ITI Interrogator 200 User manual

Page 1
Audio Verification Module
nUse a maximum of 500 feet of cable for all
speakers and microphones.
Tools Needed
nPhillips screwdriver
nMounting screws and anchors (included)
nDrill and bits
n3-conductor, 22-gauge shielded stranded wire
n2-conductor, 18-gauge stranded wire
Installation
To mount the AVM:
1. Route both 2 and 3-conductor wire cables from
the module to the panel.
2. Remove the cover screws from the module cover
and rotate it away from the base. Set the cover
and screws aside.
3. Remove the speaker plate screws and lift the
speaker plate off the back box (see Figure 1).
Figure 1. Removing the Speaker Plate
8557113A.DS4
SPEAKER
PLATE
Interrogator®200 Audio
Verification Module (AVM)
Document Number: 466-1621 Rev. A
October 1998
Installation
Instructions
Product Summary
The Interrogator 200 Audio Verification Module
(AVM) gives the central station operator the ability to
hear what’s happening at the premises during an
alarm and speak directly to the system owner. The
operator can determine how serious an alarm is, find
out what kind of help is needed, and dispatch the
appropriate assistance.
Control Panel Compatibility: SIMON ™
Only Version 2 (# 60-776)
Installation Guidelines
Use the following guidelines when installing the
AVM:
nYou can install one AVM per panel.
nWire speakers (voice terminals) in series and the
DC voltage, ground, and microphone wires in
parallel.
nUse separate cables for the speakers and the
power, ground, and microphone wires to prevent
cross talk between the microphone and the
speaker.
nUse 3-conductor, 22-gauge shielded wire from the
AVM power, ground and microphone to the
panel. Shielded cable reduces electrical noise and
cross talk.
nUse 2-conductor, 18-gauge wire from the speakers
to the panel.
60-787
8569G04A.DS4

Audio Verification Module
Page 2
4. Place the back box on the wall at the desired loca-
tion and mark mounting holes (see Figure 2).
Figure 2. Mounting Hole Locations
5. Install anchors if needed and secure the back box
to the wall with the enclosed screws.
6. Feed the cables through one of the cable holes in
the back box (see Figure 3).
Figure 3. Cable Holes and Channels
7. Align the back box mounting screw key holes
with the two mounting screws and slide down.
8. Level the back box and tighten the mounting
screws.
9. Feed the cable through the large hole on the
speaker plate.
10. Replace the speaker plate on the back box.
Wiring the AVM to the Control
Panel
To wire the AVM to the control panel:
1. Unplug the transformer and the battery.
2. Plug the panel cable, supplied with the AVM, into
the back of the control panel.
3. Connect terminals as shown in Figure 4. Use 18-
gauge wire for speakers and 22-gauge for power,
ground, and microphone.
Figure 4. Wiring the AVM to the Control Panel
4. Connect the black speaker wires on the AVM to
the blue wires on the control panel cable using the
18 gauge wire.
5. Connect power on the AVM to the red wire on the
control panel cable using the 22 gauge wire.
6. Connect the shielded cable drain wire (bare wire
shown in Figure 5) to the black wire on the control
panel cable and ground on the AVM.
Figure 5. Shielded Cable Detail
8557114A.DS4
MOUNTING SCREW
KEY HOLES
8557115A.DS4
CABLE
HOLES
8569G01C.DS
F
SPLICE
BLACK
YELLOW
CABLE
SHIELD
YELLOW
SPLICE
SPLICE
SPLICE
SPLICE
RED
BLUE
CONTROL PANEL CABLE CONNECTOR
(INCLUDED WITH AVM)
3-CONDUCTOR
22-GAUGE
SHIELDED
STRANDED WIRE
2-CONDUCTOR
18-GAUGE
STRANDED
WIRE
SPLICE
–
BLACK
+
INSULATED WIRE
SHIELDED
CABLE
DRAIN
WIRE
8569G02A.DS4

Audio Verification Module
Page 3
7. Splice the yellow wire on the AVM to one end of
the microphone cable and the other end to the yel-
low wire on the control panel cable.
8. Replace the AVM cover and screws.
Powering Up
To power up the panel and AVM:
1. Make sure all wires are connected correctly and
securely crimped.
2. Apply AC and battery power to the panel.
Programming
Programming the AVM involves entering the
following:
nEnabling AVM
nAVM mode of operation
nFire shutdown
nPanic talk
Enabling the AVM - Option 33
To allow the user or Central Station use of the AVM,
option 33 must be on. To turn option 33 on, follow
these steps:
1. Press Add from the Start Menu on the Control
Panel.
2. Press Option #, 33.
3. Press DONE.
Setting the AVM Mode - Option 47
The following describes the available AVM operating
modes.
Call-back - Option 47 is on
After reporting an alarm, the panel answers on the first
ring. A 5 minute window allows remote access alarm
verification after an alarm is reported.
This window is activated after an alarm has been
reported and allows access to the AVM after one ring
at the alarm site. The 5 minute window is cleared
when the monitoring service operator hangs up using
99.
Instant - Option 47 is off
The central station traps the panel when it reports an
alarm. Monitoring personnel can then initiate anaudio
session from a central station parallel telephone.
Fire Shutdown - Option 46
Shutdown - Option 46 is on
Fire sirens will be shut down at the customer site when
audio access is gained. Instead of sirens, the system
will beep every ten seconds.
Doesn’t Shutdown - Option 46 is off
Fire sirens will continue to sound at the customer site
when audio access is gained.
The default is off.
To turn Option 46 on:
1. Press Add from the control panel’s Start Menu.
2. Press Option #, 46.
3. Press DONE.
Panic Talk- Option 48
Talk - Option 48 is on
The central station operator is able to speak to the
person at the customer site during a silent alarm.
Listen Only - Option 48 is off
The central station operator is only able to listen to the
customer site during a silent alarm. The central station
will not be able to put the system into speak mode.
The defaul is off.
To turn Option 48 on:
1. Press Add from the control panel’s Start Menu.
2. Press Option #, 48.
3. Press DONE.
Testing
The panel must be programmed before testing.
When installation and programming are complete, test
the AVM as follows.

Audio Verification Module
Page 4
Off-Site Testing
You will need a helper and touch-tone phone at an off-
site location to perform this test.
Note: Option 27 (Ring, Hang, Ring) must be on to
perform the test.
To test the module from off-site:
1. The off-site helper calls the panel, lets the phone
ring once or twice, and hangs up.
2. The helper must call the panel again in 10 to 40
seconds. The panel answers.
3. The helper dials the following on the phone:
* CODE 5.
4. The helper should dial 1 and be able to speak to
you through the AVM.
5. The helper should dial 3 and listen to you.
6. Walk through the vicinity of the AVM while
speaking at a normal conversation level.
7. To return to speaking mode, the helper dials 1.
8. When testing is complete, have the helper dial 99
to hang up.
Central Station Testing
You can also use the central station to test the module.
To test the module from the central station:
1. Inform the central station that you will be sending
an alarm and testing an AVM.
2. Give them the programming selections you made
for the panel.
3. Use a touchpad panic button to initiate an auxil-
iary alarm.
4. The central station operator waits for the alarm to
be reported and initiates an audio session.
5. Have the operator speak to you.
6. Tell the operator to press 3 and walk through the
vicinity of the AVM while speaking at a normal
conversation level.
7. When testing is complete, the operator will end
the session by pressing 99.
Sound Volume
The AVM microphone volume is automatically
controlled and is not adjustable. The speaker volume is
preset to full volume.
If It Doesn’t Work
AVM communication failure usually occurs because of
panel programming errors. Check the programming
selections you made at the panel.
Specifications
Power Requirements: 12 VDC, 10 mA (maximum)
Dimensions: 6.9" L x 4.9" H x 2.5" D
Color: Belgian Grey
Notices
This device complies with part 15 of the FCC rules. Operation is subject to the following
two conditions:
1) This device may not cause harmful interference.
2) This device must accept any interference received, including interference that may
cause undesired operation.
Changes or modifications not expressly approved by Interactive Technologies, Inc. can
void the users’ authority to operate the equipment
ITI, Simon, and Interrogatorare registered trademarksof Interactive Technologies, Inc..
651-777-2690
651-779-4890
Other ITI Control Unit manuals
Popular Control Unit manuals by other brands

urmet domus
urmet domus alpha 1168/51 installation manual

AB Quality
AB Quality 1734-OW2 installation instructions

Honeywell
Honeywell V5004TF installation instructions

Flowserve
Flowserve Kammer 132000 Series manual

Wetco
Wetco Water Specialist 1.5EI Programming and Drawings Manual

GEA
GEA SVU 442 operating instructions