TFP1401
Page 5 of 8
Design
Considerations
The automatic sprinklers and/or
nozzles, fire detection devices, manual
pull stations, and signaling devices
that are to be utilized with the Red-E
Cabinet must be UL Listed, ULC Listed,
C-UL Listed, or FM Approved, as appli-
cable. With reference to Figure 3, the
system designer must consider and
make preparations for use of a Red-E
Cabinet as follows:
• Adequate floor space to facilitate
opening of the cabinet doors
• Minimum ambient temperature of
40°F (4°C)
• Installation of a suitably sized water
supply to the water supply header
(Port B, Figure 1)
• Installation of system piping (Port A,
Figure 1) including automatic sprin-
klers and/or nozzles from the Red-E
cabinet outlet
• Installation of drains from main drain
header (Port C, Figure 1)
• Installation of the detection system
components and alarms
• Determination of air compressor size
for double interlock preaction sys-
tems as a function of system type
and volume as shown in Table B
• Power supply to Red-E Cabinet
• Separate power supply to the air
compressor
Installation
The TYCO Red-E Cabinet is to be
installed following the directions
given in the “Red-E Cabinet Install-
er’s Manual” provided with the Red-E
Cabinet. Instructions pertain to the fol-
lowing items:
• Placing the cabinet
• Connecting the system piping
• Electrical connections
• System start-up
Care and
Maintenance
The TYCO DV-5ARed E-Cabinet must
be maintained and serviced in accor-
dance with this section.
Before closing a fire protection system
main control valve for maintenance
work on the fire protection system that
it controls, permission to shut down
the affected fire protection systems
must first be obtained from the proper
authorities. All personnel who may
be affected by this decision must be
notified.
Inspection, testing, and maintenance
must be performed in accordance
with the requirements of the NFPA, and
any impairment must be immediately
corrected.
The TYCO Red-E Cabinet does not
require any regularly scheduled inspec-
tion or maintenance. The riser com-
ponents enclosed within the Red-E
Cabinet, however, must be main-
tained in accordance with their appli-
cable technical data sheet as shown in
Table A. In addition, the control panel
and automatic air supply components
must be maintained in accordance with
their applicable instructions provided
with the Red-E Cabinet.
The owner is responsible for the inspec-
tion, testing, and maintenance of their
fire protection system and devices in
compliance with this document, as well
as with the applicable standards of any
authorities having jurisdiction. Contact
the installing contractor or product
manufacturer with any questions.
Automatic sprinkler systems are rec-
ommended to be inspected, tested,
and maintained by a qualified Inspec-
tion Service in accordance with local
requirements and/or national codes.
Model
Number
Power
Rating
(kW)
60 Hz Model
Equivalent
Horsepower
Rating1
(hp)
Voltage
Electric/Electric
Actuation Electric/Pneumatic
Actuation
System Volume
@20 psi (1.36 bar) in 30 mins
gal (L)
System Volume
@40 psi (2.76 bar) in 30 mins
gal (L)
OLR12016AC-50 0.12 1/6 220-240 VAC
50 Hz
192
(727)
96
(362)
OLR25033AC-50 0.25 1/3 220-240 VAC
50 Hz
414
(1567)
207
(785)
OLR40050AC-50 0.56 1/2 220-240 VAC
50 Hz
664
(2514)
332
(1257)
OLR43075AC-50 0.75 3/4 220-240 VAC
50 Hz
989
(3743)
357
(1350)
OLR615100AC-5021.2 1220-240 VAC
50 Hz —517
(1956)
OLR915150AC-5021.5 1 1/2 220-240 VAC
50 Hz —758
(2870)
OLR1225200AC-5022 2 220-240 VAC
50 Hz —1014
(3840)
Notes
1. Denotes the equivalent model of 60 Hz compressor for part number use. 50 Hz must specically be request in ordering process. The horsepoer model equivalent is not a direct
conversion to kW. Actual conversion from kilowatts (kW) to horsepower units (hp) is based on 1 kW = 1.34102 hp.
2. For 6 in. (DN150) and 8 in. (DN200) cabinets only.
TABLE C
50 HZ AIR COMPRESSOR SELECTION CRITERIA
FOR DOUBLE INTERLOCK PREACTION SYSTEM ARRANGEMENTS
BASED ON SYSTEM TYPE AND VOLUME