
5
NE210
For protection against shock hazards as specified in VDE 0411 part
100, stranded conductors may only be connected using wire end
ferrules with insulating caps. Terminals which are not assigned in
the factory must not be otherwise assigned by the user. We
recommend shielding all encoder connecting leads and earthing
the shield at one end. Earthing at both ends is recommend to avoid
RF interference or if equipotential bonding conductors are installed
over long distances. Encoder connecting leads should not be laid in
the same trunking as the mains power supply cable and output
contact leads.
3.1 Connecting the power supply
AC voltage connection
It is possible to switch between two different alternating voltage
ratings (see adjoining table) by means of the voltage selector switch
at the side of the unit. The higher of the two alternating voltage
ratings (48V or 230V) is preset by the factory.
➜Set the required alternating
voltage with the voltage
selector switch.
➜Connect the alternating
voltage supply to terminals 2
and 3 in accordance with the
counter wiring diagram.
DC voltage connection
Connect an interference-free power supply, i.e. do not use it for the
parallel connection of drive systems, contactors, solenoid valves, etc.
➜Connect the DC voltage in accordance with the counter wiring
diagram.
Fire protection: Operate the instrument using the recommended
external fusing indicated in the terminal diagram. VDE 0411
specifies that 8A/150 VA(W) must never be exceeded in the event
of a fault.
3.2 Assignment signal output „relay contact“
Terminals 4, 5 and 6 form a no-potential changeover contact, which
can be assigned as a pulse or continuous contact in accordance with
the adjoining wiring diagram.
Implementation as a pulse or continuous signal is effected via DIP-
switch 2 and in the programming mode, line 12 (see 3.6). The pulse
time is programmed in the programming mode, line 2.
Counter connecting
Voltage selector
6 5 4
Power supply Recommended
AC voltage external fusing
24V ±10% 50/60 Hz M 400 mA
48V ±10% 50/60 Hz M 400 mA
115V ±10%50/60 Hz M 125 mA
230V +6/ -10 %
50/60 Hz M 125 mA
Power supply Recommended
AC voltage external fusing
24 V ±10 %
approx. 5 % RW M 400 mA
Max. switching Max. switching Max. switching
output voltage current
150 VA/30 W 250 V 1A