Jandy AquaLink RS User manual

All Button and OneTouch
Control Panels
™

2
ImportantSafetyPrecautions
When installing and using this electrical equipment, these basic safety precautions should always be
followed:
1. READ AND FOLLOW ALL INSTRUCTIONS.
2.DANGER- to reduce the risk of injury, do not permit children to use this product unless they are closely
supervised at all times.
3. All electrical work must be performed by a licensed electrician and must conform to all national, state, and local
codes.
4. WARNING: Water temperature in excess of 100°F/38°C may be injurious to your health.
AVERTISSEMENT: Il peut être dangereux pour la santéde se plonger dans de l'eau àplus de 100°F/38°C.
Prolonged immersion in hot water may induce hyperthermia. Hyperthermia occurs when the internal
temperature of the body reaches a level several degrees above the normal body temperature of 98.6°F/37°C.The
symptoms of hyperthermia include dizziness, fainting, drowsiness, lethargy, and an increase in the internal
temperature of the body. The effects of hyperthermia include: 1) unawareness of impending danger; 2) failure to
perceive heat; 3) failure to recognize the need to exit spa; 4) physical inability to exit spa; 5) fetal damage in pregnant
women; 6) unconsciousness resulting in a danger of drowning. WARNING - The use of alcohol, drugs, or
medication can greatly increase the risk of fatal hyperthermia in hot tubs and spas.
La consommation d'alcool ou
de drogue augmente considérablement les risques d'hyperthermie mortelle dans une cuve de relaxation.
5. Install to provide drainage of compartment for electrical components.
6. Install at least five (5) feet (152.4cm) from the inside wall of the pool and tub. Canadian installations must be at least
three (3) meters from the water.
Les installations canadiennes doivent se trouver àau moins trois (3) mètres de l'eau.
7. A ground-fault circuit-interrupter must be provided if this device is used to control underwater lighting fixtures. The
conductors on the load side of the ground-fault circuit-interrupter shall not occupy conduit, boxes or enclosures
containing other conductors unless the additional conductors are also protected by a ground-fault circuit-interrupter.
Refer to local codes for complete details.
8. A terminal bar marked GROUND is provided within the Power Center. To reduce the risk of electrical shock, connect
this terminal bar to the grounding terminal of your electric service or supply panel with a continuous green insulated
copper wire equivalent in size to the circuit conductors supplying this equipment, but no smaller than No. 12 AWG
(3.3 mm). In addition, a second wire connector should be bonded with a No. 8 AWG (4.115mm) copper wire to any
metal ladders, water pipes, or other metal within 5 feet (1.52m) of the tub.
9.CONTROL SYSTEM IS INTENDED TO CONTROL HEATERS WITH BUILT-IN HIGH LIMIT CIRCUITS ONLY.
10.PLEASE SAVE THESE INSTRUCTIONS.
LIRELANOTICETECHNIQUE.
SPECIFICATIONS(USA&CANADA):
POWER SUPPLY: 120 Volts A.C.; 60 Hz.; 3 amps.
CONTACT RATING:(High Volt.) 25 amp; 3 h.p. @ 240 Volts A.C.,
1½h.p. @ 120 Volts A.C.;
1500 Watts Incandescent
CONTACT RATING: (Low Volt.) Class Two, 1 amp at 24V A.C.
EMERGENCY SERVICE SWITCHES: All circuits.
DIMENSIONS(USA&CANADA):
Standard Power Center: Height-13¾"; Width-14½"; Depth-5"
Sub Panel Power Center: Height-20"; Width-14½"; Depth-5"
All Button Control Panel: Length-8"; Width-5"; Depth-1¼"
OneTouch Control Panel Height-4½"; Width-4½"; Depth-1¼"
Four Function Switch: Diameter-2¾"
SPECIFICATIONS(EUROPEAN):
POWER SUPPLY: 230-240V~50/60 Hz.; 3 A.
CONTACT RATING:(High Volt.) 25A;3h.p.@240Volts V~
CONTACT RATING: (Low Volt.) Class Two@24V~
EMERGENCY SERVICE SWITCHES: All circuits.
DIMENSIONS(EUROPEAN):
Standard Power Center: Height-35.3cm; Width-37.2cm; Depth-12.8cm
Sub Panel Power Center: Height-51.3cm; Width-37.2cm; Depth-12.8cm
All Button Control Panel: Length-20.5cm; Width-12.8cm; Depth-3.2cm
OneTouch Control Panel Height-11.43cm; Width-11.43cm; Depth-3 cm
Four Function Switch: Diameter-7.1cm

3
TableofContents
2Safety Precautions
Safety Precautions
Specifications
Dimensions
Table of Contents
System Overview
Controller Package
Power Center
Options and Accessories
Other Options
Specialty Boards
TeleLink Kit
Surge Protection Kit
Basic Plumbing
Standard Plumbing for Pool and Spa
Non-Booster Pump Pressure-Side Pool Cleaner Plumbing
Booster Pump Pool Cleaner Plumbing
Solar System Plumbing
Power Center Connection
Power Center Preparation
High Voltage Wiring
Low Voltage Wiring (P.C. Board)
Auxiliary Power Centers
All Button Control Panel Wiring
Control panel Wiring
Setup for Multiple Controllers
DIP Switch Settings
OneTouch Control Panel Installation
Flush Mount
Surface Mount
Templates
All Button Programming and System Defaults
All Button Reset and Display Messages
OneTouch Programming and System Defaults
OneTouch Reset and Display Messages
Four Function Spa Side Switch or SpaLink™RS
Provisions
Preparation for Installation of Four Function Switch or SpaLinkRS
AquaRite Chlorine Generator Installation
AquaLink®RS Troubleshooting Quick Check List
AquaLink®RS Heater Connections
Installation Guidelines
Cancel Button Flow Chart
All Button Menu Flow Chart
OneTouch Menu Flow Chart
AquaLink®RS Wiring Diagram
3
4
5
6-7
8-11
13-15
16-18
22
23-25
26
32
31
19
20
21
33
34
12
27-28
29-30

4
*Not Available in CE Models
SystemOverview

5
OtherOptions
TeleLink®Kit Surge Protection Kit
*Not Available in CE Models
**
*Not Available in CE Models
Specialty Boards
Multiplex Board
Four
Conductor
Wire
J4
J3
J2
J1
Multiplex Board is required when
connecting more than 2 wires on a
4 pin Connector.
Auxiliary/JVA Relay Board
TB3
K1
J1
TB2
JVA Relay Aux Board is used to operate
a JVA 2440 from any Auxiliary
Relay Coil
Transformer
Socket
Extra Relay
Socket
J2
Transformer
Connection
JVA Socket
Relay Splitter
Relay Splitter is used to turn
on two relays off one circuit.
Plug into
Relay
Socket
To Relay 1
To Relay 2
K1
J2
TB2
JVA Relay Interlock Board
JVA Relay Interlock Board is used to turn
off or on a piece of equipment
as the system switches from pool to spa.
Connect to
Plug in JVA
Filter Pump
(Normally
JVA
K1
P6
P3
FILTER PU MP
3
2
1
TB1
1
2
34
P4
Normall
yNormally
Open
Plug into
NO
NC
COMMON
Required for use with two speed
pumps.
2-Speed Relay
NEUTRAL
LIGHT HOT
120 VAC HOT
Light Dimming Relay
Required for u se when using a
dimmer on a switched circuit.
Switch 2
Switch 3
Dual Spa Side Switch
Interface Board
Required for use with two or more
Spa Side Remotes.
Dual Equipment Heater
Interface Board
Required for use with AquaLink
RS2/6, 2/10, or 2/14 two heaters.
Assy # 6800
Assbly. # 6941

6
BasicPlumbing
Plumbing for Pool and Spa Combination.
The diagram to the right shows a simplified version of a
standard plumbing setup for a pool and spa that share
the same filter pump, filter, and heater. The Intake and
Return JVAs (Jandy Valve Actuators) turn simultaneously
so when the Spa button is pressed on the AquaLink®RS
Controller, water circulation switches between pool and
spa. Consult the JVA Installation Manual to ensure that the
Jandy Valve Actuators are "in synch" and rotate properly.
Please also note that if you have a pool only or a spa only,
the diagram does not apply, and if your pool and spa have
separate sets of equipment, you should install an
AquaLink®RS 2/6 model Controller, designed to control
separate equipment sets.
Non-Booster Pump Pressure-Side
The diagram to the right shows standard
plumbing for a non-booster pump pressure-side
pool cleaner (i.e., Ray-Vac, Energy Sweep, etc.) To
control this cleaner, control water circulation to
the cleaner by using a Cleaner JVA (see right).
Plumb a three-port valve between the filter pump
and the filter. Install a 2-port valve to open and
close the cleaner line, and after the valve, install a
Jandy Energy Filter to provide filtration (as the
main filter has been bypassed). Mount a JVA on
the 2-port valve and set the cam(s) (see JVA
Manual) to turn 90º. Please note the installation of
a non-booster pump pool cleaner requires
moving DIP Switch #1 to the ON position.
Pool Cleaner Plumbing.
Non-Booster Pump Cleaner Plumbing
Pool & Spa Plumbing

7
BasicPlumbing
Booster Pump Pool Cleaner Plumbing.
If you are using a Booster Pump Pool cleaner, plumb the
booster pump so its suction side is connected to the
pool return after the heater and as close to the ground
as is practical (see diagram to the right). Please note
that the installation of a booster pump pool cleaner
requires moving DIP Switch #1 to the ON position.
Solar System Plumbing
Booster Pump Plumbing
Solar System Plumbing.
If a solar system is part of the equipment, plumb the solar
feed and return lines between the main filter and the
heater (see diagram to the right). Please be sure to make
provision for solar drain down. Use a Jandy Non-Positive
Seal Valve to provide drain down. Plumb in a solar
booster pump if needed.
NOTE: A Jandy (10K) Solar Sensor will be needed for
solar system control. The sensor should be located near
the solar panels and connected to the Power Center by
18 AWG wire.
If a solar booster pump is installed, follow the
wiring diagram on page 34 for more information.

8
•Light Dimming (12 VAC and 120 VAC)
1000 Watts incandescent
PowerCenterConnection-HighVoltage
Mount Power Center.
All electrical equipment, except for the Four Function Switch, must be five feet or more from pool /spa and comply with all
national, state and local codes. If using a Jandy Power Center without built-in breaker compartment, install electrical supply
panel with separate breakers for each load. Make sure that motors on equipment have built-in thermal protection. Use the
grounding terminal, provided within the Power Center, for grounding. Bond all equipment, including the Power Center, to
earth ground. (Install to provide drainage for all electrical components.) Mount no less than 5 feet from pool/spa and at least
5 feet off the ground. In areas where lightning strikes are common, install an external surge suppression device.
RunConduit/WirefromSupplyPanel.
Depending on the amount of equipment you want to control, run ¾" or larger conduit from the power supply panel to the
lower side of the Power Center. If you are using the Power Center with built-in breaker compartment, wire power to the
appropriate breakers. Pull in appropriate wire for equipment. Each piece of equipment requires its own high voltage relay.
Connect 120 volts to the power supply terminals. Connect equipment ground(s).
WireRelay(installadditionalrelaysifneeded).
For each piece of 240 volt equipment to be controlled, wire line power to the two line terminals of a Relay and wire
equipment to the two load terminals. For each piece of 120 volt equipment, wire power to a line terminal and the equipment
to a load terminal. Order and install optional relay modules if additional equipment is to be installed. Wire all relays and feed
the relay plugs through the holes into low voltage compartment. Plug in relay coils using the wiring diagram on page 34 as
aguide.
SpecialRelays.
If you have a two-speed pump, you must order and install a two-speed relay. If you wish to install light dimming, you must
order and install a light dimming relay.
Contact Ratings: Do not exceed any rating.
•Standard Relay
3 H.P. at 240 VAC
1½H.P.at120VAC
25 Amps
1500 Watts
•Two Speed
2 H.P. at 240 VAC
1 H.P. at 120 VAC
20 Amps

9
PowerCenterConnection-HighVoltage
*This diagram shows wiring for a standard relay. For light dimming or two-speed
operation, follow wiring instructions included with those relays.
Power Center Connection - High Voltage

10
Low Voltage Wiring (Power Center P.C. Board)
If connecting more than 2 items to the RS Power Center red 4 pin terminal bar, a multiplex PCB is required.
PowerCenterConnection-LowVoltage

11
PowerCenterConnection-LowVoltage
1. Connect 24V AC Power to Bezel and Mount Bezel.
Plug the orange 24V AC power plug from the transformer into its 3-pin terminal on the back of the Low Voltage Bezel,
feed battery wires to front right and connect the Bezel to the Power Center with the screws provided. DO NOT INSTALL
BATTERY.
2. MountJVAs&runwirestoPowerCenter.
Refer to the JVA manual to install JVAs. Run JVA wires back to the low voltage compartment of the Power Center,
through low voltage raceway, and plug the JVAs into their sockets. Make certain to plug Intake JVA into Intake socket,
and Return JVA into Return Socket (see diagram). NOTE: Do not coil JVA cable inside Power Center. To shorten cable,
remove JVA lid and undo cable wire nuts. Shorten, strip, and reconnect.
3. Connect ControllerCable toP.C. Board.
Make provision for Cable to be run between the Control Panel and the Power Center. Where cable runs underground or
in concrete, it must be run in conduit. Never run high voltage and low voltage cable in the same conduit. Pull
Controller Cable into low voltage compartment. Strip back cable jacket 6". Strip each wire ¼" and connect to the red 4-
pin connector. Wire according to the Power Center P.C. Board Wiring Diagram. A Multiplex Kit may be required if
connectong more than two wires to a 4-pin connector.
4. Install Spa Side Switch or SpaLink RS and connect to Terminals.
Spa Side Switch or SpaLink RS (optional)
Follow the instructions included with the Spa Side Switch or SpaLink RS to mount and wire.
NOTE: If more than one Spa Side Switch will be installed, an additional interface board is required,
Dual Spa Side Switch kit, Part No. 6588. For the SpaLink RS, a Rev. G or newer PPD is required and if more than one
SpaLink will be installed, a Multiplex Kit is required.
Radio Remote, and TeleLink Telephone Interface
To install, follow the instructions included with these optional items.
5. Connect Sensors to Terminals.
WaterTemperatureSensor.
Drill 3/8" hole in pipe between filter pump and filter. Insert sensor and use clamp (provided) to hold in place. Remove
the 10-pin terminal bar (green) from the PCB. Connect sensor wires to the 10-pin terminal bar as shown on the wiring
diagram on page 34.
Freeze/AmbientAirTemperatureSensor(required).AirSensormustbeinstalled.
Install sensor outdoors where it will be subjected to shaded air temperature (not in sun). Connect sensor wires to the
10-pin terminal bar as shown on the wiring diagram. Connect other sensors to 10-pin terminal bar as shown on wiring
diagram.
SolarTemperature Sensor(optional)
Install sensor adjacent to solar panels. Connect sensor wires to the 10-pin terminal bar as shown on the wiring
diagram. Connect other sensors to 10-pin terminal bar as shown on wiring diagram. NOTE: If a solar sensor is not
installed, the solar button can be labeled and used as an auxiliary.
6. Connect heaterto LowVoltage Terminal.
(Allgas heatersor heatpumps withthermostatic circuitryof 24VAC orless)
a. If you are connecting a Low Voltage heater, connect two 18-gauge wires, designed for use in hot environments, to the
proper terminals on the 10-pin terminal bar. If you are connecting a High Voltage heater (not electronic ignition), you must
instead connect the heater to a high voltage relay on the Power Center.
b. Bring the 2 heater wires from the P.C. Board over to the heater and wire nut in series with heater circuitry as if you
were wiring a fireman's switch or a heater delay.
c. Turn the heater thermostat to maximum.
d. Turn heater toggle switch on.
e. Do not disconnect high limit or pressure switches.
NOTE: For connection to specific heater brands, please see the Heater Connection Installation Guidelines.
ForLaars LXHeater(IftheAquaLinkRShasRev."I" orhigher theLX musthave amicroprocessor
with Rev. "C-10" or higher)
a. Remove LX GUI from the heater and turn the GUI over.
b. Run 4 conductor cable (red, black yellow, green) from the LX GUI red 4 pin terminal bar to the RS Power Center red 4
pin terminal bar.
c. If connecting more than 2 items to the RS Power Center red 4 pin terminal bar, a Multiplex Kit is required.
d. Replace the LX GUI on the heater.
7. Connect AllEquipmentto P.C.Board.
Connect the high voltage relay plugs into their appropriate sockets according to the wiring diagram located on the
inside of the Power Center door or on page 34 of this manual.
8. Set DIP Switches.
See page 14 to set DIP Switches for optional operation features.
9. Turn onpower tosystem, thenconnect 9-voltbattery. (Do not connect battery if power is not supplied to unit).
10. Install Power Center Faceplate.
Use the screws provided to install and secure the Power Center Faceplate on to the Power Center.

12
AuxiliaryPowerCenters
Auxiliary Power Center Installation
You may have up to four (4) power centers on one (1) AquaLink RS system.
The four conductor RS485 cable going to the 4-pin (red) terminal bar on the auxiliary power centers can be wired either from
the main power center, the indoor control panel or an optional accessory.
The auxiliary power centers can be located anywhere on the property, depending upon convenience and what devices are
being controlled.
AUX B1 through B8, C1 through C8, and D1 through D8 on the indoor control panel operates the relays located in the
auxiliary power centers. AUX B1 through B4 JVA sockets are energized when AUX B1 through B4 relay sockets are
energized.
Note: If you are installing more than one accessory board, order and use a Jandy Multiplex Kit (p/n 6584). Never put more
than two wires into each of the pins of the terminal bar. Use the multiplex board whenever more than two of the 4-wire cabes
are being joined.

13
AllButtonControlPanelInstallation
Prepare Control Panel Site.
With the aid of the homeowner, find the best location for the Control Panel. To ensure the Control Panel is level, hold the
Mounting Bracket against the wall and mark the top inside of the upper right screw hole. Using this mark as a guide, place a
level against the mounting wall and draw a horizontal line 4¼inches to the left. Now use the Bracket as a template to mark
holes for mounting screws (lining up the holes to the horizontal line). Drill ¼" holes for each screw and insert plastic anchors.
Mount Bracket and secure in place.
Connect Control Panel Cable to Control Panel.
Pull Control Panel Cable through the hole in the Mounting Bracket. Strip back cable jacket 6". Remove the terminal bar from
the Control Panel P.C. Board, and wire Control Panel cable according to the wiring diagram on the back of this manual.
Connect the terminal bar to the Control Panel. Mount the Control Panel by putting the top in place first, then swinging the
bottom in until the snap catches.
NOTE:Ifyouareinstalling
multipleIndoorControlPanels,
you must "address" each one
differently.Refertoinstructions
onfollowingpagefor
additionalControlPanel(s).
Control Panel (Back View)
Multiple Control Panels
W2
W1
Cancel
Delay

14
AquaLinkRSControlPanelJumperSetting:Movethesejumpers
only when installing more than one Control Panel on a system.
Thejumpersare usedtogiveeachControlPanelaunique
system address. If you are using this Control Panel to replace an
existing one, ensure the jumper settings match those on the one
beingreplaced.
TheAquaLinkRS allowseach system tosupport amaximumof fourIndoor ControlPanels.The ControlPanels
may be wired "In Series", starting from the first Control Panel (solid line), or each may be wired individually from
the AquaLink Power Center (dotted line), or a combination of the two. To accomplish the "In Series" wiring
scheme, you may "double-up" wires in the red terminal bars, but never put more than two wires into each pin of
the terminal bars. If you need to join more than two of the 4-wire cables, order and install Jandy Part # 6584
(Multiplex PCB Kit).
OR
OR
OR
All
Button
Control
Panel
FirstControlPanel ThirdControlPanel
SecondControlPanel FourthControlPanel
W2
W1
Micro
Processor
Red 4 pin
connector
Jumpers
OneTouch
Control
Panel
SetupforMultipleControlPanels
TM
TM
TM

15
DIPSwitchSettings
DIP #1 ON --
--
- —
AUX 1 CONTROLS POOL CLEANER:
If you installed a booster pump for a pool cleaner, the relay coil for the booster pump must be plugged into the AUX 1 relay
socket. If a non-booster pump cleaner is installed, plug the JVA into the cleaner JVA socket. Turn on DIP Switch #1.
•Main filter pump turns on whenever cleaner turns on.
•Cleaner will not turn on until filter pump has been on for 3 minutes (to ensure priming of system).
•Cleaner turns off when water circulation is to spa.
•Cleaner turns off when spa overflow feature is activated.
•Cleaner turns off for 3 minutes when solar is activated (to ensure air is purged from system).
•AquaLink RS Controller Display reads “CLEANER”rather than “AUX 1”.
DIP #2 ON --
--
- —
AUX 2 CONTROLS LOW SPEED OF FILTER PUMP:
Turn this switch on if you want to control both speeds of a two-speed filter pump. With this switch on, the filter pump button
on the AquaLink RS Controller will control high speed and the AUX 2 button will control low speed. IMPORTANT: You must
also install a Jandy Two-Speed Relay, purchased separately. Install the Relay according to its installation instructions.
DIP #3 ON --
--
- —
AUX 3 CONTROLS SPA SPILLOVER (OPERATES WITH POOL/SPA COMBINATION UNITS):
Turn this switch on, and when the AUX 3 button on the AquaLink RS Controller (or Spa Side Switch) is pressed, the Return
Valve Actuator will rotate to spa circulation. Because the Intake Valve Actuator does not rotate, the spa will fill with water
and overflow into the pool. NOTE: Leave AUX 3 relay socket empty.
DIP #4 ON -
HEATER COOL DOWN DISABLED:
Turn this switch on to disable the heater cool down safety feature on the AquaLink RS. WARNING: Turn this DIP Switch on
only if you are using an electric heater or heat pump that does not retain residual heat. If you are turning this switch on for
service purposes, be sure to turn it back off after you have finished.
DIP #5 OFF - FACTORY USE ONLY:
This switch is used for calibration by Jandy technicians only, and to momentarily display the solar temperature.
Please leave this switch in the off position.
DIP # 6 ON - Change Spare AUX. to active when Filter Pump is on and system is in spa mode (pool/spa combination
units only).
DIP #7 - —
NOT USED.
DIP #8 ON -
HEAT PUMP INSTEAD OF GAS HEATER:
Turn this switch on if you have installed a heat pump instead of a gas heater.
Use a pen or small tip screwdriver to slide switch
to the right to turn on.

16
OneTouchControlPanelInstallation
This document gives instructions for installing the Jandy
AquaLink®RS OneTouch Indoor Control Panel (surface
and flush mount). The instructions must be followed
exactly. Read through the instructions completely before
starting the procedure.
A.A.
A.A.
A. Installing the Flush MountInstalling the Flush Mount
Installing the Flush MountInstalling the Flush Mount
Installing the Flush Mount
Control BoxControl Box
Control BoxControl Box
Control Box
1. Determine the location of the controller. Be sure there is
nothing behind the sheetrock where the controller will be
mounted.
2. Place Template 1 in the location chosen for the control
panel, cut a square in the sheetrock. Be careful to cut
accurately with a razor knife or equivalent. Do not make
the square oversized.
3. Run the 4 conductor wire, and pull it through the hole in the
wall.
5 Pull the 4 conductor wire through the large hole in the flush
mount box. Then push the box into the wall.
6. Depending on what size sheet rock (5/8" or 1/2") determine
which side of the cleat to be used.
a. For 1/2" sheet rock face the large side of the cleat
towards you (see Fig. 2).
b. For 5/8" sheet rock, face the small side of the cleat
towards you (see Fig. 2).
7. Insert a screw through the screw boss. Put a cleat into the
top “U”shaped hole (with the orientation determined in
Step 4). Thread the screw into the cleat. Hand tighten with
a Phillips screwdriver. Repeat with second screw and
cleat using the bottom hole. (see Fig. 3 & 4).
Slide cleat
intoslot
opening,
thread screw
intocleat.
Lower flanges of
cleat prevent the
part from falling
throughthe
flushmountbox.
Upper flanges of
cleat provide a
snap fit with top
wall of box.
This allows the
screw to be
insertedwithout
havingtohold
the cleat
Figure4. CleatLocation
ThisSideand
Tip for 5/8"
Sheetrock
UpperFlange
ThisSideand
Tip for 1/2"
Sheetrock
LowerFlange
Figure2. CleatOrientation
SlotOpenings
ThroughTop,
Bottom,and
Back Walls
Screw
Bosses
Figure3. CleatLocation
Flush
Mount
Box
Sheetrock
(1/2" or 5/8"),
with 4" Square
Cut Out
Outside Wall Surface
Figure1. FlushMountBoxPositionedinSheetrock

17
8. Place the PCB w/LCD and buttons back into the box. Be
sure the rubber washer is between the screw head and the
PCB. Hand tighten the screws. Snap the cover over the
box.
B.B.
B.B.
B. Installing the Surface MountInstalling the Surface Mount
Installing the Surface MountInstalling the Surface Mount
Installing the Surface Mount
Control BoxControl Box
Control BoxControl Box
Control Box
1. Determine the location of the controller. Be sure there is
nothing behind the sheetrock where the controller will be
mounted.
2. Place Template 2 in the location chosen for the controller,
mark the holes for drilling. Drill the holes to fit the sheet
rock anchors (recommended drill bit size is 3/16"). Install
the sheet rock anchors. Drill the 1¼” hole for the 4 conduc-
tor wire.
3. Pull the 4 conductor wire through the 1¼” hole in the
surface mount box. Mount the box to the wall using the
screws provided with the product.
4. Place the PCB w/LCD and buttons back into the box. Be
sure the rubber washer is between the screw head and the
PCB. Hand tighten the screws. Snap the cover over the
box.
5. Figure 6 shows the locations of the Cancel Button and the
Reset Button on the OneTouch PCB.
OneTouchControlPanelInstallation
Face Plate
FlushMount
Box
Surface Mount
Box
PCBw/LCD&
Buttons
Face Plate
PCBw/LCD&
Buttons
Figure5. AquaLink RS One Touch (surface and flush mount) Assembly
Figure6. Location, CancelDelayand ResetButtons
JANDY AquaLink RS
FILTER PUMP OFF
AIR 79
01/31/00 MON
6:00 PM
EQUIPMENT ON/OFF
ONETOUCH ON/OFF
MENU /HELP
ResetButton
CancelDelay

18
OneTouchInstallationTemplates
Drill Thru 3/16"
(3)Places
Drill Thru 1¼”
Figure8. Surface Mount Template
Template 2- Surface Mount
WARNING
Do not cut
thesheetrock
any bigger than
the template.
Template 1- Flush Mount
4.03"
4.03"
Figure7. FlushMountTemplate

19
Basic Programming.
To set a particular piece of equipment to turn on and off at
predetermined timeS, press the MENU button, scroll to the PROGRAM
MENU, press ENTER, and then press the button for the equipment that
you want to program. The Controller Display will ask you to enter the
day. Use the arrow keys <—>* to select, and press ENTER. The display
will now ask you for the starting time and ending time. Repeat this
process for each piece of equipment that you wish to program. You may
enter as many programs as needed for each piece of equipment.
Set the Time.
To set the time, press the Menu button. Use the arrow keys to scroll to
the SET TIME
Menu and press ENTER. Now scroll to the correct year
and month and press ENTER. Scroll to the correct hour and minute and
press ENTER.
Depending on the age of the AquaLink RS, the following items can be
found either in the Main Menu or in a Sub Menu under SETUP:
Press the MENU button, scroll to the SET TEMP Menu item and press
ENTER. Use the arrow keys to select POOL or SPA and again, press
ENTER. Once you have selected which heater to set the temperature for,
use the arrow keys to move to the desired temperature, and press
ENTER, to complete.
Label Auxiliary Functions.
To label Auxiliary functions, press the MENU button. Scroll to SYSTEM
SETUP and press ENTER, then scroll to the LABEL AUX
Menu and
press ENTER. Press the button to be labeled (example: AUX 1). Scroll
to the desired label and press ENTER. Repeat for all functions.
NOTE 1: The labels "TIMEDAUX", "AIR BLOWER", and "FILL LINE" are
30 minute timed circuits. NOTE 2: If DIP switch 1, 2 or 3 are on,
Auxiliaries 1, 2 and 3 are labeled CLEANER, LOW SPEED and
SPILLOVER respectively and cannot be relabeled.
Set Spa side Switch or SpaLink RS Functions.
The buttons on the Spa Side Switch or the SpaLink RS may be set to
control any functions the home owner wishes. To the right is a list of
default settings for the Switch. If you wish to change which functions the
Switch(es) control, first press the MENU button. Scroll to SYSTEM
SETUP and press ENTER, then scroll to FOUR FUNCTION SWITCH
(SPA SWITCH on Rev. G or higher) or SPA LINK and press ENTER.
Follow the prompts to assign each REMOTE button.
Set Freeze Protection.
AquaLink RS Freeze Protection senses when the air temperature falls
below 38ºF and automatically turns on the filter pump to circulate the
water, thus preventing freezing of pipes. To add freeze protection to
other equipment, press the MENU button. Scroll to SYSTEM SETUP
and press ENTER, then scroll to FRZ PROTECT
and press ENTER.
Press the button for the equipment you want to protect.
Assign JVAs.
The Assign JVAs Menu lets you assign Jandy Valve Actuators (JVAs)
to any auxiliary button. This means that whenever you press that
auxiliary button, a valve turns. On pool/spa combination models,
there are two JVA Valve Actuators that can be assigned to auxiliary
buttons: the Cleaner JVA and the Solar JVA. On pool only/spa only
models, there are four JVAs available. The AquaLink RS installer
must set up these JVAs for this feature to operate correctly.
Assigning JVAs lets the owner control certain features like
diverting water to a waterfall or bank of spa jets.
Set the Temperature.
AllButtonControlPanelProgrammingandSystemDefaults
Default Time - 1:00 P.M.
Default Day - MONDAY
Default Date - 01/31/00
Default Time
How to assign values:
1. Press theMENU button. Use the FORWARD and BACK
buttons to move to SYSTEM SETUP. Press ENTER. Use
FORWARD button to move to ASSIGN JVAs Menu and
press ENTER. The AquaLink RS display will read
CLEANER JVA <—>*. If both JVAs are being used, you
will not be able to use this Menu.
2. Use the FORWARD and BACK arrows to choose
among the JVA's listed. When the JVA you want to assign
to an auxiliary is displayed, press ENTER.
3. The AquaLink RS display will read SELECT AUX TO
ASSIGN JVA TO. Press the button of the Auxiliary
that you want to activate the JVA.
Default Temperature
Default Pool Temp - 80ºF.
Default Spa Temp - 102ºF.
Default Temperature
Button 1 - Spa (Filter Pump)*
Button 2 - Spa Heater (Temp1)*
Button 3 - AUX 1
Button 4 - AUX 2
* pool/spa only controls.
Default Switch Setting
Default Freeze Protect. Settings
NOTE: If you select
SPA
to be freeze protected,
water circulation will switch between pool and spa
every 30 minutes during freezing conditions once
freeze mode is active.
FILTER PUMP: Freeze Protection ON. ALL OTHER
EQUIPMENT, Freeze Protection OFF.

20
AllButton Control Panel ResetandDisplayMessages
Reviewing:
To review equipment, press the MENU button, then use the FORWARD arrow to scroll to the REVIEW menu. Press ENTER,
use the arrows to scroll to the item you wish to review, and press ENTER again.
Canceling Items:
If you make a mistake in programming or you want to change, for example, the ON/OFF times for a specific device, you can
cancel programs for that piece of equipment. For example, to CANCEL A DIMMER, press the CANCEL button; use the
forward and back buttons to advance to DIMMERS and press ENTER. The AquaLink RS display will prompt to select an Aux.
Press the button of the Auxiliary for which you want to cancel the dimmer.
If you want to cancel a JVA assignment, first press the CANCEL button (if no JVAs are assigned, you cannot use this
function). Use the FORWARD and BACK arrows to advance to JVA ASSIGNS and press ENTER. The AquaLink RS display
will read CLEANER JVA. Use the FORWARD and BACK arrows to toggle between JVAs to cancel. When the JVA
assignment that you want to cancel is displayed, press ENTER. The AquaLink display will read PRESS ENTER TO CANCEL
JVA ASSIGNMENT,
or CANCEL TO ABORT. Press ENTER to cancel the JVA assignment, or press CANCEL to abort.
Resetting the System:
To remove all labeling, programming, assignments, and temperature settings, press the MENU button, scroll to CLEAR
MEMORY and press ENTER twice.
Power Center Service Switch:
AUTO Mode (automatic):
The Controller has complete control of all functions. All programmed settings will operate. All safety delays and equipment
protection interlocks are operational.
SERVICE Mode:
The Power Center has complete control of all functions. Service Mode must be turned On/Off at the Power Center. No
programmed settings will operate. CAUTION: In service mode, the safety interlocks for equipment protection are overridden.
TIMEOUT Mode:
The Power Center has complete control for 3 hours. After 3 hours, the system will return to Auto Mode. Programmed On/Off
times will be overridden during the 3 hours. After the three hour "time-out", the system will resume any programmed times
that were overridden.
BatteryBack-Up:
A nine-volt battery is located at the Power Center. Do not install battery in the Power Center until system is ready to operate.
Battery will drain if power is left off. Review DIAGNOSTICS in the SYSTEM SETUP section of the Menu. The DIAGNOSTICS
will indicate when the battery needs replacement.
LightDimmer:
Dimmers can be set at 25%, 50%, 75% or 100%, depending upon the amount of light desired, by pressing the AUX assigned
as a dimmer and using the arrow <—>* buttons to dim or brighten. Once desired brightness is achieved, press ENTER.
Press AUX to turn off.
NOTE: When light is turned back on, it will automatically return to brightness last set.
From the Spa Side Switch or SpaLink RS, light dimming operates as follows:
When a button assigned to a light dimming auxiliary is pressed, the light will turn on at full brightness, and each press of
the button will decrease brightness 25% until light is off.
Special Note to "Start-up Person":
The AquaLink RS allows you two options for operating the pool equipment for the first day of operation:
Option #1 - Once all programming of equipment is completed, go to the Power Center Service Switch. Push the Switch
three times which moves from "AUTO" to "SERVICE" to "TIME-OUT" and finally back to "AUTO". The
AquaLink RS will now "look back" (review) all programs and turn on any equipment which is programmed to
be on. Close up system; it will now operate as programmed.
Option #2 - If you want the filter pump or cleaner to operate continually for the first day, leave the Power Center Service
Switch in "AUTO" mode. Go to the indoor controller and press the AUX buttons for the equipment you want
to run. The equipment activated will now run continuously, ignoring the first programmed off time, and turn
off at the programmed off time for the next day.
Other manuals for AquaLink RS
9
This manual suits for next models
3
Table of contents
Other Jandy Control Panel manuals

Jandy
Jandy AquaLink RS User manual

Jandy
Jandy AquaLink RS One Touch 7953 Parts list manual

Jandy
Jandy AquaLink RS User manual

Jandy
Jandy LEGACY LRZE User manual

Jandy
Jandy AquaLink RS Programming manual

Jandy
Jandy AquaLink RS User manual

Jandy
Jandy AquaLink RS User manual

Jandy
Jandy AquaLink RS User manual