Johnson Controls Penn MR4 Manual

FANs 125, 121
Temperature Controls Section A
Installation Bulletin
Issue Date 1199
© 1999 Johnson Controls, Inc. 1
Part No. 24-7664-1687, Rev. A www.johnsoncontrols.com
Code No. LIT-125193
IMPORTANT: All MR4 controls are designed for
use only as operating controls.
Where an operating control
failure would result in personal
injury or loss of property, it is the
responsibility of the installer to
add devices (safety, limit
controls) or systems (alarm,
supervisory systems) that protect
against, or warn of, control
failure.
Refer to the MR Series Refrigeration Temperature
Controls Product Bulletin, LIT-125199, for necessary
information on operation and performance
specifications for this product.
Mounting
The MR4 control is not position-sensitive but should be
mounted for convenient wiring and adjustment.
To mount the Panel Mount version, ensure that there
is at least 2 3/4 inches (70 mm) space behind the
panel. Make a cutout 1 3/16 x 2 13/16 inches
(29 x 71 mm). Remove retaining clip from the control.
Insert the control into the hole. Install retaining clip and
adjust for tightness.
To mount the DIN Rail Mount version, install the DIN
rail where appropriate. Snap the control onto the rail
into position.
Repair and Replacement
Field repair of the control should not be made. In case
of a defective or improperly functioning control, check
with your nearest authorized Johnson Controls/PENN
distributor. When contacting the supplier for
replacement, state the model number of the control.
This number can be found on the data plate.
Wiring
!
WARNING: Shock Hazard. To avoid
possible electrical shock or
damage to equipment,
disconnect power supply before
wiring any connections.
Follow these wiring guidelines:
All wiring must conform to the National Electric
Code and local regulations.
Make all wiring connections using adequate gauge
copper conductors only. Connectors are rated for
14-22 AWG wiring.
Internal to Control
V1 V2
Power
Supply Compressor Evaporator
Fan Defrost
SC S2S1 DCD
Process Temperature Sensor
Binary Input
Alarm
Evaporator
Temperature
Sensor
Fr Fn Df
A1 A2
C1 C2C3
Sensor
Common Binary Common
Terminal Not Used
Refer to Rating Table for more information.
Figure 1: MR4 DIN Rail Mount Control
CSCS1 S2DV1 V2
Internal to Control
Power
Supply
Evaporator Temperature
Sensor
Binary
Input
Process Temperature Sensor
Common
Compressor
Alarm
Defrost
Evaporator
Fan
Fr A1 Df Fn
Refer to Rating Table for more information.
Figure 2: MR4 Panel Mount Control
INSTALLATION BULLETIN
MR4 Refrigeration Temperature/Defrost Control
2A—MR4 Refrigeration Temperature/Defrost Control Installation Bulletin
Use Table 1 with function So to compensate for long
sensor leads.
Table 1: Sensor Wire Size and Length
18 AWG
20 AWG
22 AWG
Offset
300-599 ft
91-183 m
190-374 ft
58-114 m
120 -239 ft
36-73 m
1F°
1C°
600-899 ft
183-274 m
375-564 ft
114-172 m
240-349 ft
73-107 m
2F°
2C°
900+ ft
274+ m
565+ ft
172+ m
350+ ft
107+ m
3F°
3C°
Table 2: Rating Table
Rating Category
120
VAC
240
VAC
24
VDC
Horsepower
1/4
1/2
-
Full Load Amperes
5.8
4.9
-
Locked Rotor Amperes
34.8
29.4
-
Inductive (non-motor)
Amperes
8
8
8
Pilot Duty VA
275
450
-
Relay outputs must not exceed 20 amperes total
connected load. Power source is 24 VAC. Alarms require
separate external power source.
FCC Compliance
This equipment has been tested and found to comply
with the limits for a Class A digital device pursuant to
Part 15 of the FCC Rules. These limits are designed to
provide reasonable protection against harmful
interference when the equipment is operated in a
commercial environment. This equipment generates,
uses, and can radiate radio frequency energy and, if
not installed and used in accordance with the
instruction manual, may cause harmful interference to
radio communications. Operation of this equipment in
a residential area is likely to cause harmful
interference, in which case the user will be required to
correct the interference at his/her own expense.
Canadian DOC Compliance
This digital apparatus does not exceed the Class A
limits for radio noise emissions from digital apparatus
set out in the Radio Interference Regulations of the
Canadian Department of Communications.
Display
Press Up and Down buttons to scroll through process
temperature, binary input status (On or OF), and
auxiliary temperature sensor reading (F2 if none). After
15 seconds of inactivity, the display shows the process
temperature.
Programming the Control
To lock and unlock the unit for programming:
Press the Enter, Up, and Down buttons
simultaneously and hold until “- - -” is
displayed. Hold for about 10 seconds until the
current temperature is displayed.
To change the setpoint:
1. Hold the Enter button for approximately
3 seconds. The display will change to
show the setpoint. Release the Enter
button.
2. Press the Up or Down button until you
reach the new setpoint.
3. Press the Enter button to save the new
setpoint.
Note: If the Enter button is not pressed after selecting the new
setpoint, the new setpoint is not saved. The control reverts
to the original setpoint.
To run the self-test procedure:
IMPORTANT: Disconnect loads before self-test
procedure. Cycle power to resume
normal operation.
Press the Up and Down buttons in sequence,
and hold for 5 seconds.
To begin a manual defrost cycle:
Hold the Defrost button for 3 seconds.
To begin a deep freeze cycle:
Press the Enter and Up buttons in sequence
and hold both for 5 seconds. The compressor
status LED will light.
To program values other than setpoint:
1. Hold the Enter button for about 10
seconds. The display changes to HY.
2. Press the Up or Down button until the
desired parameter is displayed.
3. Press the Enter button. The parameter’s
current value is displayed.
4. Press the Up or Down button until the
desired value is shown.
5. Press the Enter button to save the new
value. After 10 seconds of inactivity, the
display will return to its normal function.
Note: If the Enter button is not pressed after selecting the new
value, the new value is not saved. The control reverts to the
previous value.
A—MR4 Refrigeration Temperature/Defrost Control Installation Bulletin 3
Table 3: Functions and Settings
Function
Description
Setting Range
Default
SI:Setpoint
Primary temperature setpoint at which compressor
control contacts open on temperature fall
-40 to 158°F (-40 to 70°C)
---
HY: Hysteresis (Differential)
Temperature difference relative to setpoint at which
compressor control contacts close on temperature rise
1 to 9 F° (1 to 9 C°)
5
LL: Low Setpoint Stop
High setpoint adjustment limit
-40°F (-40°C) to HL
-25
HL: High Setpoint Stop
Low setpoint adjustment limit
LL to 158°F (70°C)
40
CC: Anti-short Cycle Delay
Minimum time between two compressor On cycles
0 to 9 minutes
1
Co: Deep Freezing Time
Time compressor forced On during deep freeze
0 to 99 minutes
60
AH: High Temperature Alarm
Temperature above setpoint where alarm is initiated
0 to 50 F° (0 to 50 C°)
10
AL: Low Temperature Alarm
Temperature below setpoint where alarm is initiated
-50 to 0 F° (-50 to 0 C°)
-10
Ad: Alarm Differential
Temperature difference between alarm On and Off
1 to 9 F° (1 to 9 C°)
5
At: Alarm Time Delay
Delay between alarm detection and activation
0 to 99 minutes
3
dF: Defrost Type
Select defrost type
0 = electric heater
1 = hot gas
0
dE: Defrost End Mode
Defrost termination type; note that defrost cycle always
ends after time set for dd
0 = time
1 = temperature
1
dt: Defrost Termination
Temperature
Only used when dE = 1; defrost ends when
temperature reaches dt
32 to 68°F (0 to 20°C)
55
di: Defrost Interval
Time between two subsequent defrost cycles; when
di=1 hour, dd cannot exceed 40 min.
1 to 99 hours
7
dd: Maximum Defrost Duration
Defrost ends after this time, even if defrost end
temperature has not been reached; 0 disables defrost
0 to 99 minutes
45
dC: Dripping Time
Time compressor stopped after defrost so evaporator
can drip
0 to 99 minutes
5
dU: First Defrost After Power Up
Time first defrost is delayed after power up
OF, 0 to 99 minutes
OF (Off)
dP: Display During Defrost
Temperature displayed during defrost cycle
0 = last reading
1 = setpoint
0
dr: Display Delay After Defrost
Time after defrost before sensed temperature displays
1 to 99 minutes
20
iF: Binary Input Function
Configuration for normally closed binary input
0 = none
1 = compres. off, alarm on
2 = alarm on
3 = fan off, alarm on, AH
and AL disabled.
0
id: Binary Input Time Delay
Time between binary input detection and enabling of
the function set through iF
0 to 99 minutes
0
FF: Fan Operating Function
Fan operation; note that the fan is always Off during
the defrost cycle
0 = parallel with compres.
1 = always on
0
Fd: Fan Start-up Delay (After
Defrost)
Time after defrost that fan is switched On, even if
temperature set through Fr has not been reached
0 to 99 minutes
5
Fr: Fan Start Temperature After
Defrost End
Evaporator sensor temperature at which the fan is
switched On after a defrost cycle
-22 to 41°F (-30 to 5°C)
40
SF: Sensor Failure Operation
Control function after a sensor or sensor wire failure
0 = compressor on
1 = compressor off
2 = based on last 4 cycles
2
So: Temperature SensorOffset
Compensate for long sensor leads
-20 to 20 F° (-20 to 20 C°)
0
Un: Temperature Units Used
Temperature units used
0 = °C 1 = °F
1
PU: Display Refresh Rate
Time after which display is refreshed
1 to 99 seconds
1
4A—MR4 Refrigeration Temperature/Defrost Control Installation Bulletin
Alarm and Fault Codes
Table 4: Error Codes and Status
Error Code (Codes will flash on the display.)
System Status
F1 Open or shorted temperature sensor
Alarm output On. Compressor runs according to SF. Cycle power
to reset.
F2 Open or shorted evaporator sensor
Alarm output On. Defrost cycle controlled by di and dd. Correct
problem to reset.
A1 Binary input open for longer than id and iF = 1
Compressor output Off. Alarm output On. Correct problem to
reset.
A2 Binary input open for longer than id and iF = 2
Alarm output On. Correct problem to reset.
A3 Binary input open for longer than id and iF = 3
Fan output Off. Alarm output On. AH and AL disabled. Correct
problem to reset.
HI Temperature has reached or exceeded
(setpoint + AH)
Alarm output On. Correct problem to reset.
LO Temperature has reached or fallen below
(setpoint –AL)
Alarm output On. Correct problem to reset.
EE Program failure
Alarm output On. Other outputs Off. Replace control.
Ordering Information
Table 5: Specifications
Power Requirements
3.7 VA @ 24 VAC 50/60 Hz, Class 2 (20-30 VAC)
Ambient Conditions
Operating 14 to 140oF (-10 to 60oC); 0 to 95% RH (non-condensing)
Storage -22 to 176oF (-30 to 80oC); 0 to 95% RH (non-condensing)
Accuracy
+1.8 F(+ 1C)
Agency Listings
UL Recognized: File E194024, CCN XAPX2
Canadian UL Recognized: File E194024, CCN XAPX8
FCC Compliant per Class A Digital Device, Part 15
Canadian DOC Compliant per Class A, Radio Interference Regulations
Table 6: Ordering Information
Product Code Number
Description
MR4PM24-12C
MR4 Panel Mount Control; 2 A99BB-200C sensors included
MR4DR24-12C
MR4 DIN Rail Mount Control; 2 A99BB-200C sensors included
A99BB-200C
Replacement Sensor, lead length: 6-1/2 ft (2 m)
The performance specifications are nominal and conform to acceptable industry standards. For application at conditions beyond these
specifications, consult Johnson Controls/Penn Refrigeration Application Engineering at (414) 274-5535. Johnson Controls, Inc. shall not be
liable for damages resulting from misapplication or misuse of its products.
Controls Group
507 E. Michigan Street
P.O. Box 423 Printed in U.S.A.
Milwaukee, WI 53201 www.johnsoncontrols.com

Other Johnson Controls Control System manuals

Johnson Controls Unisab III User manual

Johnson Controls

Johnson Controls Unisab III User manual

Johnson Controls ZZ Series User manual

Johnson Controls

Johnson Controls ZZ Series User manual

Johnson Controls SABROE Unisab III Control Installation and operation manual

Johnson Controls

Johnson Controls SABROE Unisab III Control Installation and operation manual

Johnson Controls AIM-200 User manual

Johnson Controls

Johnson Controls AIM-200 User manual

Johnson Controls CMS-1655 User manual

Johnson Controls

Johnson Controls CMS-1655 User manual

Johnson Controls Penn System 450 Series Service manual

Johnson Controls

Johnson Controls Penn System 450 Series Service manual

Johnson Controls FC-2000 Reference manual

Johnson Controls

Johnson Controls FC-2000 Reference manual

Johnson Controls MS2 Manual

Johnson Controls

Johnson Controls MS2 Manual

Johnson Controls HomeLink User manual

Johnson Controls

Johnson Controls HomeLink User manual

Johnson Controls YORK YLAA0189SE User manual

Johnson Controls

Johnson Controls YORK YLAA0189SE User manual

Johnson Controls VMA1200 Series Service manual

Johnson Controls

Johnson Controls VMA1200 Series Service manual

Johnson Controls System 450 Series Service manual

Johnson Controls

Johnson Controls System 450 Series Service manual

Johnson Controls CCXL01 Installation and operation manual

Johnson Controls

Johnson Controls CCXL01 Installation and operation manual

Johnson Controls Unisab III User manual

Johnson Controls

Johnson Controls Unisab III User manual

Johnson Controls SABROE Unisab III Control Installation and operation manual

Johnson Controls

Johnson Controls SABROE Unisab III Control Installation and operation manual

Popular Control System manuals by other brands

CYBELEC CybTouch Series user manual

CYBELEC

CYBELEC CybTouch Series user manual

Mitsubishi Heavy Industries SC-SL1N-E Data book

Mitsubishi Heavy Industries

Mitsubishi Heavy Industries SC-SL1N-E Data book

Elsner WS1 Color Installation and operation guide

Elsner

Elsner WS1 Color Installation and operation guide

Microengine XP-GT3500L quick start guide

Microengine

Microengine XP-GT3500L quick start guide

DEEP SEA ELECTRONICS DSEE400 installation instructions

DEEP SEA ELECTRONICS

DEEP SEA ELECTRONICS DSEE400 installation instructions

fadini Coral 1080 Fitting instructions

fadini

fadini Coral 1080 Fitting instructions

Festo CDPX-X-E1-W Series manual

Festo

Festo CDPX-X-E1-W Series manual

Autoquip AQ 3076-AFC3-000 Instructions-parts list

Autoquip

Autoquip AQ 3076-AFC3-000 Instructions-parts list

Whelen Engineering Company CanTrol Installation & operating guide

Whelen Engineering Company

Whelen Engineering Company CanTrol Installation & operating guide

Gentex HomeLink 2-Button Programming and information guide

Gentex

Gentex HomeLink 2-Button Programming and information guide

Beacon BM5 Series owner's manual

Beacon

Beacon BM5 Series owner's manual

Techno CNC Systems Venture Series user manual

Techno CNC Systems

Techno CNC Systems Venture Series user manual

EOS LSG 18 Assembly and operating instruction

EOS

EOS LSG 18 Assembly and operating instruction

ABB REC670 2.1 IEC Product guide

ABB

ABB REC670 2.1 IEC Product guide

HALE SAM GENERATION 2 quick start guide

HALE

HALE SAM GENERATION 2 quick start guide

ONEFINITY Elite Series Installation and operation instruction

ONEFINITY

ONEFINITY Elite Series Installation and operation instruction

Strand Vision.net RS232 user manual

Strand

Strand Vision.net RS232 user manual

Louisiana Grills Country Smokers CS Series quick start guide

Louisiana Grills

Louisiana Grills Country Smokers CS Series quick start guide

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.