  9. jablotron Futura User manual

jablotron Futura User manual

Other manuals for Futura

3

Other jablotron Fan manuals

jablotron Futura User manual

jablotron

jablotron Futura User manual

jablotron Futura User manual

jablotron

jablotron Futura User manual

Popular Fan manuals by other brands

Minka Group minkaAire Wave F843 instruction manual

Minka Group

Minka Group minkaAire Wave F843 instruction manual

Airflow Adroit DV50 instruction manual

Airflow

Airflow Adroit DV50 instruction manual

Vornado 270 Series owner's guide

Vornado

Vornado 270 Series owner's guide

comfort air TH-10D instruction manual

comfort air

comfort air TH-10D instruction manual

Livoo DOM386 instruction manual

Livoo

Livoo DOM386 instruction manual

Holmes BLIZZARD HAOF-90 owner's guide

Holmes

Holmes BLIZZARD HAOF-90 owner's guide

Taurus GRECO 16 ELEGANCE manual

Taurus

Taurus GRECO 16 ELEGANCE manual

Quorum PINNACLE installation instructions

Quorum

Quorum PINNACLE installation instructions

Monte Carlo Fan Company 3DIR58RBD-V1 Owner's guide and installation manual

Monte Carlo Fan Company

Monte Carlo Fan Company 3DIR58RBD-V1 Owner's guide and installation manual

Craftmade UH52 installation guide

Craftmade

Craftmade UH52 installation guide

Jocel JVA030658 instruction manual

Jocel

Jocel JVA030658 instruction manual

MIKA MFB1211/GR user manual

MIKA

MIKA MFB1211/GR user manual

Harbor Breeze RLG52NWZ5L manual

Harbor Breeze

Harbor Breeze RLG52NWZ5L manual

Allen + Roth L1405 instruction manual

Allen + Roth

Allen + Roth L1405 instruction manual

ViM KUBAIR F400 ECOWATT Technical manual

ViM

ViM KUBAIR F400 ECOWATT Technical manual

HIDRIA R10R-56LPS-ES50B-04C10 user guide

HIDRIA

HIDRIA R10R-56LPS-ES50B-04C10 user guide

BLAUBERG Ventilatoren CENTRO-M 100 L user manual

BLAUBERG Ventilatoren

BLAUBERG Ventilatoren CENTRO-M 100 L user manual

Triangle Engineering HEAT BUSTER SPL Series owner's manual

Triangle Engineering

Triangle Engineering HEAT BUSTER SPL Series owner's manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.

JABLOTRON FUTURA INSTALLATION MANUAL
1/43 JABLOTRON LIVING TECHNOLOGY
TABLE OF CONTENTSTABLE OF CONTENTS
1. Introduction
1. Symbols used
2. Identification and application
3. Safety instructions
4. Technical specifications
5. Installation
1. Air ducts connection
2. Condensate drain connection
3. Electrical connection
4. Connecting the CoolBreeze
5. Commissioning
6. Configuration of the unit using Bluetooth
7. Online registration
8. Room-by-room ventilation (zoning system)
1. Configuration of Alfa control panel DIP switch
2. Configuration of a valve DIP switch
3. Configuration of an extract button DIP switch
4. Supply zone configuration
5. Extract zone configuration
9. BMS connection
10. Connection, sharing information and functions with Volta boiler
11. Emergency shutdown function
12. Error alerts and their solutions
1. Alfa control panel error alerts
2. Wall-mounted control panel error alerts
3. Reset to default settings
13. Maintenance
14. Annex
1. Annex 1 - Unit structure
2. Annex 2 - Sonotex silencer
3. Annex 3 - Wiring diagram
4. Annex 4 - Control board connectors
5. Annex 5 - Unit connection
1. Examples of IN1 and IN2 input connection
6. Annex 6 - Connecting control panels and CO2 sensors
1. Connecting Alfa control panel via RS-485 bus
2. Connecting Alfa control panel via AA BUS
3. Connecting a wall-mounted control panel with CO2 sensor or a separate CO2 sensor
7. Annex 7 - Setting Modbus RTU addresses of control panels and CO2 sensors
1. Alfa control panel
2. Wall-mounted control panel with CO2 sensor or a separate CO2 sensor
8. Annex 8 - Room-by-room ventilation (zoning system) - DIP setting combinations
9. Annex 9 - Product fiche
10. Annex 10 - Energy labels
11. Annex 11 - Dimensional drawing
Version 3.0
JABLOTRON FUTURA INSTALLATION MANUAL
2/43 JABLOTRON LIVING TECHNOLOGY
11. . IntroductionIntroduction
The subject of this installation manual is F utura - venti l ati on uni t wi th heat and moistur e recoveryF utura - venti l ation uni t wi th heat and moi sture recovery , which is designed for controlled
ventilation and treatment of the indoor environment of residential premises. The heat recovery unit ensures recovery of heat and moisture,
filters supplied air and helps maintain optimum air humidity. In summer, it provides additional cooling in the night mode thanks to an integrated
automatic bypass.
Before proceeding to the entire installation and commissioning of the heat recovery unit, read this Installation Manual carefully. It is intended
for trained professionals with appropriate qualifications. The Installation Manual contains explanations concerning basic configuration of the
unit, its assembly, installation, settings and maintenance.
Pay attention to all specifications and instructions included in this manual and follow them accordingly. This is the only way of ensuring proper
and safe operation of the heat recovery unit.
This device complies with the Commission Regulation (EU) No 1253/2014 with regard to ecodesign requirements for ventilation units and
Commission Delegated Regulation (EU) No 1254/2014 with regard to energy labelling of residential ventilation units.
ANY CHANGES RESULTING FROM TECHNICAL DEVELOPMENT ARE RESERVED. WE RESERVE THE RIGHT TO CHANGE THE CONTENTS OF THIS
INSTALLATION MANUAL ANYTIME WITHOUT PRIOR NOTICE.
11..11. . Symbols usedSymbols used
Please, pay increased attention to the symbols used. In the interest of your safety and proper operation of the heat recovery unit follow the
instructions that accompany every symbol.
Symb olSymb ol Des crip t ionDes crip t ion
IMPORTANT W ARNI NGIMPORTANT W ARNI NG
C AU TIO N! IMMINENT DANGER!C AU TIO N! IMMINENT DANGER!
(risk of injury of the user or the service staff; risk of ventilation unit damage or disruption of its proper
function and operation).
C AU TIO N! ELEC TRI C EQ U IPMENT!C AU TIO N! ELEC TRI C EQ U IPMENT!
DANGER! C AUTIO N! RISK O F HAND INJURY!DANGER! C AUTIO N! RISK O F HAND INJURY!
22. . Identification and applicationIdentification and application
The heat recovery unit provides controlled ventilation of residential premises with required ventilation volume of: 100 – 350 m3 (3530 - 12360
ft3) for Futura L or 50 - 250 m3 (1766 - 8830 ft3) for Futura M, at the outdoor air temperature range from -19 °C to +45 °C (-2 °F to 113 °F). The unit
can be used at the maximum relative indoor humidity level of 60% measured at 22 °C (72 °F).
Figure 1 – Identification label
JABLOTRON FUTURA INSTALLATION MANUAL
3/43 JABLOTRON LIVING TECHNOLOGY
33. . Safety instructionsSafety instructions
Always follow the safety instructions that are included in this Installation Manual. Failure to observe them may result in an injury or damage to
the heat recovery unit.
The unit has been developed and manufactured to provide controlled ventilation in residential buildings.
The unit may only be used for purposes for which it has been developed and manufactured and within its adequate technical possibilities –
in line with conditions defined by its manufacturer, its design, construction and technical condition while complying with safety regulations.
The heat recovery unit must be installed in compliance with general and local safety regulations.
The heat recovery unit may only be installed, connected, commissioned and maintained by an authorized service technician with respective
professional qualifications. A service technician is a person with adequate qualification, experience and knowledge of respective regulations
and standards as well as possible risks and dangers.
Conductors connected to the equipment must be laid in such a way so as not to be exposed to mechanical damage and harmful
environmental effects and not interfere with the use of the premises where the unit will be installed.
The unit may be operated only by physically and mentally apt persons that have thoroughly read and understood the Installation and User
Manual. The manuals must be stored in an accessible place.
Do not change or modify the heat recovery unit in any way!
The unit cannot be used while there is still an ongoing construction work in the building. The unit must be installed and commissioned in a
finished and clean building.
The heat recovery unit is designed for joint operation with a fireplace only when the fireplace is suitable for passive buildings, has a sealed
fireplace insert and its own air supply.
Joint operation with a fireplace is possible only if relevant safety and fire regulations are followed. Such operation requires setting and
using the Overpressure function (see User manual: Heat recovery unit functions).
The F utura heat recovery uni t is HVAC devi c e wi th heat recover y and an acti ve control of moi sture r ecovery , that i sThe F utura heat recovery uni t is HVAC devi c e wi th heat recover y and an acti ve control of moi sture r ecovery , that i s
desi gned for comf ortabl e and ener gy - effi c i ent c ontr oll ed ventilati on of f ami l y houses.desi gned for comf ortabl e and ener gy - effi c i ent c ontr oll ed ventilati on of f ami l y houses.
The uni t must be of f and di sconnec ted from electrical mains dur i ng any mai ntenance i ncl udi ng f i l terThe uni t must be of f and di sconnec ted from electrical mains dur i ng any mai ntenance i ncl udi ng f i l ter
repl acement!repl acement!
Do do not reach i nto the f i l ter space wi th y our hand when repl aci ng f i l ters! Avoi d ri sk of hand i njury !Do do not reach i nto the f i l ter space wi th y our hand when repl aci ng f i l ters! Avoi d ri sk of hand i njury !
JABLOTRON FUTURA INSTALLATION MANUAL
4/43 JABLOTRON LIVING TECHNOLOGY
44. . Technical specificationsTechnical specifications
See table below for all technical data concerning the heat recovery unit:
Des crip t ionDes crip t ion Da t aDa t a Da t aDa t a
Air flow 50-250 m³/h (29-147 CFM) 100-350 m³/h (59-206 CFM)
Identification label Futura M Futura L
Specific Energy Consumption (SEC) in kWh/(m².a) for each
applicable climate zone and each applicable SEC class A+ A+
Dimensions (height x width x depth) 835 x 995 x 522 mm (32.9 x 39.2
x 20.6 in)
835 x 995 x 522 mm (32.9 x 39.2
x 20.6 in)
Weight 47 kg (104 lbs) 47,5 kg (105 lbs)
Declared typology bidirectional bidirectional
Drive type variable speed drive variable speed drive
Heat recovery system type recuperative recuperative
Heat recovery efficiency 91.8 %˟91.4 %˟
Reference flow 175 m³/h (103 CFM)˟˟˟ 245 m³/h (144 CFM)˟˟˟
Electric power input of the fan, including the motor control
equipment at maximum flow 230 W 320 W
Maximum power input including heating/td> 580 W 670 W
Acoustic power level 46 dBa˟˟ 46 dBa˟˟
Reference pressure difference 50 Pa˟˟˟ 50 Pa˟˟˟
SPI 0.34 W(m³/h)˟˟˟ 0.33 W(m³/h)˟˟˟
Condesate condensate drain, HT pipe 32mm
(1.26 in), siphon
condensate drain, HT pipe 32mm
(1.26 in), siphon
Electrical connection 230 V/50 Hz, 16 A; connection to
electric mains via power socket
230 V/50 Hz, 16 A; connection to
electric mains via power socket
Operational range without preheating -19 °C to +45 °C (-2 °F to 113 °F) -19 °C to +45 °C (-2 °F to 113 °F)
JABLOTRON FUTURA INSTALLATION MANUAL
5/43 JABLOTRON LIVING TECHNOLOGY
Des crip t ionDes crip t ion Da t aDa t a Da t aDa t a
Fans 2× EBM Papst with integrated electronics and air flow
regulation
2× EBM Papst with integrated electronics and air flow
regulation
Annual electricity
consumption (AEC)
(in kWh/m²
electric energy
consumption/year)
„average“, „warm“,
„cold“) at
reference flow
2.26/1.81/7.63 2.20/1.75/7.57
Annual heat
savings (AHS) (in
kWh/m2 of
primary
energy/year) for
individual climate
zones („average“,
„hot“, „cold“) at
reference flow
47/92/21 47/92/21
Exchanger enthalpy counter-current exchanger with humidity
recovery control/td>
enthalpy counter-current exchanger with humidity
recovery control
Summer function fully automatic by-pass controlled by the
temperature setpoint/td>
fully automatic by-pass controlled by the
temperature setpoint
Control
Integration in the MyJABLOTRON mobile application,
which supports easy control of all user functions and
settings. It enables remote monitoring, system
administration and provides automatic alerts for
error conditions and dirty filter replacement.
Standard supply includes one wall-mounted control
panel with an integrated CO2 sensor.
Integration in the MyJABLOTRON mobile application,
which supports easy control of all user functions and
settings. It enables remote monitoring, system
administration and provides automatic alerts for
error conditions and dirty filter replacement.
Standard supply includes one wall-mounted control
panel with an integrated CO2 sensor.
Optional
accessories
CoolBreeze heating/cooling module, CO2 sensors
(max. 8 pieces), more wall-mounted control panels
(max. 3 pieces), VAC material a distribution elements
CoolBreeze heating/cooling module, CO2 sensors
(max. 8 pieces), more wall-mounted control panels
(max. 3 pieces), VAC material a distribution elements
˟ According to Czech norm ČSN EN 308
˟˟ According to Czech norm ČSN EN ISO 3744
˟˟˟ According to Directive of the Commission (EU) no.1253/2014
JABLOTRON FUTURA INSTALLATION MANUAL
6/43 JABLOTRON LIVING TECHNOLOGY
55. . InstallationInstallation
After receiving the heat recovery unit, please make sure that the unit has been delivered free of defects and that the delivery is complete. The
delivery includes:
Futura - ventilation unit with heat and moisture recovery,
wall-mounted control panel,
mounting bracket,
230 V connection cable,
LAN cable,
user manual,
installation manual,
siphon HL 138.
Choose a mounting location so that a sufficient handling space is available in front of the unit to ensure easy access and maintenance. Place
the heat recovery unit in a room protected from frost or very high temperatures, ideally in a separate utility room. I n case of C ool BreezeIn case of C oolBreeze
instal l ati on, pl ease al l ow addi ti onal 7 0 c m (28 i n) of fr ee spac e above the uni t!instal l ati on, pl ease al l ow addi ti onal 7 0 c m (28 i n) of fr ee spac e above the uni t!
The following has to be available at the installation site:
2 x EPP air duct connections for outdoor use and 2 x Sonotex flexi (silencer) for indoor use,
230 V mains power supply with separate 16A circuit breaker, B type,
HT 32 condensate drain connection.
Al l doors i n rooms wi th for ced venti l ati on must have Al l doors i n rooms wi th for ced venti l ati on must have no threshol dno threshol d and a gap of at l east 8mm (0.3 i n)! and a gap of at l east 8mm (0.3 i n)!
Do not remove the packaging from the heat recovery unit until right before the installation. In case you interrupt the installation, make sure the
flanges on top of the unit are closed to prevent the dust and moisture from entering the unit's interior. The unit is mounted onto a mounting
bracket, which must be fixed to the wall in 4 points (see following picture). Use a technology that is recommended and appropriate for the
surface and material of the wall that the unit will be mounted on.
JABLOTRON FUTURA INSTALLATION MANUAL
7/43 JABLOTRON LIVING TECHNOLOGY
222277,,55
110011 666600
554400 222277,,55
Figure 2 – Installation
55..11. . Air ducts connectionAir ducts connection
The heat recovery system is equipped with 4 EPP ∅ 150 mm (6 in) flanges. It is necessary to use (intake/exhaust) EPP pipes both at the air intake
from the exterior and the air exhaust to the exterior to prevent the possibility of unwanted condensation inside the pipes. For indoor air
distribution use Sonotex piping with silencer.
The ai r i nlet and outl et openi ngs must remai n f ree and c l ear ! It i s nec essary to i nstal l si l encers at the ai rThe ai r i nlet and outl et openi ngs must remai n f ree and c l ear ! It i s nec essary to i nstal l si l encers at the ai r
suppl y to and extract f rom the interior i n the length of approx. 1.5 m (5 ft) equi pped wi th end el ementssuppl y to and extract f rom the interior i n the length of approx. 1.5 m (5 ft) equi pped wi th end el ements
(12 5mm (5 i n) di ameter) speci f i ed and rec ommended by the pr oducer (see Annex 2 ).(12 5mm (5 i n) di ameter) speci f i ed and rec ommended by the pr oducer (see Annex 2 ).
JABLOTRON FUTURA INSTALLATION MANUAL
8/43 JABLOTRON LIVING TECHNOLOGY
55..22. . Condensate drain connectionCondensate drain connection
In the heat exchanger, the extracted air is cooled by the supplied air causing moisture condensation. Resulting condensed water is drained
towards the siphon. The condensate drain connection is found on the bottom of the heat recovery unit. A siphon, which is connected to the
sewerage system, must be mounted onto the coupling of the condensate drain connection (HT 32 mm (1.26 in) drain pipe).
C ondensate must be al l owed to fr eel y f l ow out of the heat rec overy uni t by gravity !C ondensate must be al l owed to fr eel y f l ow out of the heat rec overy uni t by gravity !
3322
224477
225533
Pipe HT - 32
Siphon HL 138
Connection
to sewerage
Connection to siphon
Figure 3 – Condensate drain connection