Jaquet FT 3000 User manual

JAQUET AG, Thannerstrasse 15, CH-4009 Basel
Tel. +41 61 306 88 22 Fax +41 61 306 88 18
FT 3000 Speed measurement system
3-channel speed control and overspeed protection
System documentation FT 3000 :
•Operating instructions FT 3000
•Operating instructions sensor
•Rack 19 ¨ description
•Bloc function description
•System configuration
•Connection diagram
•IEC 61508 certificate

Operating Instructions FT 3000JAQUET AG
377E-63917 Rev 4.00 page 2 of 47
Table of contents
1 THE REDUNDANT OVER SPEED PROTECTION CONCEPT :.............................................................. 5
2 SAFETY WARNING..................................................................................................................................... 7
3 APPLICATIONS............................................................................................................................................ 7
4 CONSTRUCTION......................................................................................................................................... 7
5 FRONT PANEL DESCRIPTION.................................................................................................................. 8
5.1 FTFU 3024............................................................................................................................................. 8
5.2 FTV 3090 ............................................................................................................................................... 8
5.3 FTK 3072............................................................................................................................................... 9
5.4 FTW 3013............................................................................................................................................... 9
5.5 FTBU 3034 .......................................................................................................................................... 10
6 SPECIFICATIONS...................................................................................................................................... 11
6.1 STATISTICS............................................................................................................................................ 11
6.2 IEC 61508-2-3 SPECIFICATIONS :.......................................................................................................... 11
6.3 TECHNICAL DATA OSPS........................................................................................................................ 11
6.4 TECHNICAL DATA TCCC........................................................................................................................ 16
7 PRINCIPLE OF OPERATION.................................................................................................................... 16
7.1 MEASURING SYSTEM.............................................................................................................................. 16
7.2 MEASURING PRINCIPLE .......................................................................................................................... 16
7.2.1 Standardising the measured value......................................................................................... 16
7.2.2 Speed monitor............................................................................................................................ 16
7.2.3 Frequency measurement (Period measurement principle) ................................................ 16
7.2.4 Acceleration measurement...................................................................................................... 19
7.2.5 Limit value control..................................................................................................................... 21
7.2.6 Limit value time control............................................................................................................ 21
7.3 MONITORING FUNCTIONS........................................................................................................................ 21
7.3.1 Supply.......................................................................................................................................... 21
7.3.2 Monitoring of internal voltages................................................................................................ 21
7.3.3 Sensor monitoring..................................................................................................................... 21
7.3.4 System monitoring.................................................................................................................... 22
7.3.5 Module OK message................................................................................................................. 22
7.3.6 Fault condition ........................................................................................................................... 22
7.4 DIRECTION OF ROTATION DISCRIMINATOR............................................................................................... 22
7.5 RELAY CONTROL.................................................................................................................................... 22
7.6 TEST FREQUENCY GENERATOR .............................................................................................................. 23
Operating Instructions
377E-63917
V 4.00 20.12.04
FT 3000

Operating Instructions FT 3000JAQUET AG
377E-63917 Rev 4.00 page 3 of 47
7.7 TEST...................................................................................................................................................... 23
7.8 FREQUENCY OUTPUTS ........................................................................................................................... 23
7.9 LAMP TEST............................................................................................................................................. 24
7.10 MESSAGE ACKNOWLEDGEMENT............................................................................................................. 24
7.11 BINARY INPUTS ...................................................................................................................................... 24
7.12 PARAMETER ENTRY................................................................................................................................24
7.13 SIGNAL MONITORING.............................................................................................................................. 24
8 INSTALLATION.......................................................................................................................................... 26
8.1 GENERAL............................................................................................................................................... 26
8.2 IEC 61508-2-3 SPECIFIC INSTALLATION RULES..................................................................................... 26
9 SETTING PARAMETERS AND OPERATION......................................................................................... 27
9.1 SOFTWARE CONCEPT............................................................................................................................. 27
9.1.1 Process parameter list.............................................................................................................. 27
9.1.2 Configuration parameter list.................................................................................................... 27
9.1.3 Service parameter list............................................................................................................... 29
9.2 PC COMMUNICATIONS............................................................................................................................ 29
9.2.1 PC system requirements.......................................................................................................... 29
9.2.2 PC software installation............................................................................................................ 29
9.2.3 Optimisation...............................................................................................................................30
9.2.4 Setting the display interval....................................................................................................... 30
9.2.5 Protection of configuration parameters................................................................................. 30
9.2.6 Protection of process parameters .......................................................................................... 30
9.2.7 Reading and writing parameters............................................................................................. 30
9.2.8 Parameter printout..................................................................................................................... 30
9.2.9 Display of current measured data........................................................................................... 30
9.3 SETTING PARAMETERS........................................................................................................................... 31
9.3.1 System settings ......................................................................................................................... 31
9.3.2 Sensor monitor .......................................................................................................................... 32
9.3.3 Analog outputs........................................................................................................................... 32
9.3.4 Limit values................................................................................................................................. 32
9.3.5 Test values.................................................................................................................................. 33
9.3.6 Parameter enable....................................................................................................................... 33
9.3.7 Password .................................................................................................................................... 33
9.4 OPERATING BEHAVIOUR......................................................................................................................... 33
9.4.1 Power up..................................................................................................................................... 33
9.4.2 Measurements............................................................................................................................ 34
9.4.3 Response to sensor failure...................................................................................................... 34
9.4.4 Behaviour during system alarm.............................................................................................. 34
9.4.5 Response to mains failure........................................................................................................ 34
9.5 FREQUENCY MEASUREMENT CALIBRATION ............................................................................................. 34
9.5.1 Calibration tools......................................................................................................................... 35
9.5.2 Factors influencing accuracy .................................................................................................. 35
9.5.3 Calibration rules......................................................................................................................... 35
9.6 CALIBRATING THE SENSOR MONITOR...................................................................................................... 36
9.6.1 Factors influencing accuracy .................................................................................................. 36
9.6.2 Calibration rules......................................................................................................................... 36
10 MECHANICAL CONSTRUCTION......................................................................................................... 37
11 CIRCUIT DESCRIPTION........................................................................................................................ 39
11.1 FTFU 3024 MOTHERBOARD AND INPUT CARD....................................................................................... 39
11.1.1 Frequency measurement.......................................................................................................... 39
11.1.2 Speed monitors.......................................................................................................................... 39
11.1.3 Micro controller.......................................................................................................................... 39
11.1.4 Supply.......................................................................................................................................... 39
11.1.5 Reset and non-maskable interrupt (NMI)............................................................................... 40
11.1.6 Input amplifier ............................................................................................................................ 40
11.1.7 Sensor monitoring..................................................................................................................... 40
11.1.8 Module monitoring .................................................................................................................... 41
11.1.9 Relay outputs ............................................................................................................................. 41

Operating Instructions FT 3000JAQUET AG
377E-63917 Rev 4.00 page 4 of 47
11.1.10 LIMIT LED’s............................................................................................................................. 41
11.1.11 Frequency generator............................................................................................................. 41
11.1.12 Frequency outputs ................................................................................................................ 41
11.1.13 Binary inputs .......................................................................................................................... 41
11.1.14 Test .......................................................................................................................................... 41
11.1.15 Direction of rotation discriminator...................................................................................... 42
11.1.16 Lamp test ................................................................................................................................42
11.2 FTW 3013 - A/D CONVERTER AUXILIARY MODULE................................................................................. 42
11.2.1 Supply.......................................................................................................................................... 42
11.2.2 Analog outputs........................................................................................................................... 42
11.3 FTV 3090 RELAY CARD ........................................................................................................................ 42
11.3.1 Supply.......................................................................................................................................... 42
11.3.2 Relay outputs ............................................................................................................................. 42
11.4 FTK 3072 COMMS MODULE .................................................................................................................. 42
11.4.1 Rack bus ..................................................................................................................................... 42
11.4.2 RS 232 interface......................................................................................................................... 43
12 MAINTENANCE...................................................................................................................................... 44
12.1 PERIODIC TEST....................................................................................................................................... 44
12.1.1 Description ................................................................................................................................. 44
12.1.2 IEC 61508-2-3 specifications.................................................................................................... 44
12.2 TROUBLE SHOTING :...............................................................................................................................45
12.2.1 Procedure for the OSPS ........................................................................................................... 45
12.2.2 Procedure for the TCCC :......................................................................................................... 46
12.2.3 IEC 61508-2-3 specifications.................................................................................................... 46
12.3 MODULE EXCHANGING :......................................................................................................................... 46
12.3.1 General........................................................................................................................................ 46
12.3.2 IEC 61508-2-3 specifications :.................................................................................................. 47
13 STORAGE............................................................................................................................................... 47
14 WARRANTY............................................................................................................................................ 47
15 DRAWINGS............................................................................................................................................. 47

Operating Instructions FT 3000JAQUET AG
377E-63917 Rev 4.00 page 5 of 47
1 The Redundant Over Speed Protection Concept :
Speed
Measurement
1
Speed
Measurement
2
Speed
Measurement
3
PSU 1 PSU 2
2 of 3
Module
commissio
ning
Customer specific control logic, 1/3, 2/3 …
Secure monitoring
even if modules are
exchanged during
operation
1. Measurement
Protection
Safety
Availability
3. Measurement
Protection
Safety
Availability
2. Measurement
Protection
Safety
Availability
OUTPUT CONTACTS
Secure supply via
redundant PSU’s
allowing exchange
during operation
FT 3000


Operating Instructions FT 3000JAQUET AG
377E-63917 Rev 4.00 page 7 of 47
2 Safety Warning
During operation, parts of the FT 3000 are under dangerous voltages. The units conform to protection class 1 and
require an earth connection on the corresponding module connector and/or terminal on the 19" rack.
The units have been designed and tested in accordance with IEC 348 and have left the factory in perfect condition.
These operating instructions include information and guidance on the safe operation of the equipment and installation.
Please specially note section 6.
If in doubt about the condition of any part following electrical, environmental or mechanical damage, the unit should be
returned for repair.
3 Applications
FT 3000 tachometers are used to monitor and measure frequencies in the range 0 to 30000Hz eg from frequency
proportional sources such as rotational speed.
The FT 3000 family comprises of the following modules:
•Monitoring module (Motherboard) FTFU 3024
with input card -E01 FTFU 3024- E01 Art. Nr. 377Z-03981
with input card -E02 FTFU 3024- E02 Art. Nr. 377Z-03982
with input card -E03 FTFU 3024- E03 Art. Nr. 377Z-03983
•Trip Chain Control card FTBU 3034 Art. Nr. 377Z-05030
•Frequency to current converter FTW 3013 Art.Nr.377Z-03984
(Auxiliary module)
•Relay card (Auxiliary module) FTV 3090 Art. Nr. 377Z-03985
•Comms module FTK 3072 Art. Nr. 377Z-03986
•PSU 116/230Vac FTZ 3061 Art. Nr. 377Z-04065
•PSU 24/48Vac FTZ 3062 Art. Nr. 377Z-04073
•PSU 14...70Vdc FTZ 3064 Art. Nr. 377Z-04074
•PSU 75...372Vdc FTZ 3065 Art. Nr. 377Z-04075
•Mains filter (2 wire) FTZ 3069 Art. Nr. 804D-35886
FT 3000 3 channel speed monitoring and over speed protection systems comprise of 3 independent channels, from
speed pick ups through to limit signalling. High integrity operation is provided for in the rack through the use of 2
redundant power supplies to each module via diode decoupling. Rack module supply requirements are matched to the
incoming supply by the 2 redundant power supplies.
4 Construction
The modules are plug in units in a 19" rack, with height 3 HE and with 4, 12 or 20 TE in accordance with DIN 41494.
Compatible card frames with up to 21 locations at 4 TE are used for mounting and wiring the modules. The card frames
are built by JAQUET to customer requirements. Connections for speed sensors, control and output signals along with
power supplies are normally provided at the back via screw terminals or Termi-Point connections.The setting of
measuring range, monitoring and relay parameters is via front panel RS 232 interface on the FTK 3072 comms module
to a PC. This module controls the data flow between the PC and individual modules in the rack (RS 485 rack bus). The
parameters are stored in EEPROM’s and protected against mains failure.

Operating Instructions FT 3000JAQUET AG
377E-63917 Rev 4.00 page 8 of 47
5 Front Panel description
5.1 FTFU 3024
5.2 FTV 3090
PSU Monitor
Green if 18V
<
V
<
33V
PSU Monitor
Green if 18V < V < 33
V
Self check system fault = red
No system fault (Green)
Sensor fault = red
Sensor monitor OK = green
Direction forwards = yellow
Direction backwards =
y
ellow
Limit 1, 2, 3, 4 passed high /low = red
(
de
p
endent on confi
g
uration
)
Limit 1, 2, 3, 4 passed high /low = green
(
de
p
endent on confi
g
uration
)
For factor setting only Sensor frequency = yellow
Test point ; Reference signal inputTest point ; Refrence signal input
Test point ; scaled trigger level
0V corresponds to 0%, 10V to 100%
(of max 3.5V) (E01)
Lower sensor monitor current limit
10V corresponds to 30 mA (E01)
Upper sensor monitor current limit 10V
corresponds to 30 mA (E01)
Sensor current :
10 V corres
p
onds to 30 mA
(
E01
)
Relay 1 active = yelllow
Relay 2 active = yellow
Relay 3 active = yellow
Relay 4 active = yellow

Operating Instructions FT 3000JAQUET AG
377E-63917 Rev 4.00 page 9 of 47
5.3 FTK 3072
5.4 FTW 3013
PSU 2 monitor
Green if 18V < V < 33V
Self check system fault = red
PSU 1 monitor
Green if 18V < V < 33
V
No system fault = green
A
ctive comms to PC =
y
ellow
Active internal rack bus comms =
yellow
Interface to PC

Operating Instructions FT 3000JAQUET AG
377E-63917 Rev 4.00 page 10 of 47
5.5 FTBU 3034
PSU Monitor
Green if 18V
<
V
<
33V
PSU Monitor
Green if 18V < V < 33
V
Self check system fault = red
No system fault (Green)
6 Signal monitoring channels.
If red, the corresponding channel is
activ e
6 signal monitoring channels.
If green, the corresponding channel is
not active
Combinated signal monitoring output.
Yellow if no signal input active.
Off, if the channel combination criteria is
reached :
channel 1 and channel 2 active
or channel 3 and channel 4 active
or channel 5 active
or channel 6 active

Operating Instructions FT 3000JAQUET AG
377E-63917 Rev 4.00 page 11 of 47
6 Specifications
6.1 Statistics
Mean Time Between Failure for each channel (without voting) : 188683 hours # 21.5 years
Mean Time Between Failure for each OSP channel (FTFU 3024) : 230700 hours # 26,0 years
Mean Time Between Failure for each signal monitoring channel (FTBU 3x34) : 1036000 hours # 118 years
PFHg according to IEC 61508-2 : 2.69e-8 fits
DC % according to IEC 61508-2 : 94.23%
Life duration for the system is 20 years. During this period the data integrity of the programable devices are garanted,
this time is equivalent to the MTBF of the channel. After this period the overspeed protection system must be replaced.
6.2 IEC 61508-2-3 specifications :
•System configuration for the Overspeed Protection System :
The system definition must include for reaching the IEC 61508-2-3 and SIL 3 conformity an alarm signal with
following activated selfcontrols for the S + M + P Alarm output :
-System check : Watchdog, Parameter monitoring, software test
-Sensor monitoring : Static and/or dynamic sensor monitoring activated
-Power supply check : monitoring of the supply voltage
In addition, for a safe system behaviour in the case of multiple faults, the system S +M + P Alarm must be
combined with the overspeed signal. This means that multiple detected system faults generate a trip.
Only 3 channel systems can fulfil the IEC 61508-2-3 requirements.
•System configuration for the optinal additional Trip Chain Control Card.
Only a 3 channel Trip Chain Control System can fulfil the IEC 61508-2-3 requirements for SIL3. The voted or
non voted TCCC signals can be combined with OSPS trip signals.
•System installation :
The installation specification must be kept for reaching the IEC 61508-2-3 conformity. These specifications must
be realised by the system integrator / end user. See chapter Installation.
•System maintenance :
The maintenance specification must be kept for reaching the IEC 61508-2-3 conformity. These specifications must
be realised by the system integrator / the end user. See chapter Maintenance.
6.3 Technical data OSPS
Reference conditions: Operating temperature +20ºC
Supply within defined limits
Smallest measuring range: 0...1.000 Hz
Largest measuring range: 0...35.00 KHz
Once the machine factor M is defined (M = Freq. In Hz/ measured value eg rpm), the input of measuring range and
limit values is directly in the chosen physical units eg rpm. In place of the machine factor, the number of pulses per rev
from the pole wheel may be entered. Moreover once the nominalspeed is defined (=100%), limits can be given as a
percentage of nominal. The measured range may be continuously exceeded up to 55KHz without affecting
functionality or causing any damage to the unit.
Sensor signal input-
Frequency input 1 Input card -0X for frequency input 1, plugged onto the motherboard FTFU 3024

Operating Instructions FT 3000JAQUET AG
377E-63917 Rev 4.00 page 12 of 47
Input card E-01:
potential free, isolation 500V, 50Hz,1 Min. from electronics and earth ie from front panel
and card frames.
for connection of electromagnetic, ferrostat or HF sensors, proximity switches and sensors
with line amplifiers.
Input impedance: 100kohm
Input voltage: 50mV...80V rms
Bandwith (-3dB) : 0,5 Hz /3.3 kHz
Frequency domain for pulsed signals : 0.02Hz / 30kHz
Input level for sinus signals : 50 mv rms at min trigger
Input level for pulsed signals : 10Vpp at 20% trigger level
Trigger level: adjustable between 0 and +3.5V via front panel
trimmer T. The voltage at test point T to ground of
fixed hysteresis of 50mV rms = 141mVss
Integral pull up (+12V) and pull down (0V) resistance of 820 Ohm for connecting 2 wire
sensors, jumper selectable.
Sensor monitoring of 2 and 3 wire sensors, jumper selectable -If the supply current is
< I min or > I max a defect is signalled by the green LED ‘MO’ off and the red LED ‘MO’
on.
I min is set via front panel trimmer ‘L’
I max is set via front panel trimmer ‘H’
A voltage at test points ‘L’ and ‘H’ to ground of 0...10V corresponds to supply current of
0...30mA.
A voltage of 0...10V at test point ‘M’ corresponds to the actual supply current of ...30mA.
To adjust the trimmers the module must be plugged onto an extension card to open the seal.
Integral sensor supply of +11.5...12.5V, max 25mA, short circuit proof (max 40mA).
Input card E-02: potential free, insulation 500V, 50Hz,1 Min. from electronics and earth ie from front panel
and card frames.
This input card is a special version and is only for specific applications available.
Configuration available only by contacting the system supplier.
Input impedance: 100kohm
Input voltage: 0...-24V
Frequency domain for pulsed signals : 0... 30kHz
Input level for pulsed signals : 0.2 ...24Vpp
Trigger level: Adjustable between 0 and +3.5V via front panel trimmer T.
The voltage at test point T of 0...10V correspnds to 0...3.5V Trigger Voltage
Fixed hysteresis of 50mV rms = 141mVss
Default setting : T = 2V corresponds to 660mV Trigger level
The sensor monitoring is realised by checking the sensor output signal (Card Uin).
Uin (low) must be greater then the defined minimum value (absolut values).
Uin(high) must be smaler then de defined maximum value (absolut values).
Uin < Uin(min) or Uin > Uin(max) is signaled by the green LED ‘MO’ off and the red LED
‘MO’ on.
Uin(min) is set via front panel trimmer ‘L’
Uin(max) is set via front panel trimmer ‘H’
A voltage at test points ‘L’ and ‘H’ to ground of 0...10V corresponds signal level of 0...-24V.
Default setting of ‘L’ = 1V corresponds to a minimum signal level of -2.4V.
Default setting of ‘H’ = 8.33 V corresponds to a maximum signal level of – 19.9V.
A square wave signal of 0...10Vpp at test point ‘M’ corresponds to the actual sensor signal of
0...-24Vpp.
To adjust the trimmers the module must be plugged onto an extension card to open the seal.
Integral sensor supply of –24V +/- 4%
Frequency inputs 2 and 3 Motherboard FTFU 3024

Operating Instructions FT 3000JAQUET AG
377E-63917 Rev 4.00 page 13 of 47
For average/max values and direction
2 inputs with common
reference voltage -
-V of supply
+24 level
U low: 0...+3V or open
U high: +10...+33V, I source = max 3mA.
Limit values 1 - 4 Motherboard FTFU 3024 with optional relay card FTV 3090
Up to 4 limits for speed or frequency functions
Hysteresis Upper and lower set points are freely programmable for each limit
Relay function Monostable function, individually definable as ‘Normal’ energized in when upper set point
exceeded ‘Inverse’ energized in when speed below lower set point
Relay outputs 1, 2 and 3 on
FTFU 3024 motherboard 1 potential free change over contact
AC Umax 250V, Imax 5A, Pmax 1250VA
DC Umax 30V, Imax 5A, Pmax 150W
Initial breakdown voltage : 1000Vrms 1min. from neighbouring output, electronics and
earth, ie from front panel and card frames
Relay outputs 1 - 4 on
FTV 3090 relay card 1 potential free change over contact
AC Umax 250V, Imax 2A, Pmax 125VA
DC Umax 220V, Imax 2A, Pmax 60W
Initial breakdown voltage : 1000Vrms 1min. from neighbouring output, electronics and
earth, ie from front panel and card frames
Accuracy 0.1% of the set point
Temperature error max +/- 50ppm with reference to the set point
Reaction time of speed
monitor
Reaction time of
comporaters
Where the limit is assigned to one of the three speed monitors on the motherboard, the
minimum measuring time is 1 period of the corresponding set point frequency.
The reaction time of the corresponding relay output is Max 1 period of the input frequency
+ 9ms.
Where the limit is assigned to one of the 4 comparators on the motherboard, the minimum
measuring time may be set as the Fixed Time. Where the period of the input frequency is
shorter than the Fixed Time the relay output reaction time is -
Max twice Fixed Time + max input freq. period + 12ms
Typically = Fixed Time + 1 input period + 12ms
Where the input period is longer than the Fixed Time the reaction time of the relay output is -
Max max input period + 12ms
Analog outputs 1, 2 and 3 Auxiliary module FTW 3013
Each of the 3 analog outputs can be used for speed or frequency functions each having
independent ranges. The outputs are potential free and isolated to 500V, 50Hz, 1 Min. from
each other, the main electronics and earth (neighbouring o/p, front panel and card frame).
Standard configuration 0...20mA or 4...20mA,
programmable for rising or falling characteristic Max load 500 Ohm (10V)
Optional version S3 0...5mA or 1...5mA
programmable for rising or falling characteristic Max load 2000 Ohm (10V)
Option U, voltage output 0...10V or 2...10V
programmable for rising or falling characteristic Max load 7 KOhm (1.4mA)
Max output voltage 30 V
Resolution 12 Bit. 1: 4096
Max linearity error 0.1%

Operating Instructions FT 3000JAQUET AG
377E-63917 Rev 4.00 page 14 of 47
Accuracy 0.2% of the range
Temperature drift typically +/- 150ppm/ºK, max +/- 300ppm/ºK
Reaction time (step change) The minimum measuring time may be entered. Where the input period is shorter than the
Fixed Time, the reaction time is -
Max twice Fixed Time + max input period + 7.5ms
Typically Fixed Time + 1 input period + 7.5ms
Where the input period is longer than than the Fixed Time, the reaction times is
Max input period + 7.5ms
Each of the analog outputs can be allocated a software defined low pass filter, whose time
constant T can be configured in the range 0.0 to 9.9 seconds. The sample rate is T/10.
Binary inputs 1 - 6 Motherboard FTFU 3024
For programmable control functions such as
- failure memory reset
- max memory reset
- initiate lamp test
- set direction of rotation
- initiate test
2 binary inputs (B1 and B2)
having common reference -
-V of the supply
4 potential free binary inputs
(B3...B6) with common
floating reference voltage
+ 5 V level with pull up resistor
V low = active 0...+1V, Isink = max 1mA
V high + 3,5...+33V or open
Isolation 500V, 50Hz, 1 Min. from electronics and earth
+24V level
V low 0...+5V or open
V high = active +10...+33V Isource = max 4mA
Frequency outputs 1 and 2 Motherboard FTFU 3024
Frequency output 1
having common 0V with
supply
Square wave, amplitude +10V, output impedance 100 Ohm
Output current +/-50mA continuous
+/- 100mA for 10% of operating time
Frequency output 2
potential free Square wave, amplitude +15Vpp, output impedance 100 Ohm
Output current +/-50mA continuous
+/- 100mA for 10% of operating time
Isolation 500V, 50Hz, 1 Min. from electronics and earth
Frequency generator Motherboard FTFU 3024
Frequency range 0.002Hz / 30KHz. Signal only accessible internally = F4
Data I/O Comms module FTK 3072
Having potential free
floating reference Serial RS 232 interface via front panel D9 connector
Supply PSU in the rack for all modules excluding supply modules
18...33Vdc
Power consumption Typically Max
Motherboard FTFU 3024/E01 4.5W 5.5W
Converter FTW 3013 2.6W 2.8W

Operating Instructions FT 3000JAQUET AG
377E-63917 Rev 4.00 page 15 of 47
Relay card FTV 3090 4.0W 4.2W
Comms module FTK 3072 2.0W 2.5W
Power on surge is limited as follows
Motherboard FTFU 3024/E01 7A
Input cards E01, E02, E03 3.3A
Converter FTW 3013 0.1A
Relay card FTV 3090 0.1A
Comms module FTK 3072 7A
Power Supply To FTZ 306X
Output 24VDC-2A (1.5A for FTZ3061/62, 4A for FTZ3066)
Isolation 500V, 50Hz, 1min from earth
Isolation 2000V, 50Hz, 1min from input
Model
FTZ 3061
FTZ 3062
FTZ 3064
FTZ 3065
FTZ 3066
FTZ 3069
Voltage max power consumption surge
115/230Vac, -20, +15% 63VA 10A
24/48Vac, -20, +15% 63VA 50A
14...70Vdc 60W 500A
88...372Vdc 60W 55A
14 … 70Vdc 120W 500A
Mains filter - required if modules
supplied direct with 18...33Vdc 66A
Environment KUE to DIN 40 040
Operating temp 0...+60ºC, +70ºC for max 2 hours Storage temp -25...+85ºC
rH 75% yearly average, max 90% over 30 days, condensation to be avoided.
Electromagnetic immunity Conforms to current european standards
Card frames and modules Mounting to DIN 41494
Material anodised aluminium
Rack space 84 TE - 21 slots each 4 TE
Height 3 HE
Depth approx 220mm
Connectors 2 or 3 row type F to DIN 41612, wire wrap connections as standard to rear
screw terminals.
Optional Termi Point terminals for direct connection.
Dimensional drawings Card frames Dwg nr. 3-110.544/4
Modules Dwg nr. 3-110.544/2
Rear screw terminals Sprung terminals for 2.5mm sq. cable or 1.5mm sq. wire
Protection class to DIN 40050 Card frames IP 10
Plugged modules IP 20
Terminals IP 20
Block diagram Dwg nr. 4-110.505
Module layout in rack Dwg nr. 4-110.545
Rack terminal layout/wiring Dwg nr. 3-110.536
Module connections
Motherboard FTFU 3024
Converter FTW 3013
Relay card FTV 3090
Comms module FTK 3072
Dwg nr. 4-110.531/23
Dwg nr. 4-110.531/24
Dwg nr. 4-110.531/25
Dwg nr. 4-110.531/26

Operating Instructions FT 3000JAQUET AG
377E-63917 Rev 4.00 page 16 of 47
6.4 Technical data TCCC
TCCC = Trip Chain Control Card, FTBU 3x34
INPUT : IN1 – IN6 6 potential free inputs.
Input voltage for IN1- IN6 20 – 50 V, active level is 0V.
IN1 – IN6 Sink current Min 10 mA, Max 15 mA
Logical channel combination The output OUT is active when the following logical combination occurs :
IN1.IN2 + IN3.IN4 + IN5 + IN6, where Ini means channel i is active (low level).
INPUT : TEST The TEST input simulates the logical combination which activates the OUT output. This
signal is used for performing periodic FTBU testing.
Input voltage for TEST 5 – 48V, input active level is high. No test mode is at TEST = 0V
TEST Sink current < 15 mA for the whole voltage range.
OUTPUT : K1 – K6 These relays are the output stage associated with each signal channel. The Relay Ki is
energized when INi is high.
Relay K1 – K6 Potential free change over contact
AC Umax 250V Imax 5A Pmax 1250 VA
DC Umax 30 V Imax 5A Pmax 150 VA
Initial breakdown voltage : 1000Vrms 1min. from neighbouring output, electronics and earth,
ie from front panel and card frames
Reaction time INi to Ki < 8 ms
OUTPUT : OUT This relay is the combined output of the 6 signal channels. The Relay OUT is energized when
the logical combination of IN1 – IN6 is not true.
Relay OUT 2 potential free change over contacts
AC Umax 250V Imax 2A Pmax 125VA
DC Umax 220V Imax 2A Pmax 60W
Initial breakdown voltage : 1000Vrms 1min. from neighbouring output, electronics and
earth, ie from front panel and card frames
Reaction time Ini to OUT < 8 ms
OUTPUT : ALARM The alarm relay is the output stage of the on board self-diagnostic function. The supply
voltage and the logical correlation between input levels and output levels are monitored. The
relay is energized when the current card status is no-alarm.
Relay ALARM Potential free change over contact,
AC Umax 250V Imax 5A Pmax 1250 VA
DC Umax 30 V Imax 5A Pmax 150 VA
Initial breakdown voltage : 1000Vrms 1min. from neighbouring output, electronics and earth,

Operating Instructions FT 3000JAQUET AG
377E-63917 Rev 4.00 page 17 of 47
ie from front panel and card frames
Power Supply The card FTBU 3x34 can be used with standard FT3000 redundant power supply units. Both
voltages are combined on the card and the supply voltages are monitored.
Supply voltage 18 ... 33V
Supply current Typ : 160 mA Max 250 mA at 24V
Power on surges Limited at 1 A
7 Principle of operation
7.1 Measuring system
The measuring system on the FTU 3024 motherboard processes four frequencies, F1, F2, F3, F4.
Input F1 is derived from the amplified sensor signal from the input card EOX. Inputs F2 and F3 are derived from
the outputs of additional FTFU 3024’s present in a 3 channel system. Input F4 is derived from the test frequency
generator.
7.2 Measuring principle
7.2.1 Standardising the measured value
Following input of the machine factor M = f/n, where f = sensor frequency in Hz for a known speed and
n = machine speed in rpm
or input of the number of pulses per rev (nr. of pole wheel teeth), the frequency relay limit values and the converter
measuring ranges can be directly entered in rpm.
The relationship between the sensor signal frequency f and the speed n of a pole wheel to be sensed is
f = n * p/60 where f = sensor frequency in Hz
n = pole wheel speed in rpm
p = nr. of pole wheel teeth
For rotational speed measurements the machine factor M = p/60.
In place of speed n in the formulae above, any other frequency proportional physical unit may be used.
If the limit values and measuring ranges are to be entered in percent of nominal, the above calculations are still
required.
7.2.2 Speed monitor
The max 3 speed monitors are based on hardware re-triggerable One Shot circuits that are set with every positive edge
of the input frequency. The timebases are derived from 3 down counters that are set with the set point frequency and
clocked down using a 2.5MHz reference signal. If the counter reaches zero before the arrival of the next positive edge,
this indicates that the input frequency is lower than the set point. These functions for one limit value are performed in an
ASIC (Application Specific IC). The preset values for the down counter are computed by a microprocessor for the
required set point and loaded into the ASIC.
The 3 speed monitors continuously collect speed frequency data without interruption.
Each speed monitor is supplied with 1 of 5 possible input signals, defined by software configuration (None, F1, F2,
F3, F4)
7.2.3 Frequency measurement (Period measurement principle)
FT 3000 tachometers work on the continuous period measurement principle. The measuring chains for 3 frequency
measurements are implemented in hardware using ASIC’s. Each of the 3 ASIC’s contain a counter to measure the
period duration of up to 3 frequencies. The mpu reads the counter’s status with each positive edge of the input
frequency. The difference between the status of 2 counters is a measure of the period of the input signal. The frequency

Operating Instructions FT 3000JAQUET AG
377E-63917 Rev 4.00 page 18 of 47
data is continuously collected from all 3 measuring chains without pause. The number of periods measured is
determined by the Fixed Time and the magnitude of the input frequency.
The measured value (rotational speed) is then computed by the mpu. There are then 3 floating point values
available - <AbsolutA>, <AbsolutB> and <AbsolutC>.
Each measuring chain is supplied with 1 of 5 possible input signals, defined by software configuration (None, F1, F2,
F3, F4).
7.2.3.1 Measurement functions
Based on the measured values <AbsolutA>, <AbsolutB> and <AbsolutC>, the following functions can be realised:
<FunctionOutput>
•Majority value of A, B and C: From the 3 values 2 are selected that display the smallest difference
and used to generate an average value.
•Max value of A, B and C: The max value is selected from the 3
•Min value of A, B and C: The min value is selected from the 3
•Average of A+B+C
•Average of A+B
•Average of B+C
•Average of C+A
•Difference A-B
•Difference B-C
•Difference C-A
•Ratio A/B
•Acceleration 1 (Accel. 1) :
Accel1 = (speed2– speed1) / (time2– time1) (RPM/s)
•Acceleration 2 (Accel. 2) :
Accel2= Accel1/ speed1 (RPM/s)
Accel2 units could also be %/s, this means that we are speaking here of a rate of change from the nominal
speed.
The function is defined by software configuration.
7.2.3.2 Max value memory
The max value memory <MaxMem> registers the maximum value of a measurement (Drag pointer function)
The max value memory can only be reset via an intentional entry ResetMaxMem in the CommandByte or through total
power failure. Which measured value is stored is defined by the software configuration -
•<AbsolutA>
•<AbsolutB>
•<AbsolutC>
•<FunctionOutput>
Always remember to reset the Max value memory following testing with internal generators.
Speed measurement and over speed trip monitors are separate functions within the FT 3000.
In operation, there are 2 main reasons why the recorded Max value may not correspond to the
limit setting:
- the trip point is reached but the machine runs on until the shutdown valve has closed. The maximum
speed the machine reached prior to shutdown is therefore recorded.

Operating Instructions FT 3000JAQUET AG
377E-63917 Rev 4.00 page 19 of 47
- gear machining inaccuracies, coupled with a low number of pulses configured for the trip
setting may result in the over speed monitor activating the trip relay at a speed apparently lower
than the limit set. The solution to this is to increase the number of pulses used to say 20% of the number
of teeth on the gear
7.2.3.3 Comparators
Each of the 4 comparators can be allocated one value from the following list by software configuration -
•<AbsolutA>
•<AbsolutB>
•<AbsolutC>
•<FunctionOutput>
•<MaxMem>
A comparator compares the actual measured value with the predefined set point and establishes limit status
(upper/lower limit reached)
7.2.3.4 Analog outputs
Each of the 3 analog outputs from the FTW 3013 can be allocated one measured value via software. The start and end
values for each range can be independently defined. Rising and falling characteristics are permissible. Each analog
output may include a low pass filter with software configurable time constant.
7.2.4 Acceleration measurement
The acceleration is measured with the speed measurement unit implemented in hardware (FPGA). The measurement of
the speed is made every 10 ms (for speeds greater than 100 RPM). The precision of this measurement is determined by
the clock of the „time counter“, which is 2.5 Mhz. Here we consider that this clock has no jitter, what is true due to the
integration of the jitter during the measurement
The relative measurement accuracy of the acceleration is defined by :
)/( )(
*8.0(%) sRPMonaccelerati RPMspeed
onaccelerati onaccelerati =
Δ
For example :
Speed = 3000 RPM
Acceleration = 1200 RPM (rate of change of 40% per second)
The reachable accuracy is +/- 2% for the acceleration.

Operating Instructions FT 3000JAQUET AG
377E-63917 Rev 4.00 page 20 of 47
FT3000 acceleration measurement error
0.01
0.1
1
10
100
0.1 1 10 100
nominal speed (RPM) / acceleration (RPM/s)
measurement error (%)
3000 RPM / 1200 RPM/s
2%
Table of contents
Other Jaquet Measuring Instrument manuals