manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. jablotron
  6. •
  7. Fan
  8. •
  9. jablotron Futura User manual

jablotron Futura User manual

Ventilation unit
with heat and moisture recovery
FUTURA
Installation manual
JABLOTRON FUTURA INSTALLATION MANUAL
1/45 JABLOTRON LIVING TECHNOLOGY
TABLE OF CONTENTSTABLE OF CONTENTS
1. Introduction
1. Symbols used
2. Identification and application
3. Safety instructions
4. Technical specifications
5. Installation
1. Air ducts connection
2. Condensate drain connection
3. Electrical connection
4. Connecting the CoolBreeze
5. Commissioning
6. Configuration of the unit using Bluetooth
7. Online registration
8. Room-by-room ventilation (zoning system)
1. Configuration of Alfa control panel DIP switch
2. Configuration of a valve DIP switch
3. Configuration of an extract button DIP switch
4. Supply zone configuration
5. Extract zone configuration
9. BMS connection
10. Connection, information and function sharing with Volta or Aura boiler
11. Emergency shutdown function
12. Error alerts and their solutions
1. Alfa control panel error alerts
2. Wall-mounted control panel error alerts
3. Reset to default settings
13. Maintenance
14. Annex
1. Annex 1 - Unit structure
2. Annex 2 - Sonotex silencer
3. Annex 3 - Wiring diagram
4. Annex 4 - Control board connectors
5. Annex 5 - Unit connection
1. Examples of IN1 and IN2 input connection
6. Annex 6 - Connecting control panels and CO2 sensors
1. Connecting Alfa control panel via RS-485 bus
2. Connecting Alfa control panel via AA BUS
3. Connecting a wall-mounted control panel with CO2 sensor or a separate CO2 sensor
7. Annex 7 - Configuration of control panel and CO2 sensor Modbus RTU addresses
1. Alfa control panel addresses
2. Wall-mounted control panel with CO2 sensor or a separate CO2 sensor
8. Annex 8 - Room-by-room ventilation (zoning system) - DIP setting combinations
9. Annex 9 - Product fiche
10. Annex 10 - Energy labels
11. Annex 11 - Dimensional drawing
Version 6.0 EN
JABLOTRON FUTURA INSTALLATION MANUAL
2/45 JABLOTRON LIVING TECHNOLOGY
11. . IntroductionIntroduction
The subject of this installation manual is Futura - ventilation unit with heat and mois ture recoveryFutura - ventilation unit with heat and moisture recovery, which is designed
for controlled ventilation and treatment of the indoor environment of residential premises. The heat recovery unit ensures
recovery of heat and moisture, filters supplied air and helps maintain optimum air humidity. In summer, it provides additional
cooling in the night mode thanks to an integrated automatic bypass.
Before proceeding to the entire installation and commissioning of the heat recovery unit, read this Installation Manual carefully. It
is intended for trained professionals with appropriate qualifications. The Installation Manual contains explanations concerning
basic configuration of the unit, its assembly, installation, settings and maintenance.
Pay attention to all specifications and instructions included in this manual and follow them accordingly. This is the only way of
ensuring proper and safe operation of the heat recovery unit.
This device complies with the Commission Regulation (EU) No 1253/2014 with regard to ecodesign requirements for ventilation
units and Commission Delegated Regulation (EU) No 1254/2014 with regard to energy labelling of residential ventilation units.
ANY CHANGES RESULTING FROM TECHNICAL DEVELOPMENT ARE RESERVED. WE RESERVE THE RIGHT TO CHANGE THE
CONTENTS OF THIS INSTALLATION MANUAL ANYTIME WITHOUT PRIOR NOTICE.
11..11. . Symbols usedSymbols used
Please, pay increased attention to the symbols used. In the interest of your safety and proper operation of the heat recovery unit
follow the instructions that accompany every symbol.
SymbolSymbol Descri ptio nDescriptio n
IMPORTANT WARNINGIMPORTANT WARNING
CAUTION! IMMINE NT DANGE R!CAUTION! IMMINE NT DANGE R!
(risk of injury of the user or the service staff; risk of ventilation unit damage or disruption of its
proper function and operation).
CAUTION! ELE CTRIC EQUIPMENT!CAUTION! ELE CTRIC EQUIPMENT!
DANGER! CAUTION! RISK OF HAND INJURY!DANGER! CAUTION! RISK OF HAND INJURY!
22. . Identification and applicationIdentification and application
The Futura heat recovery unit is HVAC device with heat recovery and an active control of moisture recovery, that is designed for
comfortable and energy-efficient controlled ventilation of family houses. The heat recovery unit provides controlled ventilation of
residential premises with required ventilation volume of: 100 – 350 m3 (3530 - 12360 ft3) for Futura L or 50 - 250 m3 (1766 - 8830
ft3) for Futura M, at the outdoor air temperature range from -19 °C to +45 °C (-2 °F to 113 °F). The unit can be used at the maximum
relative indoor humidity level of 60% measured at 22 °C (72 °F).
Figure 1 – Identification label
JABLOTRON FUTURA INSTALLATION MANUAL
3/45 JABLOTRON LIVING TECHNOLOGY
33. . Safety instructionsSafety instructions
Always follow the safety instructions that are included in this Installation Manual. Failure to observe them may result in an injury
or damage to the heat recovery unit.
The unit has been developed and manufactured to provide controlled ventilation in residential buildings.
The unit may only be used for purposes for which it has been developed and manufactured and within its adequate technical
possibilities – in line with conditions defined by its manufacturer, its design, construction and technical condition while
complying with safety regulations.
The heat recovery unit must be installed in compliance with general and local safety regulations.
The heat recovery unit may only be installed, connected, commissioned and maintained by an authorized service technician
with respective professional qualifications. A service technician is a person with adequate qualification, experience and
knowledge of respective regulations and standards as well as possible risks and dangers.
Conductors connected to the equipment must be laid in such a way so as not to be exposed to mechanical damage and
harmful environmental effects and not interfere with the use of the premises where the unit will be installed.
The unit may be operated only by physically and mentally apt persons that have thoroughly read and understood the
Installation and User Manual. The manuals must be stored in an accessible place.
Do not change or modify the heat recovery unit in any way!
The unit cannot be used while there is still an ongoing construction work in the building. The unit must be installed and
commissioned in a finished and clean building.
The heat recovery unit is designed for joint operation with a fireplace only when the fireplace is suitable for passive buildings,
has a sealed fireplace insert and its own air supply.
Joint operation with a fireplace is possible only if relevant safety and fire regulations are followed. Such operation requires
setting and using the Overpressure function (see User manual: Heat recovery unit functions).
The unit must not be operated together with an open fireplace or with any fireplace without its ownThe unit must not be operated together with an open fireplace or with any fireplace without its own
air air supply!supply!
The unit mus t be off and disconnected from electrical mains during any maintenance including filterThe unit mus t be off and disconnected from electrical mains during any maintenance including filter
replacement!replacement!
Do do not reach into the filter space with your hand when replacing filters! Avoid ris k of hand injury!Do do not reach into the filter space with your hand when replacing filters! Avoid ris k of hand injury!
JABLOTRON FUTURA INSTALLATION MANUAL
4/45 JABLOTRON LIVING TECHNOLOGY
44. . Technical specificationsTechnical specifications
See table below for all technical data concerning the heat recovery unit:
Descriptio nDescri ptio n DataData DataData
airflow 50-250 m³/h (29-147 CFM) 100-350 m³/h (59-206 CFM)
Identification label Futura M Futura L
Specific Energy Consumption (SEC) in kWh/(m².a) for
each applicable climate zone and each applicable SEC
class
A+ A+
Dimensions (height x width x depth) 835 x 995 x 522 mm (32.9 x
39.2 x 20.6 in)
835 x 995 x 522 mm (32.9 x
39.2 x 20.6 in)
Weight 47 kg (104 lbs) 47,5 kg (105 lbs)
Declared typology bidirectional bidirectional
Drive type variable speed drive variable speed drive
Heat recovery system type recuperative recuperative
Heat recovery efficiency 91.8 %˟91.4 %˟
Reference flow 175 m³/h (103 CFM)˟˟˟ 245 m³/h (144 CFM)˟˟˟
Electric power input of the fan, including the motor
control equipment at maximum flow 230 W 320 W
Maximum power input including heating/td> 580 W 670 W
Acoustic power level 46 dBa˟˟ 46 dBa˟˟
Reference pressure difference 50 Pa˟˟˟ 50 Pa˟˟˟
SPI 0.34 W(m³/h)˟˟˟ 0.33 W(m³/h)˟˟˟
Condesate condensate drain, HT pipe
32mm (1.26 in), siphon
condensate drain, HT pipe
32mm (1.26 in), siphon
Electrical connection
230 V/50 Hz, 16 A; connection
to electric mains via power
socket
230 V/50 Hz, 16 A; connection
to electric mains via power
socket
Operational range without preheating -19 °C to +45 °C (-2 °F to 113
°F)
-19 °C to +45 °C (-2 °F to 113
°F)
JABLOTRON FUTURA INSTALLATION MANUAL
5/45 JABLOTRON LIVING TECHNOLOGY
Descriptio nDescri ptio n DataData DataData
Fans 2× EBM Papst with integrated electronics and
airflow regulation
2× EBM Papst with integrated electronics and
airflow regulation
Annual electricity
consumption
(AEC) (in kWh/m²
electric energy
consumption/year)
„average“, „warm“,
„cold“) at
reference flow
2.26/1.81/7.63 2.20/1.75/7.57
Annual heat
savings (AHS) (in
kWh/m2 of primary
energy/year) for
individual climate
zones („average“,
„hot“, „cold“) at
reference flow
47/92/21 47/92/21
Exchanger enthalpy counter-current exchanger with
humidity recovery control/td>
enthalpy counter-current exchanger with
humidity recovery control
Summer function fully automatic by-pass controlled by the
temperature setpoint/td>
fully automatic by-pass controlled by the
temperature setpoint
Control
Integration in the MyJABLOTRON mobile
application, which supports easy control of all
user functions and settings. It enables remote
monitoring, system administration and
provides automatic alerts for error conditions
and dirty filter replacement. Standard supply
includes one wall-mounted control panel with
an integrated CO2 sensor.
Integration in the MyJABLOTRON mobile
application, which supports easy control of all
user functions and settings. It enables remote
monitoring, system administration and
provides automatic alerts for error conditions
and dirty filter replacement. Standard supply
includes one wall-mounted control panel with
an integrated CO2 sensor.
Optional
accessories
CoolBreeze heating/cooling module, CO2
sensors (max. 8 pieces), more wall-mounted
control panels (max. 3 pieces), VAC material a
distribution elements
CoolBreeze heating/cooling module, CO2
sensors (max. 8 pieces), more wall-mounted
control panels (max. 3 pieces), VAC material a
distribution elements
˟ According to Czech norm ČSN EN 308
˟˟ According to Czech norm ČSN EN ISO 3744
˟˟˟ According to Directive of the Commission (EU) no.1253/2014
JABLOTRON FUTURA INSTALLATION MANUAL
6/45 JABLOTRON LIVING TECHNOLOGY
55. . InstallationInstallation
After receiving the heat recovery unit, please make sure that the unit has been delivered free of defects and that the delivery is
complete. The delivery includes:
Futura - ventilation unit with heat and moisture recovery,
wall-mounted control panel,
mounting bracket,
230 V connection cable,
LAN cable,
user manual,
installation manual,
siphon HL 138.
Choose a mounting location so that a sufficient handling space is available in front of the unit to ensure easy access and
maintenance. Place the heat recovery unit in a room protected from frost or very high temperatures, ideally in a separate utility
room. In case of CoolBreeze installation, please allow additional 70 cm (28 in) of free space above the unit!In cas e of CoolBreeze installation, please allow additional 70 cm (28 in) of free space above the unit!
The following has to be available at the installation site:
2 x EPP air duct connections for outdoor use and 2 x Sonotex flexi (silencer) for indoor use,
230 V mains power supply with separate 16A circuit breaker, B type,
HT 32 condensate drain connection.
All doors in rooms with forced ventilation mus t have All doors in rooms with forced ventilation mus t have no thresholdno threshold and a gap of at least 8mm (0.3 in)! and a gap of at least 8mm (0.3 in)!
Do not remove the packaging from the heat recovery unit until right before the installation. In case you interrupt the installation,
make sure the flanges on top of the unit are closed to prevent the dust and moisture from entering the unit's interior. The unit is
mounted onto a mounting bracket, which must be fixed to the wall in 4 points (see following picture). Use a technology that is
recommended and appropriate for the surface and material of the wall that the unit will be mounted on.
JABLOTRON FUTURA INSTALLATION MANUAL
7/45 JABLOTRON LIVING TECHNOLOGY
222277,,55
110011 666600
554400 222277,,55
Figure 2 – Installation
55..11. . Air ducts connectionAir ducts connection
The heat recovery system is equipped with 4 EPP ∅ 150 mm (6 in) flanges. It is necessary to use (intake/exhaust) EPP pipes both
at the air intake from the exterior and the air exhaust to the exterior to prevent the possibility of unwanted condensation inside
the pipes. For indoor air distribution use Sonotex piping with silencer.
The air inlet and outlet openings must remain free and clear! It is necess ary to ins tall silencers atThe air inlet and outlet openings must remain free and clear! It is necess ary to ins tall silencers at
the air supply to and extract from the interior in the length of approx. 1.5 m (5 ft) equipped with endthe air supply to and extract from the interior in the length of approx. 1.5 m (5 ft) equipped with end
elements (125mm (5 in) diameter) specified and recommended by the producer (see Annex 2).elements (125mm (5 in) diameter) specified and recommended by the producer (see Annex 2).
JABLOTRON FUTURA INSTALLATION MANUAL
8/45 JABLOTRON LIVING TECHNOLOGY
55..22. . Condensate drain connectionCondensate drain connection
In the heat exchanger, the extracted air is cooled by the supplied air causing moisture condensation. Resulting condensed water
is drained towards the siphon. The condensate drain connection is found on the bottom of the heat recovery unit. A siphon,
which is connected to the sewerage system, must be mounted onto the coupling of the condensate drain connection (HT 32
mm (1.26 in) drain pipe).
Condens ate must be allow ed to freely flow out of the heat recovery unit by gravity!Condens ate must be allow ed to freely flow out of the heat recovery unit by gravity!
2.
3.
4.
3322
224477
225533
1.
Figure 3 – Condensate drain connection
JABLOTRON FUTURA INSTALLATION MANUAL
9/45 JABLOTRON LIVING TECHNOLOGY
55..33. . Electrical connectionElectrical connection
Electrical connection of the heat recovery unit must be in accordance w ith applicable local standardsElectrical connection of the heat recovery unit must be in accordance w ith applicable local standards
and directives. Installation to the electrical mains may be carried out only by a trained electricianand directives . Ins tallation to the electrical mains may be carried out only by a trained electrician
with appropriate electrotechnical qualification, who is familiar with the heat recovery unit to thewith appropriate electrotechnical qualification, who is familiar with the heat recovery unit to the
necessary extent.necessary extent.
The ventilation unit requires a 230 V/50 Hz socket (16 A, type B) with a separate fuse. The unit is supplied with a 3m connection
cable. The ventilation unit is connected to the internet, therefore a LAN cable with internet connection is required. To connect
the peripherals of the unit use a RS-485 bus with 24 VDC supply. We recommend using a Jablotron CC-01 installation cable. Four-
wire twisted-pair cable, such as LiYCY 2 × 2 × 0.34 – 0.5 mm2, 2 × 2 × 0.8 mm2, UTP or STP cables can be used too. We
recommend using the same cable for boost and overpresure buttons. The cable must not run parallel to high or low voltage
power lines. Occasional crossing is fine. The Jablotron JA-110Z-B RS-485 bus splitter and the JA-190PL box can be used for more
convenient wiring. When installing RS-485 cables it is possible to use a bus (line) or a star topology with Futura as a central hub
and multiple connected devices. The length and the type of topology depend on the type of cable used and number of
connected peripherals. Using cable CC-01 with a larger cross section to supply the bus enables installation of the peripherals over
longer distances. The table below states maximum lengths and topologies allowed with regard to the peripherals used. “T“
variant is designed for connection of CoolBreeze and connection of VarioBreeze valves in the utility room, where the installation
of a separate branch is permitted. Other variants describe permitted combinations of Alfa control panels, CO2 sensors and
VarioBreeze buttons depending on the topology and cable length.
To po lo gyTo po lo gy
Maxi mum branchMaxi mum branch
length accordin gleng th acco rdin g
to cable type (m):to cable type (m):
Maxi mum number o f peri pherals per branch :Maxi mum number o f peri pherals per branch :
Var.Var. No. o fNo . of
bran ch esbran ch es
Jabl o tro nJabl otron
CC-0 1CC-0 1
UTPUTP
Cat5eCat5e Al faAlfa COCO 22
sensorsensor
Vari oBreezeVari oBreeze
buttonbutton
Vari oBreezeVari oBreeze
valvevalve Coo l BreezeCo o lBreeze
T 1 10 10 0 0 0 64 1
A T+1 80 60 6 8 16 64 1
B T+1 100 80 4 8 16 64 1
C T+2 100 80 4 4 8 64 1
D T+4 140 120 2 2 8 64 1
For further information see corresponding annex:
Wiring diagram – see annex 3a. Mainboard connectors – see annex 4. Connecting the unit – see annex 5. Connecting and setting
CO2 sensor addresses – see annex 6 and 7. Room-by-room ventilation – see chapter 8.
JABLOTRON FUTURA INSTALLATION MANUAL
10/45 JABLOTRON LIVING TECHNOLOGY
55..44. . Connecting the CoolBreezeConnecting the CoolBreeze
Cooling device must be connected in accordance with relevant standards and guidelines and mayCooling device mus t be connected in accordance with relevant standards and guidelines and may
only be carried out by a trained service technician with appropriate electrical and refrigerationonly be carried out by a trained service technician with appropriate electrical and refrigeration
qualifications , who is familiar with the device to the necess ary extent. Improper handling may caus equalifications , who is familiar with the device to the necess ary extent. Improper handling may caus e
electric shock or refrigerant burn!electric shock or refrigerant burn!
The CoolBreeze module requires connection of the outdoor condensation unit to the pow er supply via s eparaterequires connection of the outdoor condensation unit to the power supply via separate
230 V/50 Hz fixed line with 16 A fuse, type B.230 V/50 Hz fixed line with 16 A fuse, type B. We recommend using additional protective connection, i.e. connection to
the main ground terminal MET according to the ČSN 33 2000-5-54 norm. In case the outdoor unit is installed outside the
protective range of the lightning conductor, we recommend installing SPD surge protection of a suitable type according to ČSN 33
2000-5-534. As an alternative, a preparation for later installation can be made. Recommended cable is CYKY-J 3x2,5. The
connection must be carried out according to the original instructions of the unit manufacturer, which is available at:
https://www.jablotronlt.com/coolbreeze -> show downloads -> Installation instructions of the outdoor unit or under direct link
https://www.jablotronlt.com/files/coolbreeze/coolbreeze_navod_instalacni_venkovni_fujitsu_AOYG07LUCA_EN.pdf.
CoolBreeze is connected to the outdoor unit by a 4 x 0.75mmby a 4 x 0.75mm ² communication cable communication cable as shown in Appendix 3b. CoolBreeze
is also connected to Futura by a communication cable according to the diagram in Appendix 3b, which is included in the package.
Internal evaporator of the CoolBreeze module is connected to the outdoor unit by a 6/10mm refrigerant pipe. A minimumA minimum
refrigerant piping length of 3m (10 ft) and not exceeding 20m (66 ft) must be guaranteed.refrigerant piping length of 3m (10 ft) and not exceeding 20m (66 ft) must be guaranteed. The unit is pre-filled to
15m (49 ft) piping. In case of longer length, 20 g/m of refrigerant should be added. The maximum height difference of the device
is 15m (49ft) and must not be exceeded! Pay special attention to the cleanliness of the joints and proper insulation of the
refrigerant pipe to prevent condensation!
Connect CoolBreeze module to Futura unit with included RS-485 Per (X3) cable. See Annex 4.
Condensate drain should be connected via STY-517-1 siphon to Futura drain siphon. See Annex 11.
Beware of frequent error:
Figure 4 – Correct and incorrect condensate drain connection
Any improper handling of the w iring that could damage the heat recovery or cooling unit will voidAny improper handling of the wiring that could damage the heat recovery or cooling unit will void
the w arranty.the w arranty.
JABLOTRON FUTURA INSTALLATION MANUAL
11/45 JABLOTRON LIVING TECHNOLOGY
CoolBreeze indoor unit is pressurized with nitrogen for convenient detection of potential damage due to transport.
Please remove refrigerant seal before commissioning!
55..55. . CommissioningCommissioning
Prior to commissioning it is necessary to pay attention to completeness of the assembly, cleanliness of the equipment and
throughput of air ducts, correct directional insertion of filters, condensate drain functionality, correct electrical connection and
readiness for the operation of all technical components of the unit.
Any defects must be corrected before commissioning!
Before commissioning it is necessary to set:
fan outputs for individual power levels 1 - 5,
fan speed coefficient for overpressure and anti-radon protection,
nominal airflow (in case of VarioBreeze installation),
initialization of new filters.
This is carried out by the service technician in MyCOMPANY application.
JABLOTRON FUTURA INSTALLATION MANUAL
12/45 JABLOTRON LIVING TECHNOLOGY
66. . Configuration of the unit using BluetoothConfiguration of the unit using Bluetooth
Connecting the unitConnecting the unit
Configuration is made using Bluetooth and the MyCOMPANY mobile application. Remove the filter cover, then press and hold
the
filter reset
button on the PCB to activate Bluetooth. The button needs to be pressed until the LED backlight on the front cover
turns blue. If not, repeat the procedure. Short press = filter initialization, long press = Bluetooth connection. Configuration is
saved directly in the unit.
If you hold the button for at least 15 seconds, the LED backlight turns purple. After releasing the button the unit will reset into
default factory settings and will have to be configured again. If you activate the reset by mistake, do NOT release the button! Hold
it until the LED backlight turns green. Only then the button can be released and the unit will not be reset into factory settings.
XX 22 XX 33 XX 44 XX 55 XX 66
TT11
GGNNDD
XX 11
LLAANN RRSS-- 448855 EExx tt RRSS-- 448855 PPeerr NNTTCC AA AA
Bu t t onBu t t on
AA++
BB--
AA++
GGNNDD
++2244VV
GGNNDD
NNTTCC
LLEEDD
BBSSTT
GGNNDD
AAAA
AAAA
BB--
IN1IN1
IN2IN2
IN/OUTIN/OUT
Figure 5 – Bluetooth connection button
Make sure there are clean new filters inserted in the unit.Make sure there are clean new filters inserted in the unit. You can „Continue“„Continue“ to the next step.
Click on the upper left menu icon and choose "Connect to device""Connect to device" , click on the device "Futura""Futura" and the application goes
on to the next step.
Figure 6 and 7 – Connection via Bluetooth
JABLOTRON FUTURA INSTALLATION MANUAL
13/45 JABLOTRON LIVING TECHNOLOGY
A following message is displayed: "Duct s ystem connected""Duct sys tem connected" and "Fully opened""Fully opened", when all the ventilation valves are
open, confirm the message and click „Continue“„Continue“.
Figure 8 – Ventilation connection check
Configuring IP addressConfiguring IP address
Configuration of the IP address is run automatically from the DHCP serveris run automatically from the DHCP server, but may be set manually as well. In order to
configure the IP address manually connection parameters provided by the network administrator must be entered.
Figure 9 – Automatic configuration of the network connection, Figure 10 – Manual configuration of the network connection
JABLOTRON FUTURA INSTALLATION MANUAL
14/45 JABLOTRON LIVING TECHNOLOGY
Pres s ure loss - air distribution analys isPres s ure loss - air distribution analys is
Each ventilation duct system has its unique thermodynamic properties, therefore MyCOMPANY application contains „Air
distribution analysis“ function. An algorithm calculates airflow and pressure loss for each individual ventilation level (supply and
extract separately) for the given duct system.
Figure 11 – Setting the nominal air volume, Figure 12 – Analysis in progress
Set the desired nominal air volume and tap the arrow in the bottom right corner to run the analysis. The function will calculate
maximum available airflow for each of the five ventilation levels according to the real layout of the duct system (diameters,
lengths, vents, T-pieces). The unit will also calculate the pressure loss of the duct system. This process is fully automatic.
Air distribution analysis also includes filter calibration.
Figure 13 – Calculated maximum possible airflow, Figure 14 – Balancing of the ventilation levels, Figure 15 – Setting air volumes for
individual ventilation levels
You can set and manually balance air volume for each ventilation level in this section of the menu (see Fig.13, 14, 15). Pressure
JABLOTRON FUTURA INSTALLATION MANUAL
15/45 JABLOTRON LIVING TECHNOLOGY
loss of each ventilation level is a read-only value. When the air volume for a ventilation level is changed, Futura recalculates the
pressure loss for this ventilation level.
When the
Overpressure
or
Radon Protection
functions are activated (only one of them can be active at a time), the factor of fan
power changes. The factor is set as a percentage.
Example:Example: Overpressure is set on 120 % - this means that the supply fan runs at 120 % of the extract fan speed.
Nominal airflow of a zoneNominal airflow of a zone When installing VarioBreeze system, it is necessary to set the nominal airflow of each zone.
Figure 16 – Setting the nominal airflow of a zone
Use the application to set the required airflow of each supply zone in case of a nominal flow. The resulting airflow ratios among
individual zones will then be applied to other airflow values too.
The application shows the list of zones and their addresses (see annex 8). The value in parentheses next to the airflow value
represents the number of valves installed within the zone.
Tapping a zone opens its airflow settings . Simultaneous ly, LED indicators on the corres ponding valves , AlfaTapping a zone opens its airflow settings . Simultaneous ly, LED indicators on the corres ponding valves , Alfa
control panel and VarioBreeze button light up.control panel and VarioBreeze button light up.
Supply configurationSupply configuration
Nominal airflow needs to be allocated to individual zones. The system offers you default airflow allocation for each zone. This
value can be manually adjusted. Then the entered value is saved, locked and the airflows of remaining zones are recalculated, so
the total sum matches the nominal airflow. The locked zone is marked in green. If you need to reconfigure the airflow of a locked
zone, tap the unlock symbol and adjust the value.
Extraction configurationExtraction configuration
Extraction configuration allows you to reduce the extracted amount of air to the required nominal value, for example in case of a
zone with low pressure loss, such as utility room. If the amount of air does not have to be limited, we recommend using the
MAX setting.
JABLOTRON FUTURA INSTALLATION MANUAL
16/45 JABLOTRON LIVING TECHNOLOGY
77. . Online registrationOnline registration
When registering the unit mus t be connected to the internetthe unit must be connected to the internet. When the unit is on, it logs into the preset server and
maintains a permanent connection.
Figure 17 – Registration key
Log in to MyCOMPANY, run device registration and enter the unit registration keyunit registration key either manually or by scanning barcode
using camera in app. Next, optionally enter "Service Name", the customer's email address, and the time zone. Tap "SEND" to
submit the registration and complete the process.
Make sure "Location services" are enabled"Location services" are enabled when installing a new unit!
If the unit is not online, the following screen will be displayed and the following will need to be confirmed.
Figure 18 – Entering registration key, Figure 19 – Registration of the device, Figure 20 – Confirmation of other parameters
JABLOTRON FUTURA INSTALLATION MANUAL
17/45 JABLOTRON LIVING TECHNOLOGY
88. . Room-by-room ventilation (zoning system)Room-by-room ventilation (zoning system)
Max. 8 11–4
Max. 8 1–4
0–2
Figure 21 – Possible zone combinations
The picture above shows the number of control panels, valves and buttons that can be used for each zone.
When configuring zones each individual zone must have a control panel, a valve and a button configured using a DIP switch.
JABLOTRON FUTURA INSTALLATION MANUAL
18/45 JABLOTRON LIVING TECHNOLOGY
88..11. . Configuration of Alfa control panel DIP switchConfiguration of Alfa control panel DIP switch
First, set zone number (1 - 8) on the DIP switch. Use only the first three switchesthe first three switches on the DIP to set zone number! See picture
below for each zone number (1 - 8) and the corresponding position of switches no. 1 - 3. Use switch no. 6 to set the use of the
terminating resistor: set the switch to the ON position when you are using a terminating resistor.
②
③
④
⑤
⑥
⑦
⑧
①
Figure 22 – Setting zone number on Alfa control panel DIP switch
88..22. . Configuration of a valve DIP switchConfiguration of a valve DIP switch
Second, it is necessary to configure a valve DIP switch (if using multiple valves within a zone, configure DIP switch on each of the
valves). Use switches no. 1 - 3 to set zone number, switches no. 4 - 5 to set valve address and switch no. 6 to set air
supply/extract. For air supply, set the switch to the OFF position, for air extract, set the switch to the ON position.
②
③
④
⑤
⑥
⑦
⑧
①①
②
③
④
# 1–8 #
Figure 23 – Setting a valve DIP switch

Other manuals for Futura

3

Other jablotron Fan manuals

jablotron Futura User manual

jablotron

jablotron Futura User manual

jablotron Futura User manual

jablotron

jablotron Futura User manual

Popular Fan manuals by other brands

Hunter 21538 Owner's and installer's manual

Hunter

Hunter 21538 Owner's and installer's manual

YitaHome TLCFLS-1003 Assembly instructions

YitaHome

YitaHome TLCFLS-1003 Assembly instructions

NuTone ZB80L installation guide

NuTone

NuTone ZB80L installation guide

Broan QTR070C manual

Broan

Broan QTR070C manual

BELACOR AC-14652 installation instructions

BELACOR

BELACOR AC-14652 installation instructions

Goldair Select GSPF40R operating instructions

Goldair

Goldair Select GSPF40R operating instructions

Uberhaus FTP5-42E user manual

Uberhaus

Uberhaus FTP5-42E user manual

Strongway 52831 owner's manual

Strongway

Strongway 52831 owner's manual

Harbor Breeze ECHOLAKE 00876 installation manual

Harbor Breeze

Harbor Breeze ECHOLAKE 00876 installation manual

Sanus CAFQ01 instruction manual

Sanus

Sanus CAFQ01 instruction manual

Hunter Pacific Coolah Installation & user manual

Hunter Pacific

Hunter Pacific Coolah Installation & user manual

Craftmade Artistry AY56 installation instructions

Craftmade

Craftmade Artistry AY56 installation instructions

Wallair W-Style Premium 100 installation manual

Wallair

Wallair W-Style Premium 100 installation manual

Royal Sovereign PRO FAM-100 owner's manual

Royal Sovereign

Royal Sovereign PRO FAM-100 owner's manual

Sealey SWF16WR.V3 instructions

Sealey

Sealey SWF16WR.V3 instructions

Brandson Equipment 303369 user manual

Brandson Equipment

Brandson Equipment 303369 user manual

Helios MiniVent M1/100 Installation and operating instructions

Helios

Helios MiniVent M1/100 Installation and operating instructions

emerio FN-110475.2 instruction manual

emerio

emerio FN-110475.2 instruction manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.