
DMX- DMX512-IN DATA - (is connected to XLR-Pin-2)
DMX+ DMX512-IN DATA+ (is connected to XLR-Pin-3)

Seebacher GmbH www.seebacher.de Phone: +49 (0) 80 41 / 77 77 6
Marktstrasse 57, 83646 Bad Tölz info@seebacher.de Fax: +49 (0) 80 41 / 77 77 2
8
11. Wiring diagram
Misprints and technical changes reserved.
+24V
0V
N
L
S
S
S
S
S
S
S
S
0(1)-10V, max. 20mA
Programming interface Address
AA1.1
ISYGLT
Article no.:
E1 E2
E3 E4
8 inputs 24V
8 outputs 24V max.150mA
Address f. DMX-OUT AA1.1 -> AA4.4
Address f. DMX-IN AA5.1 -> AA6.8
Address f. potentiometer inputs AE7.1 -> AE7.4
Address f. inputs 24V E8.1 -> E8.8
Address f. outputs 24V A8.1 -> A8.8
max. 230V/6.5A
Address
A8.8
IN OUT
-(E)
-(A)
80016021
USB
Compact-Controller CC-03-USB
Ub
0V
BUS A
BUS B
+(E)
+(A)
E1
A1
E2
A2
E3
A3
E4
A4
E5
A5
E6
A6
E7
A7
E8
A8
GND
DMX-
DMX+
GND
A1
C8
A8
DMX+
DMX-
GND
L
ECG 1-10V
N PE + -
DMX+
COM
DMX-
1
5
2
4
3
DMX+
DMX-
COM 1
5
2
4
3
This manual suits for next models
1
Table of contents
Other ISYGLT Controllers manuals
Popular Controllers manuals by other brands

Phoenix Mecano
Phoenix Mecano LD1000E Assembly instructions

Ropex
Ropex RES-225 operating instructions

Fife
Fife CDP-01 Additional instruction manual

DOLD
DOLD SAFEMASTER BH 5902/01MF2 Datasheet / Operating Instructions

BFT
BFT GIOTTO BT A 30-60S U Installation and user manual

Honeywell
Honeywell Excel 10 installation instructions