ivo NE210 User manual

06.05 171.02.154/3
Subject to modification in
technic and design.
Errors and omissions exepted.
Contents Page
1 Safety instructions 2
2 Getting to know the counter 4
3 Counter connection 4
3.1 Connecting the power supply 5
3.2 Assignment signal output „relays contact“ 5
3.3 Assignment electronic output 6
3.4 Assignment signal input 6
3.4.1 Typical connections 8
3.5 Connecting the sensor supply 8
3.6 Establishing basic settings 9
3.6.1 Settings operating modes 9
3.6.2 Setting the counting frequency 9
3.7 Executing the test routine 10
4 Operating mode 10
5 Programming mode 12
5.1 Counting modes (Input modes) 15
5.2 Output responses (Output modes) 19
5.3 Counter overrun response 19
6 Technical data 20
6.1 Dimensions 21
6.2 Default settings 22
6.3 Error messages 22
7 Order designations 22
IVO GmbH & Co. KG
P.O. Box 3360 •D-78022 Villingen-Schwenningen
Phone +49 (0)7720 942-0 •Fax +49 (0)7720 942-900
A Member of the Baumer Group
Operating Instructions
Electronic preselection counter
NE210
COUNTERS CONTROLLERS ENCODERS

2
NE210
General Information
In the following you will find the explanations of the symbols used
in this operating manual.
Explanation of symbols
➜This symbol indicates activities to be carried out.
●This symbol indicates supplementary technical information.
This symbol is located before texts to which particular
attention is to be paid to ensure proper use of the product.
This symbol is located before texts that provide important additional
information.
Italics
Important terms in the left text column are printed in italics
to help you find information more quickly.
1 Safety instructions
1.1 General information
The products has been developed and built in accordance with the
recognized rules of technology. The units have left the
manufacturing plant ready to operate and in safe condition.
To keep the units in this condition, it is necessary that the units be
installed and operated
–properly,
–in a safety and hazard-conscious manner,
–under observance of this operating manual and in particular of
these safety precautions!
Make sure that the personnel has read and understood the operating
manual, and in particular the "Safety Instructions" chapter.
In addition to the operating manual, the generally applicable legal
and other binding regulations for accident prevention and environ-m
ental protection must be observed and ensured.
1.2 Proper use
The application of the units consists of controlling and monitoring
industrial processes in the metal, wood, plastics, paper, glass and
textile industry etc.
The units may only be operated
–in the properly installed state and
–in accordance with the specifications of the technical data!
Operation not covered by the specified descriptions/parameters is
improper and can lead to
–fatal injuries,
–serious damage to health,
–property damage or
–damage to the units
in conjunction with the systems/machines/processes to be
controlled/monitored!
General Information / Safety Instructions

3
NE210
The overvoltages to which the units are subjected at the connection
terminals must be limited to the value of the overvoltage category II
(see Technical data)!
The units may not be operated
–in hazardous areas,
–as medical units,
–in applications expressly named in EN 61010!
If the units are used to control/monitor machines or processes with
which, as the result of a failure/malfunction or incorrect operation of
the units
–a life-threatening danger,
–health risks or
–a danger of property or environmental damage
could result, then appropriate safety precautions must be taken!
Do not open the housing of the units or make any
changes to it!
Tampering with the units can have a negative affect on their
operating safety, resulting in dangers!
Do not make repairs on the units! Return defective units to the
manufacturer!
1.3 Installation/commissioning
In case of changes (including in the operating behavior) that
impair safety, shut-down the units immediately.
Installation may only be carried out in accordance with the
procedure described in Chapter 3 "Counter connecting".
During installation work on the units, the power supply must
always be disconnected. Installation work may only be carried out
by appropriately trained experts.
Max. voltage 250 V terminal - terminal, ground - terminal.
Following proper assembly and installation, the units are ready for
operation. Following commissioning, familiarize yourself with the
use of the units in Chapter 4 "Operating mode".
1.4 Maintenance/repairs
Always disconnect the power supply of all units involved.
Maintenance and repair work may only be carried out by
appropriately trained experts.
If troubleshooting is unsuccessful, do not continue to use the units.
Please contact the manufacturer in this case.
Safety Instructions

4
NE210Getting to know the counter
2 Getting to know the counter
The counter is an electronic, microprocessor-based presetting
counter. It can also be programmed to function as a:
–Time counter with various timescale options
–Time delay relay with four operating modes
3 Counter connection
This section describes the terminal assignments, accompanied by an
example of a typical connection.
Sections 3.1 to 3.5 contain specific instructions and technical data
relating to the individual terminals.
Connection example
Terminal Function
1 Not assigned
2 Power supply
3 Power supply
4
5 1 Signal output - relay contact
6
7 Track A
8 Track B
9 Reset by external signal
10 Electronic output (choice of PNP or NPN logic)
11 Coding input for input logic
12 Sensor supply (0 V)
13 Sensor supply (+24 V)
Display
Selector key for programming/
operating mode
Reset key C
Setting key for decade values
Parameters/LED display
Current main counter
Preset value
Scaling factor
Control panel
Selector key for programming/operating mode
Reset key C
Setting key for decade values
Setting key for decade selection
LEDs symbol display
Setting key for decade
selection
+24V 0V
Sensor
supply
Fuse
SUPPLY
Terminal - Terminal / - Terminal
max. 250 V
A
B
Count
Reset
Electr. output
NPN Br. 11-13
PNP Br. 11-12
Main contact
13 12 11 10 9 8 7
654321

5
NE210
For protection against shock hazards as specified in VDE 0411 part
100, stranded conductors may only be connected using wire end
ferrules with insulating caps. Terminals which are not assigned in
the factory must not be otherwise assigned by the user. We
recommend shielding all encoder connecting leads and earthing
the shield at one end. Earthing at both ends is recommend to avoid
RF interference or if equipotential bonding conductors are installed
over long distances. Encoder connecting leads should not be laid in
the same trunking as the mains power supply cable and output
contact leads.
3.1 Connecting the power supply
AC voltage connection
It is possible to switch between two different alternating voltage
ratings (see adjoining table) by means of the voltage selector switch
at the side of the unit. The higher of the two alternating voltage
ratings (48V or 230V) is preset by the factory.
➜Set the required alternating
voltage with the voltage
selector switch.
➜Connect the alternating
voltage supply to terminals 2
and 3 in accordance with the
counter wiring diagram.
DC voltage connection
Connect an interference-free power supply, i.e. do not use it for the
parallel connection of drive systems, contactors, solenoid valves, etc.
➜Connect the DC voltage in accordance with the counter wiring
diagram.
Fire protection: Operate the instrument using the recommended
external fusing indicated in the terminal diagram. VDE 0411
specifies that 8A/150 VA(W) must never be exceeded in the event
of a fault.
3.2 Assignment signal output „relay contact“
Terminals 4, 5 and 6 form a no-potential changeover contact, which
can be assigned as a pulse or continuous contact in accordance with
the adjoining wiring diagram.
Implementation as a pulse or continuous signal is effected via DIP-
switch 2 and in the programming mode, line 12 (see 3.6). The pulse
time is programmed in the programming mode, line 2.
Counter connecting
Voltage selector
6 5 4
Power supply Recommended
AC voltage external fusing
24V ±10% 50/60 Hz M 400 mA
48V ±10% 50/60 Hz M 400 mA
115V ±10%50/60 Hz M 125 mA
230V +6/ -10 %
50/60 Hz M 125 mA
Power supply Recommended
AC voltage external fusing
24 V ±10 %
approx. 5 % RW M 400 mA
Max. switching Max. switching Max. switching
output voltage current
150 VA/30 W 250 V 1A

6
NE210
The user is responsible for ensuring that a switching load of
8A/150 VA (W) is not exceeded in the event of a fault. Internal spark
suppression by means of two zinc oxide varistors (275 V). The
output relays of the instrument (1 relay or several) may only be
disengaged in total 5 x per minute at the most. Admissible clicks
according to interference suppression standard EN 55011 EN
50081-2 for the industrial sector. In case of a higher switching rate,
the operator must take care of interference suppression on the spot
and under his own responsibility by observing the load to be
switched.
➜Assign terminals 4, 5 and 6 (relay contact outputs) accordingly.
3.3 Assignment electronic output
The electronic output (terminal 10) is pre-programmed by the factory
as an NPN or PNP switching transistor (open collector) in accordance
with the purchase order specification. The output is coded as a pulse
or continuous signal at DIP-switch 2.
The electronic output is not short-circuit proof.
➜Assign terminal 10 accordingly.
3.4 Assignment signal input
Terminals 7, 8 and 9 are AC optocoupler inputs. Terminals 7 (track A)
and 8 (track B) are pulse inputs for the counting function.
Terminal 9 is the external reset input.
The counter is reset by applying an external signal (signal width
≥30 ms) at terminal 9 (see part 5, programming line 7).
➜Assign terminals 7, 8 and 9 accordingly.
The maximum counting frequency is set via DIP-switch 3
(see 3.6). For suitable pulse generators, see the encoder Catalogue.
Counter connecting
Output logic Max. switching voltage Max. switching current
NPN +35 V 50 mA
PNP +12...+24 VDC with 10 mA with AC power
AC power supply 50 mA with DC power
load-dependend
E
K
B
NPN
K
E
B
PNP
Terminal Input resistance Starting current Breaking current
7, 8 1.65 kΩ> 9 mA, < 16 mA < 0.5 mA
9 3.3 kΩ> 5 mA, < 8 mA < 0.5 mA

7
NE210Counter connecting
Programming input logic
The signal input logic can be programmed by means of a bridge
between terminals 11, 12 and 13, in accordance with the table
below.
Electrical isolation is provided for instruments with an AC power
supply and a relay output without electronic signal output in the
case of an external sensor supply.
To be used
- If the pulse
generator is not
supplied by the
encoder power
supply from the
counter.
- If the pulse
generator has a
push-pull or PNP
output stage.
- If several
counters are
triggered in
parallel by a single
pulse generator.
- If the pulse
generator has an
NPN output stage.
- If a NAMUR
encoder is
connected.
- In conjunction
with a max. 24
VAC power
supply.
Encoder signals
PNP, triggered by a
plus signal.
NPN, triggered by a
minus signal.
Alternating voltage
input; 7, 8 and 9,
triggered by max. 24
VAC.
Terminal assignments
11 and 12
E
K
B
K
E
B
13 12 11 10 9 8 7
13 12 11 10 9 8 7
13 12 10
11 9 8 7
11 and 13

8
NE210Counter connecting
3.4.1 Typical connections
Triggering by no-potential contacts.
Plus actuated Zero actuated
Triggering by incremental rotary encoders.
PNP or push-pull NPN or push-pull
Triggering by proximity switches.
PNP or push-pull NPN or push-pull
3.5 Connecting the sensor supply
Connect the sensor supply at terminals 12 and 13. Do not use the
sensor supply to supply non-earthed inductive or capacitive loads.
The sensor supply is not short-circuit proof.
Terminal Voltage Max. residual ripple Max. permissible current
12 0V – –
13 +24 VDC depending on load 50 mA
+10 %/-50 %
13 12 11 10 9 8 7
+ 0 V
13 12 11 10 9 8 7
+ 0 V
UB
GND
B A
13 12 11 10 9 8 7
+ 0 V
UB
GND
B A
13 12 11 10 9 8 7
+ 0 V
UB
GND
13 12 11 10 9 8 7
+ 0 V
UB
GND
13 12 11 10 9 8 7
+ 0 V
2. sensor
2. sensor

9
NE210Counter connecting
3.6 Establishing basic settings (DIP-switches)
The basic settings are established by means of DIP-switches, the
positions and effects of which are described below. The DIP-
switches are located on one side of the counter housing, together
with a setting diagram.
➜Set DIP-switches as required before installing the unit.
●All switches are set to OFF by the factory before delivery.
3.6.1 Setting operating modes (DIP-switch 1)
Adding mode
DIP-switch 1 OFF
The counter adds from zero to the preselected number. An external,
manual or automatic reset causes the counter to revert to zero or to
the programmed start count value.
Subtracting mode
DIP-switch 1 ON
The counter subtracts from a preselected number to zero or to the
programmed start count value. An external, manual or automatic
reset causes the counter to revert to the preselected number.
For details of totalizing, up/down and differential counting, see 5.1.
3.6.2 Setting the counting frequency (DIP-switch 3)
Application Max. counting setting DIP-switch 3 setting
Sensor with 10 kHz OFF
electronic
output
Triggering via 15 kHz ON
contacts;
microswitches
AC voltages
13
42
13
42
13
42
13
42
13
42
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
Dip-switch:
1 Count mode
2 Reset
3 Count speed
4 Programming
DIP Position Effect
1 OFF Adding mode
1 ON Subtracting mode
2 OFF Automatic reset
with pulse signal
2 ON External reset with
cont. signal
3 OFF Counting
frequency 10 kHz
3 ON Counting
frequency 15 Hz
4 OFF Programming
disabled (for
operating mode
see part 4)
4 ON Programming
enabled (for
programming
mode see part 5)
13
42

10
NE210
Counter connecting / Operating mode
In the case of two counting signals, phase offset by 90°and with
fourfold evaluation, the maximum counting frequency reduces to
5 kHz.
3.7 Executing the test routine
The test routine is described below.
To start test
➜Press the and keys simultaneously.
➜Switch the counter on.
●All the display segments will be displayed automatically in
sequence and are thereby tested for functional capability.
Test repeat
If you wish to repeat the test:
➜Press the key.
Test extension
Other counter functions can be tested:
➜Press the key again.
No machine functions may be connected when the outputs are
tested.
Testing of inputs A and B and reset input R.
●Inputs can be triggered simultaneously or individually.
A display is only provided when a signal is applied.
Output test
The output is now activated. Reset the output with the key.
Testing of DIP-switches in accordance with ON/OFF settings.
The settings and functions of the DIP-switches can be changed
while the test is in progress.
End of test
The test routine is now terminated.
4 Operating mode
The operation and use of the counter are described in this section.
●As soon as the power supply has been switched on, the
counter is automatically set to the operating mode.
Operating mode
In the operating mode:
–the current counter status can be read and reset;
–the input preset value can be read and changed, provided this is
enabled in the programming mode (line 5);
–the scaling factor can be read and changed, provided this is
enabled in the programming mode (line 5);
All the parameters can be disabled in the programming mode.

11
NE210
Counter status
The current counter status is displayed in the operating mode;
no keying is necessary.
➜Read the counter status display.
To reset
Resetting must be enabled in the programming mode (line 6).
➜Press the key.
Preset value
Functions relating to the preset value must be enabled in the
programming mode (line 5).
➜Press the key.
➜Read of preset value.
To change
➜Hold down the key until the decade position you require to
change flashes.
➜Hold down the key until the required number within the
flashing decade is reached.
If a key is not operated within 15 seconds, the current counter
status will automatically be re-displayed.
To store
➜Press the key.
The preset value can be changed during counting. This function
must be enabled in the programming mode (line 4).
●If a value is disabled in the operating mode, it will be skipped
and the next value displayed.
Scaling factor
Scaling factor functions must be enabled in the programming mode
(line 5).
➜Press the key.
➜Read off the scaling factor.
The scaling factor is an adjustable multiplier, whereby the ingoing
counting pulses are multiplied. The scaling factor can be adjusted
within the range from 0.001 to 99.999. The result of the
multiplication is shown in the display. Only whole-number values are
displayed. The remainder of the value is added to the next
calculation in each case.
Operating mode

12
NE210Operating mode / Programming mode
To change
➜Hold down the key until the decade position you require to
change flashes.
➜Hold down the key until the required number within the
flashing decade is reached.
If a key is not operated within 15 seconds, the current counter
status will automatically be re-displayed.
To store
➜Press the key.
5 Programming mode
This section describes the procedure for programming the counter.
Programming mode
Operating parameters are set in the programming mode, which is
subdivided into two programming segments, i.e. PRO 0 and PRO 1.
Both segments are described below in their actual order.
To access programming
➜Set DIP-switch 4 to „ON“.
●Programming of the desired operating parameter is now
enabled.
Keying
Key operation is the same in both the PRO 0 and PRO 1
programming segments.
Key
Function 1
Transfer to the next operating parameter in the programming
segment.
Function 2
Accept and acknowledge new value.
Key
Function
Select first or next decade position.
This will now be displayed flashing.
Key
Function
When this key is pressed, the display for the decade position
concerned runs from 0 to 9 or to the maximum setting value. When
the required number is reached, release the key.
Key
Function
In the case of the preset value, pulse time and start count value,
the display is reset to zero when this key is pressed.

13
NE210Operating mode
Programming segment PRO 0
Information on changing the counter status, preset value and scaling
factor can also be found in part 4.
➜Press the key again.
Current counter status
Preset value
Scaling factor
Programming segment PRO 1
In programming segment PRO 1, 12 programming lines are
displayed in succession.
Default settings are always printed with * .
Line 1
Decimal point
0 * 99999
1 9999.9
2 999.99
3 99.999
Line 2
Pulse signal time in seconds (s); adjustable from 0.02 s to 9.99 s.
0 No output signal
1 * 0.25 s
2 max. 9.99 s
●DIP-switch 2 activates pulse contact of continuous
contact.
Line 3
Counting mode (see 5.1)
0 * Track A and UP / DOWN signal on track B
1 Track A and STOP signal on track B
2 Differential counting, track A adding, track B subtracting (A-B)
3 Totalizing, tracks A and B adding (A+B)
4 Track A 90°phase offset to track B, single evaluation
5 Track A 90°phase offset to track B, twofold evaluation
6 Track A 90°phase offset to track B, fourfold evaluation
7 Time counter with preset
8 Time delay relay function
Line 4
Accept preset value
0 * In the case of automatic, external or manual reset
1 Effective immediately with acknowledgement.

14
NE210Programming mode
Line 5
Function enabled in operating mode
0 * Changing of preset value only enabled
1 Changing of scaling factor only enabled
2 Changing of preset value and scaling factor enabled
3 Changing of preset value and scaling factor disabled
Line 6
Reset key , function enabled in operating mode
0 * Reset key activated
1 Reset key disabled
Line 7
Reset input function
0 * Counting stop activated during external reset signal.
1 Differentiating reset signal effective with signal edge, no
counting stop.
Line 8
Start count value 0-999
0 * Start count value 0
999 Any start count value from 0 - 999
●DIP-switch 1 OFF: output set to preset value
DIP-switch 1 ON: output set to start count value
Line 9
Time scale and resolution
0 * 999 s 99/100 s
1 99 min 59 s 9/10 s
2 999 min 59 s
3 999 h 59 min
●Only applicable to use as a time counter or time delay relay.
Line 10
Time delay relay cycle
0 * Operating mode 1: ON delay
1 Operating mode 2: Hold time without stop (can be re-triggered)
2 Operating mode 3: Decay delay
3 Operating mode 4: Hold time with stop
Line 11
Output signal logic
0 * Normal output signal logic
1 Inverted output signal logic
●In the inverted output logic mode, the outputs are activated
when the power supply is switched on and drop out on preset.
Line 12
Output signal function
0 * As DIP - switch 2
1 External reset but without pulse signal
To leave the programming mode
➜Set DIP-switch 4 to „OFF“ .
To reprogram the counter to the
➜Press an hold the and keys before switching the
default settings
instrument on.

15
NE210
Programming lines
Line Default settings Customer´s program Description
Separating line
Current counter status
Preset value
Scaling factor
Separating line
01 Decimal point
02 Pulse signal time
03 Counting mode
04 Accept preset value
05 Function enabled in operating mode
06 Reset key, function enabled in operating mode
07 Reset input function
08 Start count value 0-999
09 Timescale and resolution
10 Time delay relay cycle
11 Output signal logic
12 Output signal function
5.1 Counting modes (Input modes)
This counter is able to count in either direction. The counting
direction is independent of the selected adding or subtracting
operating mode. The exceptions to this are counting with one
counting track A, counting stop input on track B, and totalizing.
Up/down counting with one counting track A and an external
up/down signal on track B
Programming mode
Track A
Up/Down
Counting

16
NE210Programming mode
Counting with one counting track A and counting stop
input on track B
The operating mode and consequent counting direction are selected
with DIP-switch 1.
Differential counting, track A adding, track B subtracting (A-B)
Any signal duration and time.
Totalizing, tracks A and B adding (A+B)
The operating mode and consequent counting direction are selected
with DIP-switch 1.
Up/down counting with two counting signals, phase-offset by
90 degrees
The counting direction is automatically identified from the leading/
lagging 90°phase offset. The internal phase discriminator performs
the necessary evaluation. Twofold or fourfold evaluation is possible.
Automatic up or down counting can also be obtained with pulse ge-
nerators which are not provided with evaluating electronics and do
not deliver a counting signal with the related counting direction signal.
Track A
Stop
Counting
Add.
Counting
Subtr.
n n-1 n-2 n-3 n-4
0 1 2 3 4
n n-1 n-2 n-3 n-5 n-6 n-7
Track A
Track B
Counting
Track A
Track B
Counting
Add.
Counting
Subtr.
Track A
Track B
Counting
4-fold
Counting
2-fold
Counting
1-fold

17
NE210Programming mode
Using the counter as a time counter with preset
Function
The time counter with reset is used to control maintenance intervals,
mixing times, etc. Use of the counter as a time counter is
established in programming line 3. The four timescales are selected
in programming line 9. The decimal point is set automatically.
The operating mode and consequent counting direction are selected
with DIP-switch 1. Resetting with a pulse signal or continuous signal
is effected with DIP-switch 2.
Start input
Track A (terminal 7) in time counting mode
Stop input
Track B (terminal 8) in time counting mode
The value programmed in programming line 1 remains ineffective.
The diagrams below show the output responses as a function of the
signal inputs.
External reset with continuous signal
DIP-switch 2 ON
Automatic reset with pulse signal
DIP-switch 2 OFF
External reset with pulse signal
DIP-switch 2 ON
and Line 12 on 1
Reset
Start, A
Stop, B
Preset
Zero
Output
Reset
Start, A
Stop, B
Preset
Zero
Output
Reset
Start, A
Stop, B
Preset
Zero
Output Tw
Tw
Reset
Start, A
Stop, B
Preset
Zero
Output
Reset
Start, A
Stop, B
Preset
Zero
Output Tw
Reset
Start, A
Stop, B
Preset
Zero
Output Tw

18
NE210Programming mode
Using the counter as a time delay relay
Function
Use of the counter as a time delay relay is established in program-
ming line 3. The four timescales are selected in programming line 9.
The four operating modes are selected in programming line 10. The
internal counting sequence takes place adding in all the operating
modes, irrespective of the positions of the DIP-switches.
Start input
Track A in time delay relay mode
Stop output
Track B in time delay relay mode
The values programmed in lines 1, 2 and 8 remain ineffective.
The diagrams below depict the output responses as a function of the
signal input.
Operating mode 1: Operating mode 3: Hold
ON delay time without discontinuation
Operating mode 2: Operating mode 4: Hold
Drop-out delay time with discontinuation
All the diagram patterns begin when the counter is switched on.
The reset signal completely resets a time delay relay cycle in
progress.
Reset
Start, A
Stop, B
Preset
Zero
Output Tv
Reset
Start, A
Stop, B
Preset
Zero
Output Tv
Reset
Start, A
Stop, B
Preset
Zero
Output Th
Reset
Start, A
Stop, B
Preset
Zero
Output Th

19
NE210
5.2 Output responses (output mode)
Signal output response is determined by the following:
– Operating mode selected on DIP-switch 1
– Reset mode selected on DIP-switch 2
– Programming of the preset value, start count value, output time,
output signal logic and output signal function;
– External resetting;
– External counting direction control.
The diagrams below show the output signal responses.
Adding operating mode Subtracting operating mode
External reset with continuous signal
Automatic reset with pulse signal
External reset with pulse signal
5.3 Counter overrun response
Counter overrun in minus range
The minus counting range is 0 to -9999.
If -9999 is exceeded, the counter is automatically reset to zero.
Counter overrun in plus range
The plus counting range is 0 to 199999. If 100000 is exceeded,
prefix zero suppression is cut out and the LED X flashes, indicating
the overrun. If 199999 is exceeded, the counter is automatically
reset to 100000.
Programming mode
Reset
Preset
Start count
value
Output
Reset
Preset
Start count
value
Output
Reset
Preset
Start count
value
Output Tw
Reset
Preset
Start count
value
Output Tw
Reset
Preset
Start count
value
Output Tw
Reset
Preset
Start count
value
Output Tw

20
NE210Technical Data
6 Technical data
Electrical data
Supply voltage 115 ±10 % / 230 VAC +6/-10 % (50 / 60 Hz)
24 / 48 VAC ±10 % (50 / 60 Hz)
24 VDC ±10 %, 5 % residual ripple
Power consumption 5.5 VA, 4.5 W
Sensor supply 12...26 VDC / 50 mA
Signal inputs Count input A / B
(Optocoupler inputs) - control current 9...16 mA
- breaking current <0.5 mA
- input resistance 1.65 kOhm
Reset input
- control current 5...8 mA
- breaking current <0.5 mA
- input resistance 3.3 kOhm
Can be coded as PNP / NPN via wire jumper to screw terminal
Input counting rate Adjustable to 15 Hz, 10 kHz via DIP
Signal outputs Programmable as momentary or permanent signals;
Impulse time can be programmed 0.01...9.99 s, tolerance: +0.01s
Relay signal outputs 1 float. relay as changeover contact Internal spark quenching
Relay can be programmed in inverted output logic
Max. switching voltage 250 VAC/110 VDC
Max. switching power 1 A
Max. switching capacity 150 VA/30 W
Electronic output NPN switching transistor
- Max. switching voltage +35 V
- Max. switching power 50 mA
PNP switching transistor
- Max. swit. voltage 12...24 VDC
With AC, depending on load
- Max. swit. power 50 mA, for DC
- Max. swit. power 10 mA, for AC
Reset Manual, electr. or automatically
Data storage > 10 years via EEPROM
Operation modes Adding or subtracting via DIP-switch
Mechanical data
Display 7-segment LED-display
5-digit display of real value, 7.6 mm high
Programmable decimal point
Display suppression of preceding zeroes
- Minus sign for negative values
Operation, keypad Front membrane with short-stroke keys
Front dimensions DIN housing 48 x 48 mm
Mounting Front panel with clip frame
Weight AC: approx. 260 g
DC: approx. 140 g
Connection Plug-in screw terminals
Grid 5.08 mm
Core cross-section Max. 1.5 mm2
Housing material Macrolon 6485 (PC) black, UL 94V-0
Keypad membrane material Polyester
Table of contents
Other ivo Cash Counter manuals