800-CONModules www.janitza.com
16
4. Mounting
CAUTION
Disregard of the installation instructions may
cause property damage or personal injury!
Disregard of the installation instructions may cause
damage to your basic device with module or destroy
it and/or may also result in personal injury.
·In addition to the installation instructions for
your module, also observe the installation
instructions for your basic device, in particular
the safety and warning information.
·Before installing modules
-Disconnect the supply of power to the system!
-Secure it against being switched on!
-Check to be sure it is de-energized!
-Ground and short circuit!
-Cover or block off adjacent live parts!
·Provide adequate air circulation in your installa-
tion environment and cooling, as needed, when
the ambient temperatures are high.
· Return defective modules to Janitza electronics
GmbH in accordance with the shipping in-
structions for air or road freight (complete with
accessories).
· All usage information is also available as a
download at www.janitza.com.
4.1 Mounting the 1st transfer module with out-
put bus connector
While observing the mounting instructions for your
basic device or the connected module (e.g. check
the bus connector mounting!), mount the 1st 800-
CON transfer module with output bus connector
when the system is disconnected from the power
supply as follows:
INFORMATION
· The following module assembly sequence must
be observed!
· Always mount the components of your JanBus
system starting from the output bus connector
to the input bus connector. This will avoid an
incorrect connection of remote JanBus sys-
tems! Cf. Sect. “6.1 Data transfer with 800-CON
module” on p. 24.
· Plan for sufficient space in your installation envi-
ronment, including for the bending radius of the
data cable.
· Use end brackets and shield clamps with strain
relief to set up your measurement device and
module topology on a suitable DIN rail (for DIN rail
types, see Sect. “9. Technical data” on p. 27).
System limits:
· The maximum bus length (JanBus - proprietary)
for setting up measurement device and module
topologies can be found in Sect. “9. Technical
data” on p. 27.
· Before mounting, please check the number of
suitable modules for your measurement-device
and module topology based on the respective
usage information. Do not exceed the max-
imum number of module slots of the basic
device! The 800-CON transfer modules (set of
2) do not occupy a slot!
· For recommended data cables, refer to Sect. “6.2
Data cable for connecting the 800-CON transfer
modules” on p. 25.
ATTENTION
Improper handling may cause damage to the
module and result in material damage!
The contacts of the bus connectors (JanBus interface)
can bend or break off and destroy the bus connector.
·Never touch or manipulate the contacts of the
bus connector!
·Never force the bus connector into the module!
·When handling, transporting and storing the
module, protect the contacts of the bus con-
nector!
Output bus connector 1TE
Fig.: Output bus connector for the 800-CON transfer module at
the output of a series of measurement devices and modules.
Input bus connector 1TE
Fig.: Input bus connector for the 800-CON transfer module at the
input of a series of measurement devices and modules.
Please note before installing the module:
The scope of delivery of the 800-CON transfer
modules (set of 2) includes an input and an out-
put bus connector, so that each transfer module
can be used with the corresponding bus connec-
tor at the output or input of a series of measure-
ment devices and modules.