Technical Data / Instruction Manual
I/O-08B-230V-10A
Article no. 80022000
8-way Switching Actuator

Seebacher GmbH www.seebacher.de Phone: +49 (0) 80 41 / 77 77 6
Marktstrasse 57, 83646 Bad Tölz info@seebacher.de Fax: +49 (0) 80 41 / 77 77 2
2
1. Notes on documentation
These instructions are intended for qualified personnel who are
familiar with the assembly, installation and operation of the ISYGLT
system. It is essential that you read these operating instructions
through before commissioning and keep them accessible for further
use.
SEEBACHER cannot accept any liability for damage or malfunctions
resulting from failure to observe these instructions.
1.1. Retention of documents
These instructions and all other applicable documents are part
of the product. They must be handed over to the device operator.
The operator will store the documents so that they can be made
available if necessary.
1.2. Symbols used
Observe the following safety and other instructions in the manual:
Handling instruction
The hand indicates that you should carry out an act.
Danger!
Immediate danger to life!
Attention!
General notes, useful information and special features
Directory of Content
1. Notes on documentation
1.1. Retention of documents
1.2. Symbols used
2. Safety instructions
2.1. Intended usage
2.2. Predictable mishandling
2.3. Safe handling
2.4. Qualification of staff
2.5. Changes to the product
2.6. Use of spare parts and additional equipment
2.7. Liability notes
3. Warranty
4. Declaration of Conformity
5. Service address
6. Maintenance / Care / Disposal
7. Storage
8. Assembly
9. Product description
10. Technical Data
10.1. Pin assignment
11. Wiring diagram

Seebacher GmbH www.seebacher.de Phone: +49 (0) 80 41 / 77 77 6
Marktstrasse 57, 83646 Bad Tölz info@seebacher.de Fax: +49 (0) 80 41 / 77 77 2
3
The module is designed for cabinet installation on a 35mm DIN
rail according to EN 60715 in corresponding standard housings.
Extreme environmental conditions impair the function of the pro-
duct.
• Protect module from shocks
• Use module indoors only
• Protect module from humidity
In addition to these safety instructions, you must also observe
the special safety instructions listed in the individual chapters for
the individual acts.
2.4. Qualification of staff
Assembly, commissioning, operation, maintenance, decommis-
sioning and disposal may only be carried out by qualified staff.
Work on electrical parts may only be carried out by a trained
electrician in accordance with the applicable regulations and
directives. Other activities in connection with the ISYGLT module,
such as assembly and installation of system components with
tested standard plug connections, as well as operation and con-
figuration of the ISYGLT module may only be carried out by trai-
ned staff.
2.5. Changes to the product
Unauthorized modifications to the ISYGLT module which are not
described in this or the other applicable instructions can lead to
malfunctions and are prohibited for safety reasons.
2.6. Use of spare parts and additional equipment
The module may be damaged if unsuitable spare parts and addi-
tional equipment are used. Only use original spare parts and
additional equipment from the manufacturer.
2.7. Liability notes
SEEBACHER accepts no liability or warranty whatsoever for
damage and consequential damage caused by non-compliance
with the technical regulations, instructions and recommendati-
ons. SEEBACHER shall not be liable for any costs or damage
incurred by the user or third parties as a result of the use of this
equipment, in particular improper use of the equipment, misuse
or malfunction of the connection, malfunction of the equipment
or connected devices.
SEEBACHER accepts no liability for printing errors.
2. Safety instructions
Observe the following general safety instructions when installing
and commissioning the device:
Assembly and installation of the ISYGLT module may only be carried
out by a qualified electrician. Other activities in connection with the
ISYGLT module, such as assembly and installation of system com-
ponents with tested standard plug connections, as well as operation
and configuration of the ISYGLT module may only be carried out by
trained staff.
Observe the electrical installation regulations of the country in which
the device is installed and operated as well as its national accident
prevention regulations. In addition, observe internal company regu-
lations (work, operating and safety regulations).
Before working on the ISYGLT module system, it must be
disconnected from the power supply and secured against
being switched on again. After completion of the assembly,
installation and maintenance work, an electrical check must
be carried out! Check all protective conductor connections
and the voltages at all connection plugs as well as at each
individual module slot.
2.1. Intended usage
The module is exclusively suitable for regulation (control) in con-
nection with ISYGLT system components. Any other use is not
intended. The limit values stated in the technical data must not be
exceeded under any circumstances. This applies in particular to
the permissible ambient temperature range and the permissible
IP protection type. For applications with a higher required IP pro-
tection type, the ISYGLT module must be installed in a housing
or a cabinet with a higher IP protection type.
2.2. Predictable mishandling
The module must not be used in the following cases in particular:
•explosive area
When operating in explosive areas, sparking can lead to defla-
gration, fire or explosions.
2.3. Safe handling
This module corresponds to the state of the art and the recog-
nised safety regulations. Each device is tested for function and
safety before delivery.
Only operate this module in perfect condition in accordance with
the operating instructions, the applicable regulations and directi-
ves of the country in which the device is installed and operated,
and the applicable safety and accident prevention regulations.

Seebacher GmbH www.seebacher.de Phone: +49 (0) 80 41 / 77 77 6
Marktstrasse 57, 83646 Bad Tölz info@seebacher.de Fax: +49 (0) 80 41 / 77 77 2
4
6. Maintenance / Care / Disposal
The product is maintenance-free. It is sufficient from time to time to
remove any dust deposits. This may only be done in a power-free
state.
Disposal (European Union)
Do not dispose of product in household waste! Products with this
symbol
7. Storage
The product must be stored in a dry place, protected from dirt and
mechanical stress. After damp or dirty storage, the product may only
be operated after a condition check by an authorised electrician.
8. Assembly
(Only by certified electrician!)
Mount the product only when it is in a power-free state!
Switch off the power supply, check that there is no voltage, secure
against being switched on again!
The device may only be operated at voltages according to the tech-
nical data and loaded with the currents defined therein. Only use
suitable equipment (system modules).
Check that there are no loose parts in the product. If this is the case
and the presence of such parts is not explicitly described, do not
install or commission the product.
Only use suitable cables and fixing screws.
Assembly site
• The product can be installed in any position in a casing to be deter-
mined by the electrician (distribution box, switch cabinet). Observe
maximum ambient temperature!
Assembly steps
(Read completely before assembly!)
• Mount the device in a suitable casing.
• Make the electrical connections according to the wiring diagram.
• Congure the DIP switches according to your requirements.
• Only after a complete connection and a visual test by a qualied
electrician, the system may be put under voltage.
Seebacher GmbH
Marktstrasse 57
83646 Bad Tölz
GERMANY
Phone: +49 (0) 80 41 / 77 77 6
Fax: +49 (0) 80 41 / 77 77 2
www.seebacher.de
info@seebacher.de
5. Service address
4. Declaration of Conformity
The valid declaration of conformity for the module can be requested
from us free of charge by stating type and article no. as follows:
By phone: +49(0)8041/77776
By fax: +49(0)8041/77772
By mail: info@seebacher.de
3. Warranty
We provide warranty within the framework of the statutory provisi-
ons. These are limited to the intended use of the module and refer
to the repair or replacement of the ISYGLT module. Please send the
device with an attached error description to our company address
given below.
must be disposed of according to the EU directive WEEE 2012/19/
EU on waste electrical and electronic equipment at the local collec-
tion points for waste electrical and electronic equipment!

Seebacher GmbH www.seebacher.de Phone: +49 (0) 80 41 / 77 77 6
Marktstrasse 57, 83646 Bad Tölz info@seebacher.de Fax: +49 (0) 80 41 / 77 77 2
5
9. Product description
With the I/O module I/O-08B-230V-10A 8 circuits with a maximum of
230V/10A (2 contacts each on a common root) can be switched. As
inputs 8 optocoupler inputs 12-48V on a common reference poten-
tial are available. All inputs and outputs are freely programmable in
the functions via the software.
Inputs / Outputs
• 8 relay outputs 230V/10A, 2 contacts each on a common root can be loaded with 10A
• 8 optocoupler inputs 12-48V
Function displays
• 1 red LED indicates the operating voltage
• 1 ashing yellow LED indicates the communication with the master via subnet
• 8 green LEDs signalize the current output states
Connections
• 1 connection for the subnet (BUS A and B, RS-485)
• 1 connection for the operating voltage (Ub, 0V)
• 8 outputs (2 each on a common connection)
• 8 inputs (on a common reference terminal)
• 2 P-COM connections (subnet and operating voltage)
Design
• DIN rail mounted plastic housing light grey, snap-on on 35mm DIN rail 6 HP
Special function DIP switch 1 = Emergency operation
• Switch „OFF“ = BUS operation
• Switch „ON“ = Emergency operation
(8x impulse switching function: input E1 switches output A1, input E2 switches output A2, etc.)
NEW!! The following functions can be parameterized
• Status of the output relays after Power ON
• Denition of the inputs as currentless OFF or ON
• Denition of the functions of the BUS inputs
• Denition of the functions in the operating modes: BUS, BUS failure and emergency operating
• Safety functions for motor controls (limit switch setup, interlockings, denable unlock times, switch-on times)
• Specication of dened pulse times on the relays
• Denition of the display LEDs at the module (indication inputs or outputs, BUS error, operating mode, chaser)

Seebacher GmbH www.seebacher.de Phone: +49 (0) 80 41 / 77 77 6
Marktstrasse 57, 83646 Bad Tölz info@seebacher.de Fax: +49 (0) 80 41 / 77 77 2
6
10. Technical data
10.1. Pin assignment
Type I/O-08B-230V-10A
Article no. 80022000
Operating voltage 16V to 35V DC or 16V to 27V AC
Current consumption 16V DC = 400mA, 24V DC = 250mA, 35V DC = 165mA
16V AC = 380mA, 24V AC = 220mA, 27V AC = 190mA
(each all relays activated)
Inputs 12-48V AC/DC, input current each input 5mA at 24V
Minimum load of the contact 500mW, min. 10V, min. 5mA
Outputs Relay contact 250V AC (DC max. 25V);
Load capacity:
pure ohmic 10A
bulbs 10A
fluorescent lamps uncompensated 6A
fluorescent lamps compensated 4A
LV-halogen via transformer 10A
1-phase motor 0.55kW
ECGs manufacturer dependent! Inrush current 100A <20ms
!! The inrush current of electronic ballasts (ECGs) is up to 100 times the nominal current !!
Subnet (RS-485) max. 5.6V limited by Z-diodes
Dimensions WxHxD 106x90x59mm (6 HP)
Weight 410g
Connection screw terminals 2.5mm², inputs and BUS plug-in, BUS connector
Operating temperature -10...+50°C
Storage temperature -25...+70°C
Humidity 0...85% r. h. non condensing
Protection class IP30
CE mark yes
@Ub Operating voltage
0V Operating voltage
A Subnet (BUS A, RS-485)
B Subnet (BUS B, RS-485)
C.1 Common for A1/A2
A1 Output 1
A2 Output 2
C.2 Common for A3/A4
A3 Output 3
A4 Output 4
C.3 Common for A5/A6
A5 Output 5
A6 Output 6
C.4 Common for A7/A8
A7 Output 7
A8 Output 8
C.5 Common for E1-E8
E1 Input 1
E2 Input 2
E3 Input 3
E4 Input 4
E5 Input 5
E6 Input 6
E7 Input 7
E8 Input 8

Seebacher GmbH www.seebacher.de Phone: +49 (0) 80 41 / 77 77 6
Marktstrasse 57, 83646 Bad Tölz info@seebacher.de Fax: +49 (0) 80 41 / 77 77 2
7
View
11. Wiring diagram
0V=
+24V
BUS-A
BUS-B
L
N
N
L
L
M
N
N
1 2 3 4 5 6 7 8
Art.Nr.: 80022000
address
ISYGLT-I/O-08B-230V-10A
max. 230V/10A per group of contacts
Ub
0V
BUS A
BUS B
C.5
E1
E2
E3
E4
E5
E6
E7
E8
A1
A2
C.1
A3
A4
C.2
A5
A6
C.3
A7
A8
C.4
N
Misprints and technical changes reserved.