3.0 System configuration
WARNING ! Only qualified iZone 110 installers should configure the iZone 110 System. Incorrect configuration could result in
damage to your air conditioning unit and system.
3.1 On the C110MC, set the number of active zones required on the 6 position dip switch. By moving the associated dipswitch
up the respective zone will be deactivated and conversely by setting the dipswitch down (ON), the associated zone will be
activated. The factory setting is all 6 zones activated.
3.2 On the C110MC set the number of electronic constants you require to ensure the safe operation of the system.
An electronic constant is a safety feature and ensures that a predetermined number of zones remain open at all times even
if all the zones are switched off. If 1 electronic constant is selected, Zone 1 will automatically open if all the zones are
closed. If 2 electronic constants is selected, Zone 1 and 2 will automatically open if all the zones are closed. Only set the
number of electronic constants to 0 if the system is an old fashioned design with at least one supply air outlet that is not
zoned.
3.3 Set the AC unit fan speed to high and close all zones. Open one zone at a time and check which room the air is being
supplied to. Label the zone using the stickers provided, being care full to place the sticker squarely in the recess provided.
Peel off the protective coating from the sticker.