Jevi EFF User manual

IOM 08099901
EN, DE
11-2022
______________________________________________________________________
All rights reserved. Reproduction or issue to third parties of this manual or part of it in any
form is not permitted without prior written authorisation of the proprietor
Alle Rechte vorbehalten. Die Weitergabe sowie Vervielfältigung in jeglicher Art und Form
- auch auszugsweise - des Inhaltes dieses Handbuches ist ohne die vorherige schriftli-
che Genehmigung durch den Eigentümer nicht zulässig
EN
Installation, operation and maintenance manual for duct heaters (HVAC)
For installation in hazardous areas
DE
Installations-, Betriebs- und Wartungshandbuch für Heizlüfter (HVAC)
Für Installation im gefährdeten Bereich
EFF, EFI, EFFS, EFFL, EFIL, EFFLI, EFILI, EFFX,
EFRX, EFIX, EFR, EFRS, EFRSL

JEVI A/S
IOM 08099901
EN, DE
11-2022
______________________________________________________________________
1
ENGLISH
Safety information .............................................................................................................3
Disclaimer .........................................................................................................................4
List of abbreviations ..........................................................................................................5
1.0 Introduction..................................................................................................................6
2.0 Description of product .................................................................................................6
3.0 Packing .......................................................................................................................8
3.1 Choice of the Packing Type.....................................................................................8
3.2 Wood treatment
.....................................................................................................8
3.3 Pallets
.....................................................................................................................8
3.4 Handling
.................................................................................................................8
3.5 Centre of gravity
.....................................................................................................8
3.6 Labelling and tagging of equipment /
Identification
.............................................8
3.7 Shipping marks / labelling
......................................................................................9
4.0 Transportation ...........................................................................................................10
4.1 HVAC .....................................................................................................................10
5.0 Storage and preservation..........................................................................................11
5.1 Preservation during the transportation and pre-installation period .........................11
5.2 Preservation during the installation/construction period .........................................11
5.3 Suggestion for preservation specification & record: ..................................................13
6.0 Installation instructions..............................................................................................15
6.1 General ..................................................................................................................15
6.2 Special conditions for safe use...............................................................................15
6.3 Heater Installation ..................................................................................................15
6.4 Adjusting Thermal couple / RTD, TSH thermal switch with auto reset ...................16
6.5 Adjusting TSHH thermal cut-off (Thermal couple / RTD)........................................16
6.6 Test procedure TSH/TSHH thermal cut-off.............................................................16
7.0 Start up......................................................................................................................17
7.1 Before energizing the heating elements .................................................................17
7.2 Shutting down the heater........................................................................................17
8.0 Operating instructions ...............................................................................................18
9.0 Maintenance instructions...........................................................................................19
9.1 Maintenance and service plan................................................................................20
10.0 Trouble shooting......................................................................................................21
11.0 Disposal instructions ...............................................................................................22

JEVI A/S
IOM 08099901
EN, DE
11-2022
______________________________________________________________________
2
DEUTSCH
Sicherheitshinweis...........................................................................................................23
Haftungsausschluss ........................................................................................................24
Liste der Abkürzungen ....................................................................................................25
1.0 Einleitung ..................................................................................................................26
2.0 Beschreibung des Produktes.....................................................................................27
3.0 Verpackung ...............................................................................................................29
3.1 Wahl der Verpackungsart.......................................................................................29
3.2 Holzbehandlung
..................................................................................................29
3.3 Paletten
................................................................................................................29
3.4 Handhabung
........................................................................................................29
3.5 Schwerpunkt
.........................................................................................................29
3.6 Etikettierung und Markierung der Geräte /
Identifizierung
................................30
3.7 Versandmarkierungen/ Etikettierung
...................................................................30
4.0 Transport...................................................................................................................31
4.1 HVAC .....................................................................................................................31
5.0 Lagerung und Konservierung ....................................................................................32
5.1 Konservierung während des Transports und vor der Installation............................32
5.2 Konservierung während der Installations-/ Bauphase ............................................33
5.3 Vorschlag für Spezifikation und Dokumentation der Konservierung:......................34
6.0 Montageanleitung......................................................................................................36
6.1 Allgemeines............................................................................................................36
6.2 Besondere Bedingungen für den sicheren Einsatz.................................................36
6.3 Montage des Kanallufterhitzers..............................................................................36
6.4 Einstellung des Temperaturbegrenzers (falls vorhanden) mit Auto-Reset .............37
6.5 Einstellung TSHH Temperaturschalters (Thermoelement/ PT100) ........................37
7.0 Inbetriebnahme .........................................................................................................38
7.1 Vor Einschalten des Kanallufterhitzers................................................................38
7.2 Abschalten des Kanallufterhitzers ..........................................................................38
8.0 Betriebsanweisungen ................................................................................................39
9.0 Wartung.....................................................................................................................40
9.1 Wartungs- und Serviceplan ....................................................................................41
10.0 Trouble shooting......................................................................................................42
11.0 Entsorgungsanweisungen .......................................................................................43

JEVI A/S
IOM 08099901
EN, DE
11-2022
______________________________________________________________________
3
Safety information
To secure your personal safety, as well as prevent damages to property, this manual
contains notices you have to observe. The notices referring to your personal safety
DANGER Indicates that death or severe personal injury will result if
proper precautions are not taken
WARNING
With a safety alert symbol, indicates that minor personal injury
can result if proper precautions are not taken
CAUTION
Without a safety alert symbol, indicates that property damage
can result if proper precautions are not taken
NOTICE
Indicates that an unintended result or situation can occur if the
corresponding information is not considered
If more than one degree of danger is present, the warning notice representing the high-
est degree of danger will be used. A notice warning of injury to persons with a safety
symbol may also include a warning relating to property damage.
Qualified Personnel
Only personnel qualified for the specific task in accordance with the relevant documenta-
tion for the specific task, in particular its warning notices and safety instructions may op-
erate the product described in this documentation. Qualified personnel are those who,
based on their training and experience, can identify risks and avoiding potential hazards
when working with these products/systems.
Proper use of JEVI products
WARNING
Proper transport, storage, installation, assembly, commis-
sioning, operation and maintenance is required to ensure
that the product operates safely and without any problems.
The permissible ambient conditions must be adhered too.
Observe the information in the relevant documentation.

JEVI A/S
IOM 08099901
EN, DE
11-2022
______________________________________________________________________
4
Disclaimer
JEVI A/S assumes no responsibility for any additions placed by the customer that can in-
flict our product. Additions or alterations implemented by the customer are not covered
by our warranty.
IMPORTANT: These instructions should be read thoroughly before installation and oper-
ation. All warnings and precautions should be observed for both personal safety and for
proper equipment performance and longevity. Failure to follow these instructions could
result in equipment failure and/or serious injury to personnel.
NB! THIS IOM IS A STANDARD DOCUMENT AND IS NOT PROJECT SPECIFIC.
The English IOM is JEVI’s standard version

JEVI A/S
IOM 08099901
EN, DE
11-2022
______________________________________________________________________
5
List of abbreviations
ACBR
Air Cooled Braking Resistor
CoG
Centre of Gravity
EF
Electrical Duct heater
GA
General Arrangement (Drawing)
HVAC
Heating, ventilation, Air Conditioning
IOM
Installation, Operating and Maintenance Manual
JB
Junction Box
VLE
Fan heater with integrated controls for temperature control
VLEx
Fan heater for hazardous areas
WCBR
Water Cooled Braking Resistor
TSH
Temperature Switch High
TSHH
Temperature Switch High High

JEVI A/S
IOM 08099901
EN, DE
11-2022
______________________________________________________________________
6
1.0 Introduction
This manual is valid for variated models of HVAC designed for explosive areas.
The purpose of this document is to introduce a reader to installation, operation, and
maintenance procedure and most importantly to general safety precautions, which are
not necessarily related to any specific part or procedure, and do not necessarily, appear
elsewhere in the publication. These precautions must be thoroughly understood and ap-
plied to in all phases of operation and maintenance.
Descriptions in this manual are generic and are not project specific. Pictures may show
other equipment and options than in the actual project.

JEVI A/S
IOM 08099901
EN, DE
11-2022
______________________________________________________________________
7
2.0 Description of product
The duct heater is designed to heat air.
Reference should be made to the general drawing of this item for the intended use:
Drawing no. : Refer to equipment drawing GA
Electric supply : See electrical diagram
Voltage : See electrical diagram
Ref. number : Same as order number and item number
The heater consists of an enclosure (IP rating according to GA and/or datasheet) con-
taining:
•Certified electric heating elements (Ex e II) max load of 1,3 W/cm².
•A protective device with manual reset (TSHH) Ex de IIC Gb.
•Optional, protective device with auto reset (TSH) Ex de IIC Gb
•Alternative protective device, TSHH, thermocouple sensor type K connected to certi-
fied transmitter, Ex ia IIC T4...T6 Ga end user applies barrier, reset must be done by
hand.
•Temperature sensors are placed at the highest temperature areas of the heating bun-
dle.
In case of no airflow the TSHH will cut off the heater.
Optionally the certified equipment mentioned below may be fitted into the junction box.
•A certified Ex ia IIC T4 temperature transmitter.
•A certified Ex d IIC T5 anti-condensation heater.
•A certified Ex de IIC T6 or Ex d IIC T6 or Ex e IIC T6 control device.
Marking hazardous area certification:
•ATEX: II 2G Ex e IIC T3 Gb IECEx: Ex e IIC T3 Gb
•II 2G Ex e [ia] IIC T3 Gb Ex e [ia] IIC T3 Gb
Standards:
•ATEX: IECEx:
•EN 60079-0 IEC 60079-0
•EN 60079-7 IEC 60079-7
•EN 60079-11 IEC 60079-11
•EN 60079-14 IEC 60079-14
•IECEx group and category: Ex II 2 G
•Certificate number: IECEx TUN 13.0036X
•ATEX group and category: Ex II 2 G
•Certificate number: TÜV 13 ATEX 131672X

JEVI A/S
IOM 08099901
EN, DE
11-2022
______________________________________________________________________
8
3.0 Packing
All packing is in accordance with
the specific requirements of the individual purchase
order or contract as well as to the regulations of the country of destination.
3.1 Choice of the Packing Type
The choice of the
packing type and the requirement of particular protections depend on characteristics of
the equipment and material to be packed, its handling requirements and kind of
transport chosen.
The packing provides both mechanical and environmental protection.
3.2 Wood treatment
All solid wood,used for packing (including wooden pallets) is treated (heat treatment or
fumigation) according to the international standard ISPM 15 (IPPC),latest revision.
As these rules are not the same for all countries, the procedure is to meet the demands
of a country of final destination.
3.3 Pallets
Equipment is packed on pallets that provide adequate load support during transporta-
tion and storage. The pallets have a dynamic load capacity, enough to carry the mass
loaded on the pallet.
Where feasible the top surface of the pallet must be flat.
The pallet must be tight on all sides with steel or synthetic straps on each side.
Bolts, clamps, supporting beams, etc. will properly fix all equipment and materials.
Fragile, easily damageable and loose parts will be pertaining to the equipment se-
curely and properly packed in a separate case.
3.4 Handling
Under no circumstances may the equipment itself be used as a platform for gaining ac-
cess to installation and construction areas above. If such access is required then suitable
scaffolding must be established, the equipment may not be used as a support.
3.5 Centre of gravity
If required, large and heavy equipment are marked with Centre of Gravity (COG).
3.6 Labelling and tagging of equipment /
Identification
If no specific identification is required, (see the Purchase Order for the technical specifi-
cations)the labeling is in accordance to JEVI standard.
On demand the identification label is in accordance with the final packing list/delivery
note.

JEVI A/S
IOM 08099901
EN, DE
11-2022
______________________________________________________________________
9
3.7 Shipping marks / labelling
All packages are marked or
labelled in accordance with the data shown
in the packing list/delivery note

JEVI A/S
IOM 08099901
EN, DE
11-2022
______________________________________________________________________
10
4.0 Transportation
The product is packed according to agreement, with indication of CoG if required by cus-
tomer.
The product is packed on pallets. The packing is easily moved either by forklift or by use
of crane, handled by authorised personnel.
•For lifting lugs, see GA
•For weight, see GA or rating plate
•For COG - if any, see GA
CAUTION
Heating elements must NOT be used for lifting, this causes
damage on the elements
4.1 HVAC
All Heaters and inserts weighing > 25kg are supplied with lifting devices.
Lifting lugs

JEVI A/S
IOM 08099901
EN, DE
11-2022
______________________________________________________________________
11
5.0 Storage and preservation
The purpose of this chapter is to specify how to handle and preserve a product from the
day of shipment until the equipment is installed and commissioned.
Following conditions shall be observed for the installation/construction period.
CAUTION During storage, prior to installation the unit must be stored
dry with a relative humidity <60 %, temperature >15ºC.
CAUTION
Replace desiccant bag in junction boxes and enclosures (if
any) every 6 months.
Keep a log of the replacements as documentation.
CAUTION The Anti condensation heater, if any, must be powered up
and always connected.
5.1 Preservation during the transportation and pre-installation period
The packaging provides both mechanical and environmental protection. If the equipment
is intended for service in an outdoor environment, to avoid any risk of harmful metallic
dust during storage it is protected with enveloping plastic foil.
All openings such as cable entry holes are adequately sealed.
Packages must not be opened, or their integrity disturbed during the transport.
Packing may only be opened when the equipment has been taken from storage and has
been transported to its intended location of installation, or to connect the anti-condensa-
tion heater, after which the packing must be resealed. Storage preservation measures
are immediately invalidated as soon as the packaging is disturbed.
One shall inspect packages on receipt at the storage warehouse and at regular monthly
intervals during the storage period regarding external damages. Any visible damage that
may have a consequence to the condition of the contents or integrity of the preservation
must be immediately documented and reported. In case of such an event, the supplier
must be contacted immediately for advice
5.2 Preservation during the installation/construction period
The product must be unpacked only when the equipment is to be installed, or to connect
the anti-condensation heater. It is recommended to maintain the integrity of the packag-
ing during transport from the storage warehouse to the installation site.
Inspect the equipment within each package for damage and condition as soon as the
package is opened. Report and document any damage immediately. In case of such an
event, the supplier must be contacted immediately for advice.
Installation and handling of the equipment once unpacked must be performed in accord-
ance with the relevant elements of the documentation for the equipment delivered.

JEVI A/S
IOM 08099901
EN, DE
11-2022
______________________________________________________________________
12
Damages caused by bad workmanship or failure to adhere to the installation instructions
are not covered by the equipment warranty.
If the equipment is installed in an area where ongoing construction work of a nature that
causes airborne pollution or other adverse conditions take place, the equipment must be
suitably protected.Under no circumstances can the equipment be placed in the vicinity of
any activity, which involves grinding, welding, painting, fireproofing, spraying, etc. without
taking necessary precautions to protect it.
When cable termination is completed, a fresh desiccant bag must be placed in the enclo-
sure. The desiccant bag must be replaced every 6 month or until commissioning, has
been initiated.
All openings such as cable entry holes must be adequately sealed until the interfacing
cables or pipes are installed.
During installation, always keep the equipment in a clean condition. Remove debris from
cable installation activities at once. Take precautions to avoid any small pieces of a con-
ductive nature from being left in the termination enclosures.
Under no circumstances may the equipment itself be used as a platform for gaining ac-
cess to installation and construction areas above. If such access is required then suitable
scaffolding must be established, the equipment may not be used as a support.
During installation the equipment must be thoroughly inspected at regular weekly inter-
vals with regards to external damages, cleanliness and internal condition. Report and
document immediately if any visible damage or adverse condition occurs. In case of such
an event, the supplier must be contacted immediately for advice.
On completion of the installation work the condition of the equipment must be inspected.
Report and document any damage immediately if any visible damage. In case of such an
event, the supplier must be contacted immediately for advice.
CAUTION It is extremely important that no debris enters the vessel as
this may lead to a blockage of the return, or overflow pipes.

JEVI A/S
IOM 08099901
EN, DE
11-2022
______________________________________________________________________
13
5.3 Suggestion for preservation specification & record:
PRESERVATION SPECIFICATION & RECORD
Record No.:
Tag No.:
Description:
Record page 1 of 1
Activity
No.:
Intervals
(Months)
Description of
Preservation Activ-
ity
Recom-
mended Pre-
servative
Initial
Preservation
Date/Sign
Preserved
(2)
Date/Sign
Preserved
(3)
Date/Sign
Preserved
(4)
Date/Sign
Preserved
(5)
1 1
Check that protec-
tion structure is un-
damaged.
2 6
The desiccant bag
inside the Junction
boxes replaced.
3 1
Check the storage
conditions.
Relative humidity <
= 60 %, temp. > =
15˚C
4 12
If stored for more
than one year from
packing date, then
the supplier must
be contacted for ad-
vice regarding re-
newal of the desic-
cant bag.
5 12 Check the paint-
work.
6 12
Check that there
are no visual dam-
ages to the equip-
ment.
7 12
Verify that the gen-
eral condition of the
equipment is satis-
factory.
8 12
All openings such
as cable entry holes
are adequately
sealed. Junction
Boxes as well.
9 12
All loose items/re-
moved parts pre-
served, stored and
marked.
10 6
Verify no water
leakages, conden-
sation or moisture
where applicable.
11 6
The Anti-condensa-
tion heater in the
equipment must be
powered up and
connected at all
times.
Comments:
Performed by:
Date/Sign:
Accepted by:
Date/Sign:

JEVI A/S
IOM 08099901
EN, DE
11-2022
______________________________________________________________________
14
Note: These procedures are considered normal maintenance and are performed at the
owner’s expense.
* Depending on the environment, inspection frequency can vary.

JEVI A/S
IOM 08099901
EN, DE
11-2022
______________________________________________________________________
15
6.0 Installation instructions
6.1 General
The user must ensure that his employees are fully trained and supervised in the proper
working procedures to ensure their safety. The plant must be maintained in a safe condi-
tion.
Ensure that the equipment is correctly installed in a suitable location by technically quali-
fied personnel. Installation must meet the requirements of EN/IEC 60079-0, EN/IEC
60079-7, EN/IEC 60079-14 or equal valid standards.
6.2 Special conditions for safe use
•Only suitable certified cable glands may be used
•Heating elements may be rated up to 1,3 W/cm²
•Safety device TSHH must be permanently set at max 130°C in order to maintain T3
•Titanium heating elements may be used only when protected against impact.
•Ambient temperatures are: -25°C to +75°C
•End-user must ensure compliance between intrinsically safe parameters
6.3 Heater Installation
Before unpacking the equipment ensure that all items are available and that all crates /
or packages are in good condition and undamaged. Any damages must be reported to
the site manager and subsequently to JEVI A/S.
After removing the packing material, check all items for damage. If any damages: report
this to the site manager and subsequently to JEVI A/S.
For installation mounting and sealing materials have to be used which are suitable for the
medium to be heated and the prevailing temperatures that will occur. Please refer to the
GA-drawing for precise data and indications of fitting positions.
1. Open the junction box.
2. Connect the electric power cables to the terminals or bus bar system as indicated on
the electrical diagram and connect the earthing provisions on the mounting plate.
3. Connect the protective conductor to the earthing terminal.
4. Follow the instructions that have been provided by the supplier of the cable glands if
these are present and/or applicable.
5. Close the cover.

JEVI A/S
IOM 08099901
EN, DE
11-2022
______________________________________________________________________
16
WARNING Do not open the junction box when energized.
NOTICE
•During non-operation the unit must be stored dry. Rela-
tive humidity <60%, temperature >15°C.
•If applicable connect and switch on the space heater.
•When dismantled it is advisable to place a desiccant bag
inside the junction box
6.4 Adjusting Thermal couple / RTD, TSH thermal switch with auto reset
The TSH is adjusted to 80% of maximum.
If an adjustment is needed, then load the heater with maximum power and the lowest air-
flow according to specification.
Set the TSH on maximum temperature.
Wait until airflow and temperature is constant.
Adjust the temperature scale down on the TSH step by step with app 10°C at the time;
wait to see if TSH switches off for 10 min. adjust again 10°C continue this procedure until
TSH cuts off the heater.
Adjust the TSH scale up with10°C
Test the heater with full load and switch off airflow. TSH must switch off before maximum
allowed temperature for heater is reached.
The mechanical TSHH is nonadjustable.
6.5 Adjusting TSHH thermal cut-off (Thermal couple / RTD)
Adjusting TSHH thermal cut-off (Thermal couple / RTD) has been done by JEVI if the
transmitter is mounted in the heater.
The max temperature must be set according to the wiring diagram, and the IOM for the
transmitter.
This TSHH thermal cut-off (Thermal couple / RTD) must be with manual reset.
6.6 Test procedure TSH/TSHH thermal cut-off
TSH/TSHH are subject to factory test at JEVI.
In case an additional test of the TSH/TSHH thermal cut-off is required in connection with
the commissioning process, the following procedure is recommended:
1. For control of temperature insert a temperature sensor close to the TSH/TSHH.
2. Warm up the sensors to the set temperature by using a heat gun.

JEVI A/S
IOM 08099901
EN, DE
11-2022
______________________________________________________________________
17
7.0 Start up
Remove desiccant bag from JB before starting up
Before the initial start-up of the heater the following will have to be checked:
1. The heater has been correctly installed as described in the GA drawing and if neces-
sary, a leakage test has been performed.
2. The protective conductor (PE) has been connected and, if necessary, the external
connection between housing and ground has been effected, e.g., for avoiding electro-
static discharging.
3. The earthing connection has been effected and properly secured.
4. The electrical connections have been performed in accordance with the relevant reg-
ulations and wiring diagram.
5. The heater has been properly installed and all studs and nuts are
properly tightened.
6. All electrical connections between control panel and heater are correctly installed
e.g., power cable, temperature transmitter.
7.1 Before energizing the heating elements
1. Check the supply voltage.
Check the control voltage.
Voltages are specified on the wiring diagrams of this equipment.
2. Check whether the monitoring system has been actuated e.g., ‘Overheat Protection’.
(Thermostat, thermocouple sensor fixed to an element sheath).
7.2 Shutting down the heater.
De-energize the heater before shutting down the flow.

JEVI A/S
IOM 08099901
EN, DE
11-2022
______________________________________________________________________
18
8.0 Operating instructions
Before initial start-up of the heater, it should be checked whether:
1. The heater is properly installed and, if necessary, a leakage test must be conducted.
2. The electrical connection is performed in accordance with the relevant rules and reg-
ulations.
3. The protective conductor (PE) has been connected and, if necessary, the external
earth connection between housing and ground has been effected, e.g. for avoiding
electrostatic discharge.
4. Monitoring systems have been actuated e.g., “Flow Monitoring” and “Overheat Pro-
tection”.
5. The medium to be heated, is in accordance with the heater design.
At the cable entries temperatures exceeding 70°C are not admissible.
The minimum temperature rating for all incoming cables is 70°C
NOTICE
Before switching the heater on, check that the rated process
flow is running.
The construction materials used are chosen in accordance
with the operating conditions specified.
Should the heater be operated with other media or tempera-
tures than those specified, warranty expires immediately.

JEVI A/S
IOM 08099901
EN, DE
11-2022
______________________________________________________________________
19
9.0 Maintenance instructions
The one-year service interval only applies if the heater is installed in a dry and clean en-
vironment. If installed in environment which does not meet these requirements, the ser-
vice intervals might have to be reduced.
The responsible for the maintenance must ensure that his employees are fully trained
and supervised in the proper working procedures to ensure their safety.
1. Check the ceramic insulators on the elements for damage.
2. Check the insulation resistance of the heating elements.
Connect the Megger to an earth bolt and one of the phases U1, V1 or W1. If the
measured value is less than 2 Mega ohms, each heating element will have to be
checked separately. Minimum value is 10 Mega ohms at 1000 volts.
*The Ex-certificate together with the IOM is documentation and as soon as equipment is
ATEX and/or IECEx-marked and certified, shall the manufacturer always be contacted
before any repair jobs are planned to get the correct instruction or approval to make the
repair job.
If this is not followed, the certification will be voided.
*Text also references to page 19
Other manuals for EFF
1
This manual suits for next models
12
Table of contents
Languages:
Other Jevi Electric Heater manuals
Popular Electric Heater manuals by other brands

Holmes
Holmes FamilySafe HFH5717 owner's guide

BizHomart
BizHomart W914-40F instruction manual

Olimpia splendid
Olimpia splendid Unico Air R410A Instructions for use and maintanence

HeatStar
HeatStar HSP40E Operating instructions and owner's manual

Gasmate
Gasmate EH714 instructions

Argo
Argo STING operating instructions